Cam adjustment for servo motors with right hand rotation

Cam adjustment for servo motors with left hand rotation

MT4000A/B series

MT4000A/B series

cam

cam

I/III

&

IV

Rotate the cam clockwise to increase the opening
position of the air damper
Rotate the cam counter--clockwise to decrease
the opening position of the air damper

I/ III

&

IV

Rotate the cam counter--clockwise to increase
the opening position of the air damper
Rotate the cam clockwise to decrease the
opening position of the air damper

II

Factory set at 0 degrees, to start air damper in
closed position

II

Factory set at 0 degrees, to start air damper in
closed position

MT4001A/B/C, MT4002B & MT4003C series

MT4001A/B/C, MT4002B & MT4003C series

cam

cam

I

Rotate the cam clockwise to increase the high fire
psition of the air damper
Rotate the cam counter--clockwise to decrease
the low fire position of the air damper

I

Rotate the cam counter--clockwise to increase te
high fire position of the air damper
Rotate the cam clockwise to decrease the low fire
position of the air damper

II

Factory set at 0 degrees, to start the air damper
in closed position

II

Factory set at 0 degrees, to start the air damper
in closed position

III/IV

Rotate cam clockwise to increase the low fire
position of air damper
Rotate cam counter--clockwise to decrease the
low fire position of the air damper

III/IV

Rotate cam counter--clockwise to increase the
low fire position of air damper
Rotate cam clockwise to decrease the low fire
position of the air damper

V

Rotate the cam clockwise, to delay the switching
of the second stage gas valve
Rotate the cam counter--clockwise, to advance
the switching of the second stage of the gas valve

V

Rotate the cam counter--clockwise, to delay the
switching of the second stage gas valve
Rotate the cam clockwise, to advance the
switching of the second stage of the gas valve

ELECTRICAL CONNECTIONS

IMPORTANT

Protective earth wires of external connected devices
etc. should be connected to the MT4000 earth
terminal according the manufacturer’s instructions
(max. 2 devices)

neutral

2

3

4

5

6

7

8

9

N.O.

N.C.

N.O.

N.C.

C.

C.

drive to
low fire

auxiliary switch

auxiliary switch

drive to
high fire

1

Fig. 2. Wiring Diagram MT4000A

neutral

2

3

4

5

6

7

8

9

N.O.

C.

N.C.

N.O.

N.C.

C.

line

auxiliary switch

auxiliary switch

drive
signal

1

Fig. 3. Wiring Diagram MT4000B

Содержание MT4000 Series

Страница 1: ...ection low fire adjustment switch and fail safe pre purge timer Dimensions See Fig 1 Installation drawing MT4000 Series Supply voltage Line voltage 220 240 Vac 50 60 Hz 110 Vac 50 60 Hz Maximum voltage Current of micro switches 250 Vac 10A ac and 2A dc Ambient temperature range 15 60 C Relative humidity 0 90 at 40 oC non condensing Rated torque value Maximum torque at 6s rotation time over 90 degr...

Страница 2: ...er motor II closed position of air damper motor III auxiliary switches III low fire position of air damper motor IV auxiliary switches IV low fire position of air damper motor V switches the second stage operation of the gas valves Adjustment for cams Disconnect power supply and remove the cover Use adjustment tool inside the cover to adjust the cams Place the tool in one of the cam grooves to tur...

Страница 3: ...ry set at 0 degrees to start the air damper in closed position II Factory set at 0 degrees to start the air damper in closed position III IV Rotate cam clockwise to increase the low fire position of air damper Rotate cam counter clockwise to decrease the low fire position of the air damper III IV Rotate cam counter clockwise to increase the low fire position of air damper Rotate cam clockwise to d...

Страница 4: ... low drive signal power signal during run 1 Fig 7 Wiring diagram MT4001C input main valve neutral fan input line output main valve 2 3 4 5 6 7 8 9 fan output Tmod 1 Fig 8 Wiring Diagram MT4002B input main valve fan input neutral line output main valve 2 3 4 5 6 7 8 9 Tmod power signal during run 1 Fig 9 Wiring diagram MT4003C Control Product Satronic AG Honeywell Platz 1 CH 8157 Dielsdorf Switzerl...

Отзывы: