The front XP10-M module positions of each chassis are offset below the rear 
XP10-M module positions so that all of the status indicators are visible.

CABINETS

A BB-25, CAB-3 or CAB-4 Series cabinet will house the CHS-6 chassis with up 
to six XP10-M modules installed on it. Refer to cabinet installation documents 
for dimensions.

The BB-XP cabinet houses one or two XP10-M modules on the internal chassis 
that is part of the cabinet.  Refer to cabinet installation documents for dimen-
sions. 

INSTALLATION STEPS

1.  Cabinet Mounting

 

 In a clean, dry area, mount the backbox using the four holes provided in 
the back surface of the cabinet (Figure 3).

2.  Chassis Installation

 

 The CHS-6 chassis is mounted in the BB-25, CAB-3 or CAB-4 Series cabi-
net. It is shipped with two self-threading screws, which are used to fas-
ten the chassis to the back wall of the cabinet (see Figure 4).

The BB-XP cabinet comes with the chassis already installed, so no mounting 
is necessary.

FIGURE 3. TYPICAL MOUNTING HOLE LOCATIONS:

 

 

 

 

    

FIGURE 4. MOUNTING THE CHS-6 CHASSIS:

3.  Module Installation

 

 There are two methods for installing a module in the rear position of a 
chassis. Method one is for installation of a rear module only, when no 
module will be installed in front of it. Refer to Figure 5 for instructions. 
Method two is for installation of a rear module when another module 
will be installed in the chassis position in front of it.  Refer to Figures 6a 
and 6b for method two. All necessary screws and standoffs are supplied 
with the modules.

FIGURE 5. INSTALLATION OF REAR MODULE ONLY, METHOD ONE:

Step 1:   Insert the bottom of the XP10-M module down into a rear slot on the 

chassis. 

Step 2:   Carefully swing the upper edge of the board back towards the back of 

the chassis until it touches the two standoffs.

Step 3:  Align two 4-40 screws with the two standoffs and tighten.
Step 4:   Address and wire the modules according to the instructions in this 

manual.

The steps in Figures 6A  – 6C describe and illustrate module installation when 
the rear chassis position and the position in front of it will be filled.  Front 
position installation is possible only if the rear position is filled with an XP 
module.

FIGURE 6A. INSTALLATION OF XP10-M MODULE IN A REAR CHASSIS 
POSITION, METHOD TWO:

Step 1:   Install two long standoffs in the lower mounting holes using two 4-40 

nuts as shown.

FIGURE 6B. 

N500-77-00  2 I56-1803-010

C0237-00

C0235-00

C0236-00

C0225-01

BACKBOX

MOUNTING

HOLES

2

3

1

MOUNT WITH

SELF-THREADING SCREWS 

TO BACK OF CABINET

1

C0249-01

3

2

4

Step 2:   Insert the bottom of the XP10-M module down into a rear slot on the 

chassis.

Step 3:   Carefully swing the upper edge of the board back towards the back of 

the chassis until it touches the two standoffs on the board.

Step 4:   Align two 4-40 screws with the two standoffs on the chassis and 

tighten.

Step 5:   Address and wire the modules according to the instructions in this 

manual.

Содержание NOTIFIER XP10-M

Страница 1: ...ules This system contains static sensitive components Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re moved from the body The housing cabinet should be metallic and suitably grounded NOTICE This manual should be left with the owner user of this equipment GENERAL DESCRIPTION The XP10 M Ten Input Monitor Module is intended for use in an int...

Страница 2: ... will be installed in the chassis position in front of it Refer to Figures 6a and 6b for method two All necessary screws and standoffs are supplied with the modules FIGURE 5 INSTALLATION OF REAR MODULE ONLY METHOD ONE Step 1 Insert the bottom of the XP10 M module down into a rear slot on the chassis Step 2 Carefully swing the upper edge of the board back towards the back of the chassis until it to...

Страница 3: ...at may cause undesired operation NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordanc...

Страница 4: ...lation instructions NOTE Any number of UL listed contact closure devices may be used DO NOT mix fire alarm initiating and supervisory devices on the same initiating device circuit Install contact closure devices per manufacturer s installation instructions BASE ADDRESS TO NEXT DEVICE STATUS INDICATORS IDC ADDRESS 0 1 2 3 4 5 6 7 8 9 IDC ADDRESS IDC ADDRESS IDC ADDRESS IDC ADDRESS SLC FROM PANEL OR...

Отзывы: