Fitting/Replacing the 4-Way Sounder PCB

4

Specification

Outputs:

Sounder PCB outputs:

26 - 28.5V dc

If DIP switch 6 is set to >250mA:

4 x 1A (maximum of 1.5A in total for 2 
or more outputs)

If DIP switch 6 is set to <250mA:

4 x 250mA

Digital Inputs:

2 x 5V - 32V dc

Up to two 4-Way Sounder PCBs may be fitted in the panel. If it is 

intended to install an 8-way Relay PCB and a 4-way Sounder 
PCB, the Relay PCB 

must

 be in the first (innermost) position.

Each 4-Way Sounder PCB communicates with the PSU PCB via 16-way 
ribbon cables in a daisy-chain arrangement.

External power supply unit (if used):

Sounder PCB input: 20-30V dc, 5A
Compliancy: EN54 Part 4 with power status volt-free contact
(normally closed when there are no faults present)

Max Current (per PCB):

Quiescent:

47mA

Alarm/all active: 1547mA

External Wiring

Configurable Circuits

Typical wiring examples are given below. The functions available on a 
particular circuit are determined by the configuration options described on 
the previous page.
The PCB is supplied with an end-of-line diode across each circuit 
connector. Remove these diodes and either (depending upon the usage of 
the circuit) place across the end-of-line, or discard if not required in this 
usage.

Digital Inputs

Typical wiring examples are given below. The functions available on a 
particular input are determined by the configuration options described on 
the previous page.

External PSU

If an external PSU is being used, connect the dc input as shown at left, and 
the fault input as shown below. Links JP1 and R63 must be set correctly as 
described on the previous page.

+ 1 -

+ 2 -

+ 3 -

+ 4 -

+

-

TB3

TB2

TB4

TB1

PL1

PL2

S

K

1

S

K

2

IN-CIRC

FS02 DEOL
MON. SOUNDER PCB

SW1

JP1

A

B

1

1

2 3 4 5 6 7 8

1

2

SST

0V

0

20 - 30V dc, 5A

External Power 
Input

-

+

+

-

+ 1 -

+ 2 -

Output

Output

Ouput

Output

circuit 1

circuit 2

circuit 3

circuit 4

OUTPUT CIRCUIT APPLICATIONS:

Typical connections

+ 3 -

+ 4 -

+  1  -

+    1   -

+  2  -

+    2    -

+  3  -

+    3    -

+  4  -

+    4    -

ÜE

-

+

-

+

SOUNDERS

FIRE/FAULT ROUTING

SST

This connection is provided 
for LED box (English PN: 
020-769-001 or German PN: 
020-769).

SST LED Box 
Connection

Note: + = active polarity

Haupt-
melder

ÜE

O/P

LEDs

Output channel 1 fault

Output channel 2 fault

Output channel 3 fault

Output channel 4 fault

Heartbeat
Normal: 0.5s on, 5 sec off
Panel/PCB Comms fault: 
flashes at 1Hz, 50% duty 
cycle

Heartbeat LED is green, 
all others are yellow.

Fire

Routing

Fault

Routing

KIT

020-

773

O/P

S

S

T

O

p

e

ra

te

d

SST

!!

Digital input circuit 1. Must be linked 
to 0V if not used.

Digital input circuit 2. Must be linked 
to 0V if not used.

1

2

DIGITAL INPUTS AND
EXTERNAL PSU
FAULT INPUT

Power fault output from EN54-4 
compliant PSU:
Note:

 Must be linked to 0V if internal 

PSU is used.

Connect normally closed to this 
terminal.

Connect common to this terminal.

0V

1

2

0V

PROGR.

OUTPUT & INPUT CIRCUIT APPLICATIONS:

Typical connections

SST

FAULT

ÜE

Operated

997-536-000-2, Issue 2 July 2009

Содержание NOTIFIER 020-772

Страница 1: ...age socket connector SK2 on the Main PCB Once disengaged there is no need to remove the 2 Way Relay PCB from the panel 8 Leave the ribbon cable connected at connector SK4 H on the Main PCB disconnect the ribbon cable at socket connector SK2 on the PSU PCB DO NOT forget to reconnect this cable before re fitting the main PCB 9 Gently pull the top of the Main PCB away from the back box and lift the P...

Страница 2: ...h with the face of the PCB c Holding the spacer against the PCB now push the rivet fully home the jaws of the rivet expand inside the spacer to lock it to the PCB Ensure the spacer is orientated as shown to clear any components 18 Inspect the 4 Way Sounder PCB to be fitted in the second layer position If there is no evidence of damage proceed as follows 19 Connect the 16 way ribbon cable S observe...

Страница 3: ... Link JP1 A B R63 4 Other Configuration Options DIP switches 5 8 settings Function 5 6 7 8 Steady Pulsing 0 0 0 0 Steady sounders 1 0 0 0 Pulsing sounders 1second on 1 second off Sounders 250mA 0 0 0 0 Sounders 250mA Use this setting if one or more of the output circuits has a load current of 250mA or above 0 1 0 0 Sounders 250mA Use this setting if none of the output circuits has a load current g...

Страница 4: ...input are determined by the configuration options described on the previous page External PSU If an external PSU is being used connect the dc input as shown at left and the fault input as shown below Links JP1 and R63 must be set correctly as described on the previous page 1 2 3 4 TB3 TB2 TB4 TB1 PL1 PL2 SK1 SK2 IN CIRC FS02 DEOL MON SOUNDER PCB SW1 JP1 A B 1 1 2 3 4 5 6 7 8 1 2 SST 0V 0 20 30V dc...

Отзывы: