Honeywell Notifier NZM-100-6 Скачать руководство пользователя страница 4

0

1

2

3

4

5 6

7 8 9

BASE ADDRESS

TO NEXT DEVICE 

STATUS

INDICATORS

   

  +

   

  +

   

  +

   

  +

   

  +

   

  +

IN

OUT

+0

+1

+2

+3

+4

+5

IDC

ADDRESS

IDC

ADDRESS

IDC

ADDRESS

   

  +

   

  +

SLC

   

  +

   

  +

+

+

FROM PANEL OR

PREVIOUS DEVICE

3.9K EOL

RESISTOR

(INCLUDED)

CONNECT MODULES TO

LISTED COMPATIBLE

FIRE•LITE CONTROL

PANELS ONLY

SIGNAL LINE CIRCUIT 32 VDC MAX.

TWISTED PAIR IS RECOMMENDED.

CLASS B IDC (TYPICAL)

A/B SELECT

A/B SELECT

DISABLE 1

DISABLE 2

0

1

2

3

4

5 6

7 8 9

10

11

12

13

14

15

+

+

T6

T5

DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE  MODULE.

INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

(–)

(+)

TO PANEL CONTROLLED

RESETTABLE POWER SUPPLY

EXTERNAL SUPPL

Y

POWER-LIMITED

AND SUPERVISED 

1.  To use a common power supply between multiple NZM-100-6 

modules, connect a long power supply jumper from T5 or T6 
to T5 or T6 on the adjacent NZM-100-6 module. 

1.  To select Class A, remove the two shunts from the “A/B select” positions.
2.   To use a common power supply between multiple NZM-100-6 modules, 

connect a long power supply jumper from T5 or T6 to T5 or T6 on the 
adjacent NZM-100-6 module. 

0

1

2

3

4

5 6

7 8 9

BASE ADDRESS

TO NEXT DEVICE

STATUS

INDICATORS

   

  +

   

  +

   

  +

   

  +

   

  +

   

  +

IN

OUT

+0

+1

+2

+3

+4

+5

IDC

ADDRESS

IDC

ADDRESS

IDC

ADDRESS

   

  +

   

  +

SLC

   

  +

   

  +

+

+

FROM PANEL OR

PREVIOUS DEVICE

CONNECT MODULES TO LISTED COMPATIBLE

FIRE•LITE CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT 32 VDC MAX.

TWISTED PAIR IS RECOMMENDED.

CLASS A IDC (TYPICAL)

A/B SELECT

A/B SELECT

DISABLE 1

DISABLE 2

0

1

2

3

4

5 6

7 8 9

10

11

12

13

14

15

T6

T5

IDC 2

IDC 3

(–)

(+)

EXTERNAL SUPPL

Y

POWER-LIMITED

AND SUPERVISED 

+

+

TO PANEL CONTROLLED

RESETTABLE POWER SUPPLY

FIGURE 8. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS B

FIGURE 9. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS A

Detectors must be UL listed compatible with the module. Install detectors per 
manufacturers installation instructions.

C0779-04

C0780-03

  4 

I56-2990-004 

 

 

  7/1/2022

Содержание Notifier NZM-100-6

Страница 1: ...1151 A SYSTEM SENSOR B110LP B401 20 1451 A SYSTEM SENSOR B401 B401B 20 1451DH A SYSTEM SENSOR DH400 20 2151 A SYSTEM SENSOR B110LP B401 20 2451 A SYSTEM SENSOR DH400 B401B B401 20 2451TH A SYSTEM SENSOR B401 B401B 20 5451 A SYSTEM SENSOR B401 20 1100 A SYSTEM SENSOR N A 20 1400 A SYSTEM SENSOR N A 20 2100AT A SYSTEM SENSOR N A 20 2100B A SYSTEM SENSOR N A 20 2100D A SYSTEM SENSOR N A 20 2100S A SY...

Страница 2: ...fset below the rear NZM 100 6 module positions so that all of the status indicators are visible C0235 00 Cabinets A BB 25 CAB 3 or CAB 4 Series cabinet will house the CH 6 chassis with up to six NZM 100 6 modules installed on it Refer to cabinet installation docu ments for dimensions The BB XP cabinet houses one or two NZM 100 6 modules on the internal chassis that is part of the cabinet Refer to ...

Страница 3: ... if the base address switch is set to 28 the next five modules will be addressed to 29 30 31 32 and 33 FIGURE 7 TENS 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 C0227 00 The module is shipped in Class B position remove shunts for Class A When operating in Class A alternate modules are paired together 0 1 2 3 4 5 resulting in a total of three modules For example if the base ad dress switch is set to 28 t...

Страница 4: ...lect Class A remove the two shunts from the A B select positions 2 To use a common power supply between multiple NZM 100 6 modules connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent NZM 100 6 module 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS TO NEXT DEVICE STATUS INDICATORS IN OUT 0 1 2 3 4 5 IDC ADDRESS IDC ADDRESS IDC ADDRESS SLC FROM PANEL OR PREVIOUS DEVICE CONNECT MODULES TO L...

Страница 5: ...NAL SUPPLY EXTERNAL POWER SUPPLY PCB 1 PCB 2 VIEW A A 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 FIGURE 10 EXAMPLE OF MULTIPLE BOARDS SHARING SAME EXTERNAL SUPPLY Refer to figures 8 and 9 for typical wiring Make certain lip on long power supply jumper engages retaining tab on T5 or T6 as shown in Vie...

Страница 6: ...mined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV techni...

Отзывы: