NO-460-017 

I56-3533-000

FTM-1 Firephone Control Module

INSTALLATION AND MAINTENANCE INSTRUCTIONS

BEFORE INSTALLINg

This information is included as a quick reference installation guide. Refer to 
the control panel installation manual for detailed system information. If the 
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.

gENERAL DESCRIpTION

Firephone  Control  Modules  are  intended  for  use  in  intelligent,  two-wire 
systems, where the individual address of each module is selected using the 
built-in rotary switches. This module is used to connect a remote firefighter 
telephone  to  a  centralized  telephone  console.  A  ringing  sound  is  provided 
at each off-hook handset until it is connected to the console. Wiring to indi-
vidual telephone jacks and handsets is supervised, and status is reported to 
the panel as NORMAL, TROUBLE, or TELEPHONE. This module has two pairs 
of output termination points available for fault-tolerant wiring, and includes a 
panel-controlled LED indicator.

COMpATIBILITy REqUIREMENTS

To  ensure  proper  operation,  this  module  shall  be  connected  to  compatible 
Notifier system control panels only (list available from Notifier).

MOUNTINg

This  module  mounts  directly  to  4

  square  electrical  boxes  (see  Figure  2A). 

The box must have a minimum depth of 2

1

/

8

. Flush mounted electrical boxes 

(SMB500) are available.

WIRINg

NOTE:  All  wiring  must  conform  to  applicable  local  codes,  ordinances  and 
regulations. 
1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams (Figures 3-4).

2.  Set the address on the module per job drawings.
3.   Secure  module  to  electrical  box  (supplied  by  installer),  as  shown  in  

Figure 2.

Figure 1. Controls and Indicators:

Figure 2. Module mounting:

C1059-00

SpECIFICATIONS

Normal Operating Voltage: 

15 to 32 VDC

Maximum Current Draw: 

7.5 mA (LED on)

Average Operating Current: 

2.4mA (LED flashing)

SLC Wiring Resistance: 

40 Ohms

Supervisory Wiring Resistance: 

50 Ohms

Handset Offhook Resistance: 

400 to 1500 Ohms

External Supply Voltage  

Regulated 24VDC

(between Terminals T10 and T11) 
Temperature Range: 

32˚F to 120˚F (0˚C to 49˚C)

Humidity: 

10% to 93% Noncondensing

Dimensions: 

4.5

 H × 4.275

 W × 1.4

 D (Mounts to a 4

 square by 21/8

 deep box.)

Accessories: 

SMB500 Electrical Box; CB500 Barrier

C1070-02