ID3000 Series Installation & Commissioning Manual
Commissioning
45
997-274-000-6, Issue 6
September 2009
7.3 Powering the Panel
1
Connecting power, ALL front panel LED indicators
should be extinguished with the exception of the green
‘POWER’ LED.
2
View the liquid crystal display. It should momentarily
display the start-up message ‘NOTIFIER ID3000
Version x.xx Intelligent Fire Detection System’ where
‘x.xx’ is the software version number, together with
the version numbers of the Loop Interface Boards.
The display should then read ‘Status: NORMAL (Date
and time)’ unless faults are present on the system (if
the panel has already been configured, then faults
indicating the loss of all loop devices will be shown).
Note:
If faults are shown (other than the loss of loops on a
configured panel and battery failure), these must
be cleared before you proceed further with the
commissioning procedure.
3
Externally isolate the AC mains supply at the third-
party-supplied isolation unit.
7.4 External Wiring
Refer to the appropriate module cable and wiring instructions
to identify the terminals for cable connections:
5.7.2 Base PCB Cables and Wiring. (Loops 1 & 2, Sounder
ouputs 1 to 4, Auxiliary outputs 1 & 2, Fault Relay and
Fire relay outputs).
5.9.1 Loop interface PCB Cables and Wiring (Ioops 3 to 8).
5.10.1Enhanced Loop interface PCB Cables and Wiring
(Loops 3 to 8).
5.11.1 Isolated RS232 Interface PCB Cables and Wiring
(RS232 output).
5.12.1 Isolated RS485 Interface PCB Cables and Wiring
(RS485 output).
7.4.1 Introduction
There are five stages to commissioning the external
wiring:
a. Checking the loop wiring for continuity, reversed
devices, short circuits and open circuits.
b. Connecting the loop wiring to the panel.
c. Checking for faults after the loop wiring is connected
to the panel.
d. Checking the 24V auxiliary outputs wiring and
selecting the resettable status.
e. Checking the sounder circuits.
Note:
The total length of the communications loop pair
cannot exceed 2000 metres.
NOTIFIER ID3000 version n.nna
Intelligent Fire Detection System
LIB software versions:
L1:n.nn L2:n.nn L3:n.nn L4:n.nn
Status:NORMAL Mon 20-Nov-2006 11:20:07