Honeywell Notifier FAAST LT NFXI-ASD Series Скачать руководство пользователя страница 8

N200-102-00

8

I56-3947-200  

Notifier Ltd., Charles Avenue, Burgess Hill, West Sussex, RH15 9UF, UK

Password Sequence to Enter 

Maintenance

 Mode

Press  and  hold 

RESET

;  Left  flow  indicator  will  turn  yellow,  then 

green.
Release 

RESET

 and 

FAULT

  indicator  will  switch  on  green. The 

left flow indicator will blink green indicating the device is ready for 

the first digit.
Press 

DISABLE

 to increment the LEDs 1…9; press 

TEST

 to select 

a digit.

The  flashing  airflow  segment  will  turn  solid  green  and  the  next 

segment will begin to flash indicating set the next digit. When the 

4th digit is selected, all 4 airflow segments are turned off. If the 

password is accepted the 

FAULT

 indicator will remain green and 

the  unit  enters 

Maintenance

  mode.  If  the  password  is  incorrect 

the 

FAULT

 indicator flashes yellow and the unit remains in 

Normal

 

mode. The Default password in 

3111

.

If no button is pressed for 10s during the password sequence, the 

unit returns to 

Normal

 mode. If there is no activity in 

Maintenance

 

mode for 5 minutes (default), the 

FAULT

 indicator blinks green for 

15s and then the unit returns to the 

Normal

 state.

TESTING

Note that the sensor LEDs, which are under the control of the CIE 

(Fire Panel), must be turned on to activate the front panel alarm 

indicators.

Magnet Test

The alarm signalling can be tested for functionality by placing a 

test magnet in the position shown in Figure 9 (displayed earlier in 

the guide). This method does not test the air flow in the pipe-work.

Smoke Testing

The  system  alarm  response  can  be  tested  for  functionality 

using  smoke. The  choice  of  smoke  source  is  dependant  on  the 

installation  but  in  all  cases  the  smoke  must  be  present  for  the 

duration of the test. Smoke pellets or matches can be used close 

to  the  sampling  point  to  introduce  smoke  particulates  into  the 

system. It is recommended that smoke with a particulate life cycle 

of greater than 120s should be used – standard aerosol sprays for 

point detector testing do not work well on aspirated systems.

Fault Testing 

Simulate a fault on the detector (for example, block the outlet pipe) 

and check that a fault is signalled on both the front panel of the unit 

and at the CIE (Fire Panel).

Table 5: Front Panel Buttons

SERVICE

WARNING

Isolate the aspirating detector from the fire alarm system to prevent 

any  unwanted  alarms  when  opening  the  front  door  of  the  unit. 

Make sure all power is removed from the system before removing 

any covers. 

Service Mode

Opening the cabinet door during normal operation will cause the 

unit to enter 

Service

 Mode. The 

FILTER

 LEDs will blink, the unit will 

switch off power to the fans and stops communicating with the fire 

panel (the smoke sensors continue to communicate with the panel). 

When the cabinet door is closed, the unit restarts automatically.

Filters

Periodic cleaning or replacement of the filters will be required. 
The filters are located inside the cabinet at the top of the unit (see 

Figure 9 displayed earlier in the guide) and are removed as shown 

in the sequence below:

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

 

F  i lters 

  

Either replace the filter assembly or carefully brush off the accumulated dust. 

Refit the filter, close and secure the cabinet door. The unit will initialise and restart. 

  

 

 

 

 

  

  

 

Smoke Sensors 

1

2

3

BUTTON 

NORMAL Mode

MAINTENANCE Mode 

RESET      

When pressed for 2 s, starts PASSWORD 

PROCEDURE to enter Maintenance 

mode. 

When pressed for 2 s latched alarms, faults and 

sounders (relays) are reset.  Alarm controlled by panel. If 

alarm persists, set again immediately after the reset 

In DISABLE Mode, if pressed for 2 s unit will exit from 

DISABLE Mode (but remains in MAINTENANCE Mode) 

DISABLE  

Used to increment  Password digits in 

PASSWORD PROCEDURE

When pressed for 2 s, device enters DISABLE Mode for 

60 minutes (default).  Alarm and fault relays reset . 

Smoke sensors continue to report alarm and their faults 

to the panel. 

(To exit DISABLE Mode see RESET) 

TEST         

Used to confirm password in PASSWORD 

PROCEDURE. Default Password = 3111

When pressed for 2 s and released, both sensor will 

simulate alarm 

When pressed for 4 s and released, sensor #1 will 

simulate alarm 

When pressed for 6 s and released, sensor #2 will 

simulate alarm 

COMBINATIONS 

RESET + DISABLE 

When pressed for 2 s, shows fan speed 

(on smoke level scales) for a preset time. 

When pressed for 2 s, shows fan speed (on smoke level 

scales) for preset time. 

RESET + TEST 

No action 

When pressed for 2 s, turns off sounders 

RESET + TEST + DISABLE 

No action 

When pressed for 2 s, unit exits from MAINTENANCE 

Mode 

FOAM GASKET

Содержание Notifier FAAST LT NFXI-ASD Series

Страница 1: ...tor Characteristics Maximum rated switching current under short circuit Is max 0 9A 29V Maximum leakage current IL max with the switch open isolated state 15mA Maximum series impedance with the switch closed Zc max 190 m ohm at 15Vdc 1A Power Reset 0 5s Configurable Input Activation Time 2s min Relay Contact Ratings 2 0 A 30 VDC 0 5A 30 VAC Environmental Ratings Temperature 10 C to 55 C Relative H...

Страница 2: ... labels fixed in place This allows the installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed 1 2 3 Figure 6 Fasten the mounting bracket to the wall Mounting the LT NFXI ASD to the Wall Figure 2 Placing the Front Panel Labels 2 10 3 1 4 5 6 7 8 9 2 10 3 1 4 5 6 7 8 9 IN PU T SE NS OR ASPI RATO R E L B A S...

Страница 3: ...e unit Each unit has 2 pipe holes per channel so if installing a 1 channel unit holes 3 and 4 do not function Use Table 1 to locate the holes required for the installation Figure 8 Pipe Holes Table 1 Pipe Holes Used for Each FAAST LT Model Note 1 Pipe holes not used should be kept sealed Note 2 Do NOT glue pipes into the pipe holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel for EN54...

Страница 4: ...ANNEL 2 FILTER POWER AND ALARM CONNECTIONS CHANNEL 1 FILTER USB PORT SENSOR COVER POSITION FOR TEST MAGNET POSITION FOR TEST MAGNET Exhaust Pipe SAMPLING AREA SAMPLING AREA 5 6 EARTH BAR MOUNT EARTH BAR MOUNT EARTH BAR OPTIONAL Note 1 All wiring should comply with local requirements and regulations Note 2 Loop wiring must observe the recommendations of the panel manufacturer 3 4 ...

Страница 5: ...hen smoke is detected by one of the Aspirated Smoke Detector units but not the other To avoid problems ensure that no VIEW sensors on a loop have addresses set adjacent to the address values set in an Aspirating Smoke Detector POWERING UP Using Default Settings 1 Connect a suitable 24VDC supply complying with European Standard EN 54 4 to pins 1 and 2 on terminal block T1 See Table 2 Table 3 Relays...

Страница 6: ...E R F IL T E R L O W F L O W H IG H F L O W E L B A S I D M E T S Y S 2 10 3 1 4 5 6 7 8 9 MODULE 1 LEVEL 1 SMOKE FAULT FAULT POWER LEVEL 2 SMOKE MODULE 2 ALARM PREALARM IN P U T S E N S O R AS PI RA TO R E L B A S I D M E S Y TE MP ER AT UR E S O U N D E R F IL T E R L O W F L O W H IG H F L O W S T 2 10 3 1 4 5 6 7 8 9 2 10 3 1 4 5 6 7 8 9 2 Check the voltage at the connector Make sure it is wit...

Страница 7: ...w when initialising POWER FAULT ON Yellow Low power alert high power fault Check the power supply voltage CHANNEL FLOW INDICATORS 1 2 ON Green The LED indicates the air flow for a channel Centre normal flow Left flow low 20 at extreme Right flow high 20 at extreme On 2 channel unit Upper row Ch1 Lower row Ch2 LOW FLOW ON Low flow fault Check filter check pipe network for blockages INPUT 1 BLINK Ex...

Страница 8: ...e Mode Opening the cabinet door during normal operation will cause the unit to enter Service Mode The FILTER LEDs will blink the unit will switch off power to the fans and stops communicating with the fire panel the smoke sensors continue to communicate with the panel When the cabinet door is closed the unit restarts automatically Filters Periodic cleaning or replacement of the filters will be req...

Страница 9: ...ng normal operation 1 2 3 PipeIQ LT QUICK START INSTRUCTIONS Overview of PipeIQLT The PipeIQLT software program is a convenient and powerful Windows based application that can be used to quickly and accuratelydesignpipenetworks generateconfigurationparameters for correct set up and operation and facilitate commissioning and monitoring of the performance of FAAST LT Aspiration devices PipeIQLT prov...

Страница 10: ...uter in the normal way for your operating system Launching To launch the PipeIQLT application double click the PipeIQLT icon on the desktop Or click Start bottom left corner of the Windows screen and then select PipeIQLT from the programs list When the application opens it is possible to start a new project or to monitor or modify an existing project Use the File menu to select New or Open Choose ...

Отзывы: