FDU-80 Instruction Manual —

 P/N 51264:C2 4/24/2019

Section 3: Operation

3.1  Display Patterns

The FDU-80 Annunciator directly displays (mimics) the information on the FACP display with the following exceptions:

Upon Power-up, the FDU-80 may display the following message until a valid message is received from the FACP: 

If an FDU-80 Annunciator fails to receive communications from the panel for a period of over 30 seconds, it will activate its local 
sounder (if so programmed) and display the following message: 

A Communication Fault may be due to one of the following conditions:

• FACP has not been programmed to communicate with the 

FDU-80

.  Refer to the appropriate FACP manual programming section.

• EIA-485 wiring between the 

FDU-80

 and FACP has an open.

• Polarity of the EIA-485 wiring between the 

FDU-80

 and FACP has been reversed. EIA-485 (-) on the 

FDU-80

 must be connected to EIA-485 

(-) on the FACP and EIA-485 (+) on the 

FDU-80

 must be connected to EIA-485 (+) on the FACP.

3.2  Switch Functions

3.2.1  Key-switch

The key-switch is used to enable and disable the operation of the function switches if switch 1 on 
DIP switch SW1 has been placed in the OFF position.

To enable the Acknowledge, Silence, Drill and Reset function switches, insert key into key-switch 
located at the top right corner of the FDU-80. Make certain the key is inserted completely before 
attempting to turn it. Turn the key clockwise until it stops. Leave the key inserted while pressing 
the function switches. When finished with the function switches, turn key-switch counterclock-
wise to disable function switches.

Note that the key-switch should normally be in the disabled position (fully counterclockwise), 
with the key removed and access to the key restricted to authorized personnel only. Do not leave 
the key unattended in the FDU-80.

3.2.2  Acknowledge/Step

When the Acknowledge/Step switch is pressed and released, the FDU-80 sends an Acknowledge command to the control panel. Pressing 
the Acknowledge switch silences the local piezo sounder, the sounders located in all other system annunciators and the sounder located 
on the Fire Alarm Control Panel's main circuit board. Only one press is necessary regardless of the number of new alarms, troubles or 
supervisory signals.

An acknowledge message is also sent to the printer and the history files in the FACP. Multiple active events (alarms, troubles, superviso-
ries) are scrolled on the display at a one second rate, but may be held for sequential display by pressing and holding the Acknowledge 
switch.

When more than one event exists, the first press of the Acknowledge switch silences system piezo sounders. The second press of the 
switch stops the scrolling and holds the event on the display for one minute. Subsequent pressing of the switch 'steps' through each active 
event.

3.2.3  Silence

When the Silence switch is pressed and released, the FDU-80 sends an alarm silence command to the control panel. The Silence switch 
performs the same functions as the Acknowledge switch. In addition, if an alarm exists, it turns off all silenceable NACs and causes the 
FACP Alarm Silenced LED to turn on while the FDU-80 will display a 'silenced' message. It also sends an 'Alarm Silenced' message to 
the printer and the history file within the FACP. A subsequent new alarm will resound the appropriate NACs (Notification Appliance 
Circuits) and local sounders.

3.2.4  Drill: Hold 2 Sec.

When the Drill switch is pressed and held for at least two seconds (time required to prevent accidental activations), the FDU-80 will 
transmit a drill command to the control panel. This command causes the FACP to turn on all NAC outputs and all silenceable circuits (all 
control modules/NACs that are programmed silenceable). In the event that the system was previously silenced, the drill command will 
also turn off the Alarm Silenced LED. The 'Manual Evacuate' message is shown on the FDU-80 display. The same message is sent to the 
FACP display, printer and history files. The Silence switch operates on 

silenceable

 NAC outputs only.

INITIALIZING...

PLEASE WAIT

COMMUNICATION FAULT!

Key-switch (shown in Off position)

Содержание Notifier FDU-80

Страница 1: ...Remote Fire Annunciator FDU 80 Instruction Manual Document 51264 Rev C2 4 24 2019 ECN 18 305 ...

Страница 2: ...provide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermi...

Страница 3: ...ries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tighten ing may damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal removal This system contains static sensitive components Always ground yourself w...

Страница 4: ...riate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printed...

Страница 5: ...tch 10 3 2 2 Acknowledge Step 10 3 2 3 Silence 10 3 2 4 Drill Hold 2 Sec 10 3 2 5 Reset 11 3 3 LED Indicators 11 Section 4 Mounting 12 4 1 Annunciator Preparation 12 4 2 Semi flush Mount Backbox 12 4 2 1 Mounting in SBB 3 Three Gang Electrical Box 13 4 2 2 Mounting in Three Electrical Boxes Ganged Together 13 4 3 Surface Mount Backbox 14 Section 5 Electrical Connections 15 5 1 Power Connections 15...

Страница 6: ...s Subject to AHJ Approval This product incorporates field programmable software The features and or options listed below must be approved by the local AHJ 1 3 Related Documentation The table below provides a list of document sources manuals containing additional information regarding the fire alarm control panels and components that ACS annunciators can be connected to The NOTIFIER document DOC NO...

Страница 7: ...acters x 4 lines is backlit under normal and alarm conditions System Status LEDs for AC Power green Alarm red Trouble yellow Supervisory yellow and Alarm Silenced yellow No programming necessary duplicates messages at control panel display Local piezo sounder with alarm and trouble resound Device type identifiers from the control panel Device zone custom alpha labels from the control panel Time da...

Страница 8: ...vise all annunciators on the loop All remaining annunciators must have Switch 3 set to the OFF position for proper supervision and operation It is important to note that the function switches on all FDU 80 annunciators will operate regardless of the setting of Switch 3 A break open circuit in the power or EIA 485 connections creates an FDU 80 Annunciator fault at the control panel All annunciators...

Страница 9: ...ailable FACP DIP switches 7 and 8 OFF these switches are not used Fire Alarm Control Panel SW1 4 SW1 5 SW1 6 Use This Setting for NFS2 640 NFS 320 NFS 640 all releases AFP 300 400 with FACP software Version 3 62 or higher FireWarden2 100 FireWarden 100 all releases OFF OFF OFF Future Use OFF OFF ON Future Use OFF ON OFF Future Use OFF ON ON Future Use ON ON OFF Future Use ON OFF ON Future Use ON O...

Страница 10: ...ssing the Acknowledge switch silences the local piezo sounder the sounders located in all other system annunciators and the sounder located on the Fire Alarm Control Panel s main circuit board Only one press is necessary regardless of the number of new alarms troubles or supervisory signals An acknowledge message is also sent to the printer and the history files in the FACP Multiple active events ...

Страница 11: ... power is applied to the host FACP The green LED will turn off if AC power to the host FACP is lost Alarm This is a red LED that turns on steady when one or more fire alarms occur The Alarm LED turns off when the Reset switch is pressed Supervisory This is a yellow LED that turns on steady when one or more supervisory conditions occur such as a sprinkler valve tamper condition It turns off when th...

Страница 12: ...plied to the wiring during the installation procedure To mount the FDU 80 Annunciator in an electrical box the trim ring must first be removed The trim ring is held in place by two screws inserted through the top and bottom edge as illustrated in Figure 3 1 Removal of the trim ring will expose a metal flange with mounting holes Refer to Hardware and Backboxes on page 12 4 2 Semi flush Mount Backbo...

Страница 13: ... Figure 2 2 on page 9 Carefully insert the FDU 80 into the three electrical boxes ganged together and attach it using the four mounting holes on the FDU 80 flange and the four screws provided for this purpose Replace the trim ring and secure with the two screws which were previously loos ened Adjust the plastic trim ring to the surface of the wall before tightening the screws Do not overtighten FD...

Страница 14: ...cuit board Set DIP switch SW1 for the desired options Refer to Figure 2 2 on page 9 Carefully insert the FDU 80 into the three gang electrical box and attach it using the four mounting holes on the FDU 80 flange and the four screws provided for this purpose Replace the trim ring and secure with the two screws which were previously loosened Do not overtighten FDU 80 flange Mounting holes 4 The FDU ...

Страница 15: ...lighting is turned back on during AC loss only for alarm conditions in the system 12 18 AWG 0 75 3 25 mm2 wire for 24 VDC circuit is acceptable Power wire distance limitation is set by 1 2 volt maximum line drop from source to end of circuit 5 2 Specifications for the FDU 80 Operating Voltage Range 18 VDC to 28 VDC Current Consumption 24 VDC nominal filtered and nonresettable Normal Standby no act...

Страница 16: ...es It is however strongly recommended that the power and communication wires be separate whenever possible A Ferrite Core P N FBD 1 is required to meet FCC Part 15 requirements if the EIA 485 wiring is not in conduit The EIA 485 circuit is rated at 5 5 VDC maximum and 60 mA maximum The FDU 80 annunciator has resistors built into the circuit board at the In Terminals 2 4 and the Out Terminals 1 3 f...

Страница 17: ... entering the second annun ciator must be connected to the three gang box or Earth Ground terminal P2 7 on the second annunciator If additional annunciators are connected the shield leaving each enclosure must be left floating and the shield entering each must be connected to the three gang box or the Earth Ground terminal P2 7 on the annunciator NOTE To ensure static ESD electrostatic discharge p...

Страница 18: ...nunciator must be left floating and the shield entering the following unit must be connected to the Earth Ground terminal P2 7 on the annunciator Notes 1 Power limited 24 VDC power may be run in the same conduit as the EIA 485 wiring 2 Twisted shielded wire is recommended for the EIA 485 communications loop 3 Each electrical backbox is connected to earth ground via the conduit 4 Shield is connecte...

Страница 19: ...ns for power connections 24 VDC Non Resettable Power to UL 8th edition panels NFS 640 AFP 300 400 and FireWarden NFW 100 WARNING AHJ APPROVAL THE NFS 640 AFP 300 400 AND FIREWARDEN NFW 100 HAVE NOT BEEN CERTIFIED TO COMPLY WITH THE REQUIREMENTS IN THE STANDARD FOR CONTROL UNITS AND ACCESSORIES FOR FIRE ALARM SYSTEMS UL 864 9TH EDITION OPERATION OF THESE PRODUCTS WITH PRODUCTS TESTED FOR UL 864 9TH...

Страница 20: ... at the FACP may be required to enable EIA 485 communication Refer to the appropriate FACP Programming Manual Refer to the following illustrations for EIA 485 connections to UL 8th edition panels NFS 640 AFP 300 400 and FireWarden NFW 100 P2 FDU 80 no connection 24 VDC OUT 24 VDC OUT Earth Ground Option NFW 100 Figure A 3 Power Wiring to the NFW 100 TX RX REFTX RX REF B A B A FDU 80 TB12 EIA 485 E...

Страница 21: ... Manual P N 51264 C2 4 24 2019 21 EIA 485 Connections UL 864 8th Edition Applications FDU 80 NFW 100 EIA 485 Out to Next Device EIA 485 Out to Next Device or back to FACP EIA 485 Figure A 6 EIA 485 Wiring to the NFW 100 ...

Страница 22: ... 14 function switches 7 8 see also switch functions 10 G grounding 12 17 18 K key switch 8 10 L LCD display 7 see also display on powerup 10 LED 7 see also system status 7 LEDs 11 M maximum annunciators 7 mounting 12 13 14 mounting options 7 MS 9200UDLS Power 15 N NFS2 640 EIA 485 NFS 320 EIA 485 16 Power 15 NFS 320 Power 15 NFS 640 EIA 485 20 Power 19 NFW 100 EIA 485 21 Power 20 NFW2 100 EIA 485 ...

Страница 23: ...IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes the o...

Страница 24: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...

Отзывы: