Programming
Master Programming Level
110
MS-9200UDLS PN 52750:A 11/04/05
4+2 Standard, 4+2 Express, 3 + 1, 4 + 1 and 4+2 Expanded Formats
The information shown in Table 3.3 is automatically programmed for the Central
Station phone number Event Codes when any of these Formats are selected. Enter
00
for an Event Code Setting to disable the report.
Table 3.3 Event Codes
Event Description
Event Code Settings
Active
Restoral
PULL STATION
11
E1
MON-USER-DEF-1
11
E1
WATERFLOW
11
E1
MON-USER-DEF-2
11
E1
SMOKE (PHOTO)
11
E1
DET-USER-DEF-1
11
E1
SMOKE (ION)
11
E1
DET-USER-DEF-2
11
E1
HEAT DETECT
11
E1
DET-USER-DEF-3
11
E1
SMOKE DUCT-P
11
E1
DET-USER-DEF-4
11
E1
DUCT SUPERVISORY
81
E1
DET-USER-DEF-5
81
E1
not used
00
00
not used
00
00
not used
00
00
not used
00
00
MONITOR
11
E1
MON-USER-DEF-3
11
E1
not used
00
00
not used
00
00
SMOKE CONVEN
11
E1
MON-USER-DEF-5
11
E1
HEAT DETECT
11
E1
MON-USER-DEF-6
11
E1
MEDIC ALERT
00
00
MON-USER-DEF-7
00
00
HAZARD ALERT
00
00
MON-USER-DEF-8
00
00
TORNADO ALRT
00
00
MON-USER-DEF-9
00
00
not used
00
00
not used
00
00
TAMPER
81
E1
MON-USER-DEF-11
81
E1
MON SUPERVISORY
81
E1
MON-USER-DEF-12
81
E1
MON SUPERV AUTO
81
E1
MON-USER-DEF-13
81
E1
POWER MON
81
E1
MON-USER-DEF-14
81
E1
TROUBLE MON
POINT_FAULT code will
always
be transmitted
MON-USER-DEF-15
POINT_FAULT code will
always
be transmitted
PROCESS MON
00
00
Содержание MS-9200UDLS
Страница 4: ...4 MS 9200UDLS PN 52750 A 11 04 05 Notes ...