BEFORE INSTALLING

If the modules will be installed in an existing operational system, inform the 
operator and local authority that the system will be temporarily out of service. 
Disconnect the power to the control panel before installing the modules. This 
system contains static sensitive components. Always ground yourself with a 
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The module housing should also be grounded.
NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

The XP6-MA Six Zone Interface Module is intended for use in an intelligent 
alarm system. Each module provides an interface between the intelligent 
alarm system and a conventional alarm system loop. A common SLC input is 
used for all modules, and the initiating device loops share a common super-
visory supply and ground. Otherwise, each monitor operates independently 
from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module 
from 01 to 154. The remaining modules are automatically assigned to the next 
five higher addresses. Provisions are included for disabling a maximum of two 
unused modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled bicolor LED indicators. The panel can cause the 
LEDs to blink, latch on, or latch off.
A list of compatible two-wire System Sensor Smoke detectors for use with the 
XP6-MA is available on the System Sensor website at www.systemsensor.com.

Included:

 

(5) 1 x 4 Terminal Blocks            (2) 1.25" Stand offs           (3) Shunts

               

                        

                    

(4) Machine Screws        (2) Nuts       (1) Long Power Supply Jumper

   

           

                  

(6) 3.9k Ohm End of Line Resistors

         

 C0202-00

Shipped on Board:

 

(2)  Shunts in Class A/B position 
(Shipped in Class B position, remove shunts for Class A)

  1 

I56-1806-010 

  

7/1/2022

XP6-MA Six Zone Interface Module

SPECIFICATIONS

Normal Operating Voltage: 

15-32VDC

Stand-By Current: 

2.3 mA @ 24 V

Alarm Current: 

40 mA (assumes all six LEDs solid on)

Temperature Range: 

32ºF to 120ºF ( 0ºC to 49ºC)

Humidity: 

10 to 93% Non-condensing

Dimensions: 

6.8˝H x 5.8˝W x 1.25˝D

Accessories: 

CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-4 Series Cabinets; CAB-3 Series Cabinets

Wire Gauge: 

12-18 AWG

Maximum IDC Wiring Resistance: 

25 Ohms

External Power Supply Voltage: 

Regulated 24 VDC

Ripple Voltage: 

0.1 volts RMS maximum

IDC (supervised and power limited)
 

DC Voltage: 

18-28 volts power limited

 Frequency: 

DC

 

Alarm Current: 

90mA per circuit

 

Standby Current 6 circuits:  

42mA Maximum @18 VDC

 

 

56mA Maximum @24 VDC

 

 

66mA Maximum @28 VDC

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
Notifier system control panel (list available from Notifier).

COMPONENTS

Following are descriptions of the XP6-MA mounting frameworks. There are 
two mounting options for XP6-MA modules:

•   Up to six XP6-MA modules can be installed on a CHS-6 in a CAB-3 

Series, CAB-4 Series or BB-25 cabinet

•  One or two XP6-MA modules can be installed in a BB-XP cabinet

Chassis 

The CHS-6 chassis is used to mount XP6-MA modules in a BB-25, CAB-3 or 
CAB-4 Series cabinet. It accommodates up to six XP6-MA modules in a single 
cabinet row three modules wide and two modules deep.

FIGURE 1. CHS-6 CHASSIS

 

MOUNT WITH

SELF-THREADING SCREWS 

TO BACK OF CABINET

 C0236-01

The BB-XP cabinet has a built-in chassis that will accommodate one or two 
XP6-MA modules.

FIGURE 2. BB-XP CABINET

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

10

11

12

13

14

15

B

A

S

E

 A

D

D

R

E

S

S

A

D

D

R

E

S

S

D

IS

A

B

LE

N

O

N

E

ON
E

TW

O

THR
EE

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

10

11

12

13

14

15

B

A

S

E

 A

DDRE

S

S

A

DD
R

E

S

S

DI

S

A

B

LE

NONE

ON
E

TW

O

THR
EE

C0234-00

I56-1806-0

10

INSTALLATION AND MAINTENANCE INSTRUCTIONS

12 Clintonville Road

Northford, CT 06472-1653

Phone: 203.484.7161

Содержание NOTIFIER XP6-MA

Страница 1: ... B position remove shunts for Class A 1 I56 1806 010 7 1 2022 XP6 MA Six Zone Interface Module SPECIFICATIONS Normal Operating Voltage 15 32VDC Stand By Current 2 3 mA 24 V Alarm Current 40 mA assumes all six LEDs solid on Temperature Range 32ºF to 120ºF 0ºC to 49ºC Humidity 10 to 93 Non condensing Dimensions 6 8 H x 5 8 W x 1 25 D Accessories CHS 6 Chassis BB 25 Cabinet BB XP Cabinet CAB 4 Series...

Страница 2: ...o that all of the status indicators are visible Cabinets A BB 25 CAB 3 or CAB 4 Series cabinet will house the CHS 6 chassis with up to six XP6 MA modules installed on it Refer to cabinet installation documents for dimensions The BB XP cabinet houses one or two XP6 MA modules on the internal chas sis that is part of the cabinet Refer to cabinet installation documents for dimensions INSTALLATION STE...

Страница 3: ...d work downward If two modules are disabled the lowest four addresses will be functional while the highest two will be disabled For example in Class B operation if the shunt for Address Dis able is placed on two and the base switch is set to 28 the modules will be assigned to 28 29 30 and 31 while disabling the highest two positions NOTE Place unused shunts on single pin to store on board for futu...

Страница 4: ...rantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment ...

Отзывы: