Honeywell Notifier M710E-CZR Скачать руководство пользователя страница 1

N200-505-00

I56-4421-000

This manual is intended as a quick reference installation guide.  Please refer to the 

control panel manufacturers installation manual for detailed system information.
The M700 series of modules are a family of microprocessor controlled interface 

devices permitting the monitoring and/or control of auxiliary devices.The M710E-CZR 

is used to link a zone of conventional devices to an intelligent system controlled by 

an addressable panel. The CZR has a resistor built in, making it especially suitable 

for connection to a conventional zone that operates in a hazardous area requiring 

intrinsically safe (IS) equipment.

The  module  must  only  be  connected  to  Notifier  control  panels  using  analogue 

addressable communication protocols for monitoring and control. The module is 

compatible with System Sensor intrinsically safe sensors mounted in the B401 base, 

for use with these barriers: 
MTL model MTL4561, MTL5561 and Fuchs model KFD0-CS-EX1.51P, 

KFD0-CS-EX2.51P.

NOTE:

 When an intrinsically safe system is used on the loop, a short on the sensor 

side of the barrier will result in an alarm. Only a short on the module side of the safety 

barrier will generate a fault signal.
A single tri-colour LED indicates the status of the module. In normal conditions, the 

LED can be set by command from the control panel to blink green when the module 

is polled. In the case of a fire alarm on the conventional zone, the LED is switched 

on constant red by panel command. If a fault is detected on the conventional zone or 

the zone supply voltage drops below 12 V, or a fault with the external power supply 

is signalled, the LED will blink yellow if enabled on the control panel. When a short 

circuit is detected on the loop to either side of the module, the LED is switched to show 

a constant yellow light. 
This module does not require maintenance.

SPECIFICATIONS

Intelligent Loop

 

Operating Voltage Range: see S00-7100

LED Cutoff Voltage: 16.5 V

Max. Standby Current (@24 V and 25

o

C) External Supply Conventional Zone: 

 

No Communication: 

120 µA

Max. Standby Current (@24 V and 25

o

C) Conventional Zone connected to resistive 

EOL only (no detectors), Loop Powered Conventional Zone: 

 

No Communication: 

6.3 mA

LED Current (Red): 

1.3 mA

LED Current (Yellow): 

4.5 mA

Isolator Features:  see S00-7100

Conventional Zone

External Supply Voltage:  

12 to 28.5 V

 

18 to 28.5 V if conventional zone is loop powered

Maximum Standby Load Current:   2.8 mA for detectors at 18 V 

 

3.8 mA for detectors at 24 V

Maximum Zone Load:  

60 mA (limited internally)

Maximum Conventional Line Resistance: 50 Ω

End of Line Resistor:  

3.9 kΩ, 5% (supplied)

General 

Humidity: 

5% to 95% relative humidity (non-condensing)

Ingress protection: 

IP44 (Mounted in M200E-SMB)

Maximum Wire Gauge: 

2.5 mm²

INSTALLATION

M700 series modules can be mounted in several ways (See 

Figure 1

):

1:1

  An  M200E-SMB  custom  low  profile  surface-mounting  box. The  SMB  Base  is 

affixed to mounting surface, and then the module and cover are screwed onto 

the base using the two screws supplied. Box dimensions: 132 mm (H) x 137 mm 

(W) x 40 mm (D)

1:2

  The DIN bracket on top allows mounting onto standard 35 mm x 7.5 mm "Top Hat" 

DIN rail inside a control panel or other suitable enclosure. Install and remove as 

shown in Figure 1:2

Wiring to all series M700 modules is via plug in type terminals capable of supporting 

conductors up to 2.5 mm²

CAUTION

Disconnect loop power before installing modules or sensors. 

The module address is selected by means of rotary decade address switches (see 

Figure 3

).  A screwdriver should be used to rotate the wheels to select the desired 

address, either from the front or the top of the module. 

Note:

 The number of addresses available will be dependent on panel capability, 

check the panel documentation for information on this.  

Short Circuit Isolators 

All M700 series modules are provided with short circuit monitoring and isolators on the 

intelligent loop.  If required the isolators may be wired out of the loop to facilitate the 

use of the modules on high current loaded loops, for example if sounders are used.  

To achieve this, the loop out positive should be wired to terminal 5 rather than terminal 

2. See 

Figure 2

 for details.

M710E-CZR

INSTALLATION INSTRUCTIONS - M710E-CZR 

CONVENTIONAL ZONE INTERFACE MODULE

EN

-20°C

60°C

Fig./Abb. 2

M710E-CZR

Fig./Abb. 3

Honeywell Building Technologies, Building 5 Carlton Park, King Edward Avenue, Narborough, Leicester LE19 3EQ

M710E-CZR

M200E-SMB

Lift

Sollevare

Levantar

Anheben

Push down

Premere

Precionar 

hacia abajo

Runterdrücken

Rotate  /  Ruotare

Girar  /

  

Drehen

Rotate

Ruotare

Girar

Drehen

Clip / Agganciare

Acoplar /

 

Einrasten

Plug

Inserire

Conectar

Einhaken

2

3

1

1

3

2

1:2 DIN

1:1 M200E-SMB

Fig./Abb.  1

Notifier by Honeywell

Pittway Tecnologica S.r.l

Via Caboto 19/3

34147 Trieste, Italy

DOP-IOD101

EN 54-17: 2005, EN 54-18: 2005 

0905  22

Содержание Notifier M710E-CZR

Страница 1: ...Zone External Supply Voltage 12 to 28 5 V 18 to 28 5 V if conventional zone is loop powered Maximum Standby Load Current 2 8 mA for detectors at 18 V 3 8 mA for detectors at 24 V Maximum Zone Load 60 mA limited internally Maximum Conventional Line Resistance 50 Ω End of Line Resistor 3 9 kΩ 5 supplied General Humidity 5 to 95 relative humidity non condensing Ingress protection IP44 Mounted in M200...

Страница 2: ... standby a 24 V e 25o C zona convenzionale collegata esclusivamente a resistenza di fine linea EOL nessun rilevatore zona convenzionale alimentata dal loop Nessuna comunicazione 6 3 mA LED corrente rosso 1 3 mA sul comando del pannello LED corrente giallo 4 5 mA in modalità isolamento Caratteristiche dell Isolatore vedere S00 7100 Zona convenzionale Tensione di alimentazione esterno 12 28 5 V 18 2...

Страница 3: ...i la zona convencional se alimenta del lazo es necesario conectar la línea de comunicaciones a los terminales de la fuente de alimentación de zona además de las entradas del lazo Obsérvese que si se produce un cortocircuito en el lazo de comunicaciones en la parte en que se alimenta la zona convencional se indicará como una avería de pérdida de alimentación de zona en la central a través del tramo...

Страница 4: ...ckverbinder mit einem Kabelquerschnitt von max 2 5 mm ACHTUNG Vor der Installation von Meldern oder Modulen ist die Ringleitung spannungsfrei zu schalten Die Moduladresse wird mit einem geeigneten Schraubendreher an dem Drehschalter eingestellt siehe Abbildung 3 Dieser kann von der vorne oder der rechten Seite des Moduls erreicht werden Anmerkung Einige Brandmelderzentralen können nur 99 Adressen ...

Отзывы: