NOTE:  Power must not be applied to the unit when changing functionality on 

the shunts.

WIRING NOTES

•   Power-limited circuits must employ type FPL, FPLR, or FPLP cable as 

required by Article 760 of the NEC.

•   All wiring must be in accordance with the NEC, NFPA 72 and all other 

applicable codes and standards. All external power supplies must be 
power limited with battery back-up. All external power supplies and 
detectors must be UL listed for fire protection signaling applications.

PROGRAMMING

Connect the module to listed-compatible control panels only. Refer to panel 
installation documentation to confirm compatibility. 
The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.  

FIGURE 7. 

 

TENS

0

7 8

6

5

4

3

2

1

9

10

11

12

13

14

15

 C0227-00

  3 

I56-1806-010 

  

7/1/2022

from the end of wire, sliding the bare end of the wire under the clamping 
plate screw.  

3.   Set the address on the modules per the job drawing. Use the rotary code 

switches to set the address of the first module (between 01 and 154).

In Class B operation, the remaining modules are automatically assigned to the 
next five higher addresses. For example, if the base address switch is set to 28, 
the next five modules will be addressed to 29, 30, 31, 32 and 33.
The module is shipped in Class B position, remove shunts for Class A. When 
operating in Class A, alternate modules are paired together (+0/+1, +2/+3, 
+4/+5), resulting in a total of three modules. For example, if the base ad-
dress switch is set to 28, then 30 and 32 will be automatically assigned to the 
modules while 29, 31 and 33 are available to be used for other modules on the 
SLC. For Class A and B operation, DO NOT set the lowest address above 154, 
as the other modules will be assigned to nonexistent addresses.
NOTE: The XP6-MA must have power cycled for shunt changes to take effect.
NOTE: Some panels support extended addressing. In order to set the module 
above address 99 on compatible systems, carefully remove the stop on the 
upper rotary switch (see Figure 7). If the panel does not support extended ad-
dressing, do not set the lowest address above 94.
4.   A shunt is provided to disable a maximum of two unused modules in 

Class B operation and Class A operation. Modules are disabled from the 
highest address and work downward.  If two modules are disabled, the 
lowest four addresses will be functional, while the highest two will be 
disabled. For example, in Class B operation, if the shunt for Address Dis-
able is placed on “two” and the base switch is set to 28, the modules will 
be assigned to 28, 29, 30 and 31 while disabling the highest two positions.

NOTE:  Place unused shunts on single pin to store on board for future use.

0

1

2

3

4

5 6

7 8 9

BASE ADDRESS

TO NEXT DEVICE 

STATUS

INDICATORS

   

  +

   

  +

+0

+1

IDC

ADDRESS

   

  +

   

  +

+2

+3

IDC

ADDRESS

   

  +

   

  +

+4

+5

IDC

ADDRESS

SLC

   

  +

   

  +

+

+

FROM PANEL OR

PREVIOUS DEVICE

3.9K EOL

RESISTOR

(INCLUDED)

CONNECT MODULES TO

LISTED COMPATIBLE

NOTIFIER CONTROL 

PANELS ONLY

SIGNAL LINE CIRCUIT 32 VDC MAX.

SEE PANEL INSTRUCTION MANUAL

FOR WIRE REQUIREMENTS.

CLASS B IDC (TYPICAL)

A/B SELECT

A/B SELECT

DISABLE 1

DISABLE 2

+

+

T6

T5

DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE  MODULE.

INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

(–)

(+)

IN

OUT

   

  +

   

  +

EXTERNAL SUPP

LY

0

1

2

3

4

5 6

7 8 9

POWER-LIMITED

AND SUPERVISED

POWER TO THE NEXT INTERFACE

MODULE MUST BE EXTERNALLY

SWITCHED TO RESET THE DETECTORS.

AN FRM-1 RELAY CONTROL MODULE CAN BE 

USED TO SWITCH POWER FROM A 

STANDARD POWER SUPPLY. SEE FIGUR 10.

1.   To use a common power supply between multiple XP6-MA modules, connect a long power supply jumper from T5 or T6 to T5 or 

T6 on the adjacent XP6-MA module. 

FIGURE 8. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS B

C0154-02

FIGURE 9. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS A

0

1

2

3

4

5 6

7 8 9

BASE ADDRESS

TO NEXT DEVICE

STATUS

INDICATORS

   

  +

   

  +

+0

+1

IDC

ADDRESS

   

  +

   

  +

+2

+3

IDC

ADDRESS

   

  +

   

  +

+4

+5

IDC

ADDRESS

SLC

   

  +

   

  +

+

+

FROM PANEL OR

PREVIOUS DEVICE

CONNECT MODULES TO LISTED COMPATIBLE

NOTIFIER CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT 32 VDC MAX.

SEE PANEL INSTRUCTION MANUAL

FOR WIRE REQUIREMENTS.

CLASS A IDC (TYPICAL)

A/B SELECT

A/B SELECT

DISABLE 1

DISABLE 2

0

1

2

3

4

5 6

7 8 9

10

11

12

13

14

15

+

+

IDC 2

IDC 3

(–)

(+)

POWER TO THE NEXT INTERFACE

MODULE MUST BE EXTERNALLY

SWITCHED TO RESET THE DETECTORS.

AN FRM-1 RELAY CONTROL MODULE CAN BE

USED TO SWITCH POWER FROM A

STANDARD POWER SUPPLY. SEE FIGURE 10.

T6

T5

IN

OUT

   

  +

   

  +

EXTERNAL SUPP

LY

POWER-LIMITED

AND SUPERVISED

Detectors must be UL Listed compatible with the module. Install detectors 
per manufacturer’s installation instructions.

C0160-01

1.   To select Class A, remove the 

two shunts from the “A/B se-
lect” positions.

2.   

To use a common power 
supply between multiple 
XP6-MA modules, connect 
a long power supply jumper 
from T5 or T6 to T5 or T6 on 
the adjacent XP6-MA mod-
ule. 

Содержание NOTIFIER XP6-MA

Страница 1: ... B position remove shunts for Class A 1 I56 1806 010 7 1 2022 XP6 MA Six Zone Interface Module SPECIFICATIONS Normal Operating Voltage 15 32VDC Stand By Current 2 3 mA 24 V Alarm Current 40 mA assumes all six LEDs solid on Temperature Range 32ºF to 120ºF 0ºC to 49ºC Humidity 10 to 93 Non condensing Dimensions 6 8 H x 5 8 W x 1 25 D Accessories CHS 6 Chassis BB 25 Cabinet BB XP Cabinet CAB 4 Series...

Страница 2: ...o that all of the status indicators are visible Cabinets A BB 25 CAB 3 or CAB 4 Series cabinet will house the CHS 6 chassis with up to six XP6 MA modules installed on it Refer to cabinet installation documents for dimensions The BB XP cabinet houses one or two XP6 MA modules on the internal chas sis that is part of the cabinet Refer to cabinet installation documents for dimensions INSTALLATION STE...

Страница 3: ...d work downward If two modules are disabled the lowest four addresses will be functional while the highest two will be disabled For example in Class B operation if the shunt for Address Dis able is placed on two and the base switch is set to 28 the modules will be assigned to 28 29 30 and 31 while disabling the highest two positions NOTE Place unused shunts on single pin to store on board for futu...

Страница 4: ...rantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment ...

Отзывы: