1

I56-3674-001

M710-CZR

Notifier Ltd., Charles Avenue, Burgess Hill, West Sussex, RH15 9UF, UK

INSTALLATION INSTRUCTIONS FOR 

M710-CZR CONVENTIONAL ZONE 

INTERFACE MODULE

This manual is intended as a quick reference installation guide.  Please refer to the Notifier 
control panel installation manual for detailed system information.

GENERAL INFORMATION

The M700 modules are a family of microprocessor controlled interface devices permitting 
the monitoring and/or control of auxiliary devices.  The M710-CZR is used to link a zone 
of conventional (used in this document to mean non-addressable) devices to an intelligent 
system  controlled  by  an  addressable  panel.    The  CZR  has  a  resistor  built  in,  making  it 
especially suitable for connection to a conventional zone that operates in a hazardous area 
requiring intrinsically safe equipment.
The module must only be connected to control panels using the Notifier proprietary addressable 
communication  protocol  for  monitoring  and  control. The  module  is  compatible  with  System 
Sensor intrinsically safe sensors mounted in the B401 base, for use with these barriers: MTL 
models 4561 and 5561, P Fuchs models KFDO-CS-Ex1.51P and KFDO-CS-Ex2.51P. 

NOTE

: When an intrinsically safe system is used on the loop, a short on the sensor side of the 

barrier will result in an alarm. Only a short on the module side of the safety barrier will 
generate a fault signal.

SPECIFICATIONS

Addressable Loop:

Loop Voltage Range with isolator: 

15 to 28 VDC (Min 17.5VDC to ensure LED 
operation)

Loop Voltage Range (Isolator disabled) 

15 to 30 VDC (Min 17.5VDC to ensure LED 
operation)

 

 

18 to 32 VDC if conventional zone is loop powered

Maximum Standby Current at 24VDC, with external supply for conventional zone: 
 

No Communications 

288µA

 

Communication with LED blink enabled  500µA (One communication each 5s)

 

Read 16 sec. LED blink 8 sec 

388µA

Maximum standby current at 24VDC, conventional zone connected to resistive EOL only (no 
detectors), loop powered conventional zone:
 

No Communications 

6.5mA

 

Communication with LED blink enabled  6.7mA (One communication each 5s)

 

Read 16 sec. LED blink 8 sec 

6.6mA

LED Current (Red, Max at 24V) 

2.2mA (On panel command)

LED Current (Yellow, Max at 24V) 

8.8mA (In isolation mode)

Maximum rated continuous current with the switch closed (Ic max) 

1A

Maximum rated switching current (under short circuit) (Is max)    

1A

Maximum leakage current (IL max) with the switch open (isolated state)   15mA
Maximum series impedance with the switch closed (Zc max)  

130 m ohm at 15Vdc

Conventional Zone

External Supply Voltage 

12 to 28.5 VDC

 

 

18 to 28.5 VDC if conventional zone is loop powered

Maximum Standby Load Current 

2.8 mA for detectors at 18 VDC

 

 

3.8 mA for detectors at 24 VDC

Maximum Zone Load 

60mA (Limited internally)

Maximum Conventional Line Resistance 

50 Ohms

End of Line Resistor 

3.9 K Ohms, 5% (Supplied)

General

Operating Temperature 

-20°C to 60°C

Humidity 

5% to 95% Relative Humidity

Module Dimensions (including terminal block)  93mm (H) x 94mm (W) x 23mm (D)
Surface Mount Box Dimensions 

132mm (H) x 137mm (W) x 40mm (D)

Weight (Module Only) 

110g

Weight (Module and M200E-SMB) 

252g

Ingress protection 

IP50 (Mounted in M200E-SMB)

Maximum Wire Gauge 

2.5mm²

INSTALLATION

For mounting the M710-CZR module see figure 1.
Wiring  to  all  series  M700  modules  is  via  plug  in  type  terminals  capable  of  supporting 
conductors up to 2.5mm²

CAUTION

Disconnect loop power before installing modules or sensors

The module address is selected by means of rotary decade address switches (see figure 2).  
These can be accessed either from the front or the top of the module.  A screwdriver should 
be used to rotate the wheels to select the desired address, either from the front, or the top 
of the module. (Note: The number of addresses available will be dependent on panel capability, 
check the panel documentation for information on this). 

Short Circuit Isolators 

All  M700  series  modules  are  provided  with  short  circuit  monitoring  and  isolators  on  the 
intelligent loop.  If required the isolators may be wired out of the loop to facilitate the use of 
the modules on high current loaded loops, for example if sounders are used.  To achieve 
this, the loop out positive should be wired to terminal 5 rather than terminal 2.  See figure 
3 for details.
A single tri-colour LED indicates the status of the module.  In the case of a fire alarm on 
the conventional zone, the LED is switched on constant red by panel command.  If a fault 
is detected on the conventional zone or the zone supply voltage drops below 12V, or a fault 
with the external power supply is signalled, the LED will blink yellow.  When a short circuit 
is detected on the loop to either side of the module, the LED is switched to show a constant 
yellow light.

M710-CZR Wiring

See figure 3.
The M710-CZR can be wired so as to power the conventional zone either from an external 
supply, or directly from the communications loop provided it can supply sufficient current.  
When  using  an  external  power  supply,  the  conventional  zone  is  fully  isolated  from  the 
communications loop.  
If  the  conventional  zone  is  to  be  powered  from  the  loop,  it  is  necessary  to  connect  the 
communication  line  to  the  zone  power  supply  terminals  in  addition  to  the  loop  inputs.  
Note  that  if  a  short  circuit  occurs  on  the  communications  loop  on  the  side  powering  the 
conventional zone, it will be reported as a conventional zone loss of power supply fault to the 
control panel, via the non-isolated leg of the loop.

CAUTION

Electrostatic Sensitive Device

Observe precautions when handling and making connections.

FIGURE 1: MODULE MOUNTING METHODS

M200E-SMB Surface Mount Box

Surface Mount Box Base is affixed to 
mounting surface, and then the module 
and cover are screwed onto the base 
using the two screws supplied.

COVER

MODULE

BASE BOX

FIGURE 2:  ROTARY DECADE 
ADDRESS SWITCHES

FIGURE 3: M710-CZR CONVENTIONAL ZONE INTERFACE MODULE

LOOP OUTPUT
LOOP OUTPUT 

LOOP INPUT
LOOP INPUT

LOOP OUTPUT (SEE NOTES 1)

EXTERNAL POWER 

SUPPLY

(SEE NOTE 2)

FAULT MONITOR 

(SEE NOTE 3)

CONVENTIONAL FIRE 

DETECTION ZONE

(SEE NOTE 4)

RESET OUTPUT 

(SEE NOTE 5)

I S BARRIER*

(REQUIRED FOR 

INTRINSICALLY SAFE 

APPLICATIONS ONLY)

(SUPPLIED WITH

M710-CZR)

Notes

1.  If short circuit isolation is not required, loop  should be wired to terminal 5 

and not 2.  Terminal 5 is connected internally to terminal 4.

2.  If the conventional zone is to be powered from the communications loop, then the 

loop  should  be  connected  both  to  the  loop  input  (terminals  3  and  4)  and  to  the 
conventional zone supply (terminals 6 and 7).

 

If an external power supply is to be used, it should be connected to the conventional 
zone  supply  (Terminals  6  and  7),  and  the  communications  loop  input  should  be 
connected only to the loop input (Terminals 3 and 4).

3.  The fault monitor is an external input, which is used to monitor an external contact, 

for  example  an  external  power  supply  fault  such  as  mains  failure.    The  fault  is 
signalled  by  switching  the  fault  terminal  to  the  external  power  supply  negative.  
Terminal 12 is internally connected to terminal 6.

4.  The Reset Output terminal links to the zone (-) during a reset to provide a restart 

signal for the 6500R(S) beam detector.  This can also be used to monitor a reset.

5.  The maximum recommended number of conventional IS devices used with each 

CZR module and barrier is 20 and the minimum external power supply is 23V.

6.  The module can monitor Notifier 800 Series sensors, LED not blinking, mounted 

in 470 ohm resistor bases. The maximum recommended number of conventional 
devices used with each CZR module is 20 and the minimum external power supply 
is 18V.

M200E-DIN DIN Rail Bracket

TOP

BOTTOM

Push Module into adaptor Bracket until it clips 
into place.
Locate  top  clip  over  DIN  rail  and  rotate 
bottom down to clip into place.
To remove, lift up, then rotate top away from 
the rail.

M200E-PMB Panel Mount Bracket

Adaptor bracket is mounted directly into panel using 
2 x M4 Pan head screws.  
Module is pushed into adaptor until it clips into place.

Note:   When  the  M200E-DIN  or  M200E-PMB  mounting 

brackets  are  used,  the  assembly  must  be  mounted 
into a suitable enclosure.

*NOTE FOR HAZARDOUS AREA APPLICATIONS

1.   A  SUITABLE  INTRINSICALLY  SAFE  BARRIER  MUST  BE 

USED AS SHOWN.

2.   ALL  DEVICES  IN  THE  CONVENTIONAL  ZONE  MUST 

HOLD SUITABLE HAZARDOUS AREA APPROVALS.

FOR FURTHER INFORMATION REFER TO I S RATED DEVICE 
INSTALLATION MANUALS

0832-CPD-1391 10

EN54-17: 2005
EN54-18: 2005 

Pittway Tecnologica S.r.l,

Via Caboto 19/3,

34147 TRIESTE, Italy

Содержание NOTIFIER M710-CZR

Страница 1: ...les on high current loaded loops for example if sounders are used To achieve this the loop out positive should be wired to terminal 5 rather than terminal 2 See figure 3 for details A single tri colour LED indicates the status of the module In the case of a fire alarm on the conventional zone the LED is switched on constant red by panel command If a fault is detected on the conventional zone or th...

Страница 2: ...ioni normali il LED può essere impostato mediante il comando del pannello di controllo affinché lampeggi di luce verde quando il modulo viene interrogato In caso di allarme antincendio nella zona convenzionale il pannello attiva il LED rosso che rimane acceso in modo fisso Se viene rilevato un guasto nella zona convenzionale o se l alimentazione della zona scende al di sotto di 12 V oppure nel cas...

Страница 3: ...cendios para que parpadee en verde cuando se realiza el muestreo del módulo En caso de que se produzca una alarma de incendio en la zona convencional la central activa el LED de forma fija y en rojo Si se detecta una avería en la zona convencional o la tensión de alimentación de la zona cae por debajo de los 12 V o se indica una avería en la fuente de alimentación externa el LED parpadeará en amar...

Страница 4: ...g 3 Der Modulstatus wird mit einer 3 farbigen LED angezeigt Im Normalbetrieb kann die LED durch ein Kommando der BMZ grün blinkend angesteuert werden wenn das Modul angesprochen wird Bei einem Feueralarm auf dieser Meldergruppe leuchtet die LED rot Bei einer erkannten Störung auf der Meldergruppe oder wenn die Gruppenspannung den Wert 12V unterschreitet oder einer Störung der externen Spannungsver...

Отзывы: