IDR-2P, -2A & -6A Repeaters User Manual
Operation
31
997-411-000-9, Issue 9
March 2008
4.5.3.4 Silence/Resound Pushbutton
Function
By default, option 1 is selected. Option 2 is
only available if VdS (local or network zones)
is selected at the ‘Set Function’ menu.
Option 2 is only provided for compatability with
older German systems for which the panel
(and repeaters) have this pushbutton labelled
‘Akustik AB/AN’. If the pushbutton is labelled
‘Akustik AN-/Anstellen’
then option 1 must be
selected
.
Use the
and
pushbuttons to select the
required level, then press the
pushbutton
to return to the User menu.
4.5.3.5 Event Options
By default, option 1 is selected and all events
are repeated. If option 2 is selected, only Fire
Alarm events are repeated.
Use the
and
pushbuttons to select the
required option, then press the
pushbutton
to return to the User menu.
4.5.3.6 Technical Alarm LED
By default, option 1 is selected. If option 2 is
chosen, the PRE-ALARM LED is used to
indicate TECHNICAL ALARM instead.
Use the
and
pushbuttons to select the
required option, then press the
pushbutton
to return to the User menu.
Configuration Menu:
1:Set Language
2:Set Function
BUZZER
4:
User Tue 05-Nov-2001 11:20:07
3:Access Level for MUTE
Silence/Resound pushbutton function
Configuration Menu:
2:Set Function
3:
5:
User Tue 27-Jul-2004 11:20:07
Access Level for MUTE BUZZER
4:Silence/Resound pushbutton function
Event Options
Event Options:
1
2:Display ALARMS ONLY
User Tue 27-Jul-2004 11:20:07
:
Display all events
Technical Alarm LED:
1
2:YES
User Tue 27-Jul-2004 11:20:07
:
NO