NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
149
Appendix I: Regional Settings
The panel programming
REGIONAL
SETTINGS
choices, available through the Panel Settings (2)
screen (refer to page 22) are described below. The
REGIONAL
SETTINGS
screen (Refer to
Figure I.1) allows scrolling through the available choices by pressing the soft key. Choices are
CHICAGO
,
SINGAPORE
,
AUSTRALIA
,
CHINA
or
DEFAULT
(no special regional settings).
Figure I.1 Regional Settings Screen
I.1 Singapore
The
REGIONAL
SETTING
choice of
SINGAPORE
activates the following features:
• Does not allow the disabling of a bell circuit either locally or via the network.
• A BELL CIRCUIT Type Code will allow power monitoring.
• The panel will sound the piezo when local control is set to OFF.
• Does not turn ON the System Trouble LED or the System Trouble relay for disabled points.
• Does not turn ON the System Trouble LED, the System Trouble relay, or the piezo when
Drill is initiated.
• Turns ON keypad LEDs, PCB LEDs, and all ACM-24/48 LEDs during Lamp Test.
• Requires the user to initiate the start of the application when the panel boots/reboots. The
CPU Failure LED will be ON until the user initiates startup. (Refer to Figure I.2.)
Figure I.2 Singapore Application Initiation
R E G I O N A L S E T T I N G S
R E G I O N A L S E T T I N G S : S I N G A P O R E
T R O U B L E
L O A D I N G . . N O S E R V I C E
L A K E V I E W G E N E R A L H O S P I T A L
N 0 8 3
B O O T L O A D E R
1 1 : 5 8 : 4 5 A W E D N O V 2 2 , 2 0 0 6
C P U H A S R E B O O T E D
C O N T I N U E A B O R T
User should select CONTINUE to initiate applications.
User should select ABORT to abort applications.