High-Speed NFN Manual —

 P/N 54013:C4 8/8/2019

Section 1: Using This Manual

This manual provides a system design overview for High-Speed Noti•Fire•Net. It describes compatible fire alarm devices that can be 
linked to the network; network requirements and limitations; and configuration details, including those for NFPA Class B and Class X. 
High-Speed Noti•Fire•Net works with products that have been certified to comply with the requirements in the Standard for Control 
Units and Accessories for Fire Alarm Systems, UL 864 10h Edition.  

1.1  UL 864 9th and 10th Edition

Per the UL Continuing Certification Program, UL 864 9th edition fire alarm control equipment will retain certification after the 
rollout of UL 10th edition (12/2/2018). 

Installations of UL 864 10th Edition certified equipment are permitted to use UL864 9th Edition certified equipment when 
approved by the local Authority Having Jurisdiction (AHJ).

For product compliance, refer to the UL/ULC listing cards located on the UL online certification directory. 

http://iq.ulprospector.com

The following products have not received UL 864 9th or 10th Edition certification and may only be used in retrofit applications.

 

Opera-

tion of the High-Speed NOTI•FIRE•NET™ with products not tested for UL 864 9th or 10th Editions have not been evaluated and may 
not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having 
Jurisdiction (AHJ). 

NFS-3030

NFS-640

NCA

1.2  Related Documentation

This table lists equipment that connects directly to High-Speed Noti•Fire•Net. For information about connecting non-network devices to 
these network nodes, refer to the installation manual(s) for your system. To obtain a complete understanding of specific features within 
the network, or to become familiar with the network functions in general, make use of the documentation listed in Table 1.1.  

Table 1.1  Network Related Documentation

!

CAUTION: SAME VERSION SOFTWARE

ALL EQUIPMENT ON THE NETWORK MUST BE RUNNING THE SAME VERSION OF THE NETWORK SOFTWARE.

For information on…

Refer to…

Part No. 

Panels and Intelligent 
Annunciators 

DVC and DAA Series
NCA-2 Network Control Annunciator
NCD Network Control Display
ONYXWorks® Workstation
NFS2-3030 Fire Alarm Control Panel
NFS2-640 Fire Alarm Control Panel
NFS-320 Fire Alarm Control Panel
NFS-3030 Fire Alarm Control Panel
NFS-640 Fire Alarm Control Panel
NCA Network Control Annunciator

52411
52482
LS10210-051NF-E
52342
52544, 52545, 52546
52741, 52742, 52743
52745, 52746, 52747
51330, 51344, 51345
51332, 51333, 51334
51482

Network Interface 
Equipment

High-Speed Network Communications Module
BACNet Gateway-3
ONYXWorks NFN GW-3 Embedded
ONYXWorks NFN GW-3 PC
NWS-3 Noti•Fire•Net Web Server-3 

54014
53372
53369
53370
53371

Off-line Programming 
Utility

Veri•Fire Tools help file

Veri•Fire-TCD

Содержание Notifier High-Speed NOTI-FIRE-NET

Страница 1: ...Network System Interface High Speed NOTI FIRE NET Instruction Manual Document 54013 Rev C4 8 8 2019 ECN 18 0305 ...

Страница 2: ...vide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined...

Страница 3: ...e sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tighten ing may damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal removal This system contains static sensitive components Always ground yourself with a proper...

Страница 4: ...te version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printed ma...

Страница 5: ...ts 7 2 2 Network Node Features 7 2 3 Network Interface Boards 9 2 4 High Speed Network Communications Modules in Repeater Mode 9 Section 3 Network Configurations 10 3 1 Point to Point Configuration 10 3 2 NFPA Class B Configurations 10 3 3 NFPA Class X Configurations 11 3 4 Network Wiring for Ground Fault Detection 12 Appendix A Compatibility with Other Systems 15 A 1 Honeywell Fire Systems 15 A 2...

Страница 6: ...ith NFPA 72 and or the latest edition of UL 864 These applications will require the approval of the local Authority Having Jurisdiction AHJ NFS 3030 NFS 640 NCA 1 2 Related Documentation This table lists equipment that connects directly to High Speed Noti Fire Net For information about connecting non network devices to these network nodes refer to the installation manual s for your system To obtai...

Страница 7: ...mming enables the DVC to react to events on other network nodes The minimum requirements for a DVC node are a DVC a High Speed Network Communications Module and a 24 VDC filtered power source This power can come from the control panel or from a regulated power limited remote power supply that is listed for Fire Protection Signaling use If local ground fault detection is required an AMPS 24 power s...

Страница 8: ...ire Net network via the internet or intranet allowing the user to view the history event status device properties or other control panel informa tion The NWS 3 interfaces to the internet intranet using an IP based wire ethernet connection NFS 3030 NFS2 3030 With HS NCM W HS NCM MF HS NCM SF HS NCM WSF HS NCM WMF or HS NCM MFSF The NFS 3030 or NFS2 3030 occupy a single node address on the network T...

Страница 9: ...S NCM MF Two multi mode fiber optic cable ports HS NCM SF Two single mode fiber optic cable ports HS NCM WSF One twisted pair wire port one single mode fiber optic cable port HS NCM WMF One twisted pair wire port one multi mode fiber optic cable port HS NCM MFSF One multi mode fiber optic cable port one single mode fiber optic cable port 2 4 High Speed Network Communications Modules in Repeater Mo...

Страница 10: ...Noti Fire Net is capable of communicating using an NFPA Class B SLC refer to Figure 3 1 Under this class of operation a single open wire to wire short wire to wire short and open wire to wire short and ground or open and ground results in fragmenta tion of the network A single ground does not affect communication but is detected Each fragment of the network re configures to per mit communication a...

Страница 11: ...ntioned circumstances while the system displays a trouble condition A single ground does not affect communication but is detected Class X operation may also be achieved using fiber optic cable or mixed media wire and fiber A B A B A B A B These two nodes continue to communicate with each other but cannot communicate with the other two nodes These two nodes continue to communicate with each other b...

Страница 12: ...NCM configured as a repeater is employed two ground fault detection schemes are possible within a point to point configura tion One or both nodes refer to Figure 3 5 and Figure 3 6 may provide ground fault detection depending on the number of repeaters and the setting of the repeater ground fault detect switch SW4 at each repeater refer to EXAMPLES 1 and 2 EXAMPLE 1 In this example the node on the...

Страница 13: ...lt detection is required Figure 3 7 shows how the ground fault detection switches must be arranged in order to achieve this maximum configuration EXAMPLE 4 The HS NCM can be shared between two network nodes In this example the HS NCM is shared between two nodes with separate power supplies Ground Fault detection should only be enabled for one of the power supplies NFNPTP3Prv2 WMF Power Supply GF D...

Страница 14: ...de refer to Figure 3 9 the Ground Fault switch SW4 on the shared HS NCM should be set to OFF The power supply Ground Fault detection for each is dependent on the requirements of their respective network nodes Network Node Network Node Network Node Power Supply GF Detect Dis abled Power Supply GF Detect Enabled Power Supply GF Detect Enabled NUP Port NUP Ports NUP Port GF Detect Enabled Figure 3 9 ...

Страница 15: ...L 864 9th Edition Products A 2 Johnson Controls Fire Systems The following Johnson Controls products will function as nodes on the High Speed Noti Fire Net IFC2 3030 IFC2 640 IFC 320 IFC 3030 IFC 640 JNCA 2 JNCA JDVC EM IFI Workstation These products are compatible with the High Speed NCM as described in this manual A 3 Tyco Unimode Fire Systems The following Tyco Unimode products will function as...

Страница 16: ...16 High Speed NFN Manual P N 54013 C4 8 8 2019 Notes ...

Страница 17: ...OR IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes th...

Страница 18: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...

Отзывы: