Honeywell MS-9200UDLS Скачать руководство пользователя страница 1

 

 

 

Fire Alarm Control Panel

MS-9200UDLS

MS-9200UDLSE

PN: 52750:A          ECN 05-680

IMPORTANT!

 The SLC Manual Document #51309 must be referenced in addition to this 

manual when installing or servicing the Fire Alarm Control Panel.

Document      #52750
11/04/05       Revision:

A

http://manualforhoneywellthermostat.com

Содержание MS-9200UDLS

Страница 1: ...0UDLSE PN 52750 A ECN 05 680 IMPORTANT The SLC Manual Document 51309 must be referenced in addition to this manual when installing or servicing the Fire Alarm Control Panel Document 52750 11 04 05 Revision A http manualforhoneywellthermostat com ...

Страница 2: ...ons caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined rate or reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least once pe...

Страница 3: ...epartment if any problems are antici pated or encountered Disconnect AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere ...

Страница 4: ...4 MS 9200UDLS PN 52750 A 11 04 05 Notes ...

Страница 5: ... 1 Telephone Circuitry 24 1 10 2 Digital Communicator 24 1 10 3 Telephone Company Rights and Warnings 25 1 10 4 For Canadian Applications 26 SECTION 2 Installation 27 2 1 Mounting Backbox 27 2 2 Mounting Transformer 28 2 3 Power 31 2 3 1 AC Power and Earth Ground Connection 31 2 3 2 Battery Power 31 2 3 3 Special Application DC Power Output Connection 31 2 4 Relays 32 2 5 Notification Appliance Ci...

Страница 6: ... 3 6 3 8 Zones Available 79 3 6 4 Loop Setup 79 3 6 4 1 Style 79 3 6 4 2 Loop Protocol 79 3 6 5 System Setup 80 3 6 5 1 Trouble Reminder 81 3 6 5 2 Banner 81 3 6 5 3 Time Date 82 3 6 5 3 1 Time 82 3 6 5 3 2 Date 83 3 6 5 3 3 Clock Format 83 3 6 5 3 4 Daylight Savings Time 83 3 6 5 4 Timers 84 3 6 5 4 1 PAS Positive Alarm Sequence Delay 84 3 6 5 4 2 Pre signal Delay 85 3 6 5 4 3 Waterflow Delay 85 ...

Страница 7: ...nowledge Step 128 4 1 2 Alarm Silence 128 4 1 3 Drill Hold 2 Sec 128 4 1 4 Reset 128 4 2 LED Indicators 129 4 3 Normal Operation 130 4 4 Trouble Operation 130 4 5 Alarm Operation 132 4 6 Supervisory Operation 133 4 7 Process Monitor Operation 134 4 8 Hazard Tornado Condition Operation 134 4 9 Medical Alert Condition Operation 134 4 10 NAC Operation 134 4 11 Programmed Zone Operation 135 4 12 Disab...

Страница 8: ...nitiated at a Service Terminal 161 6 3 Uploading Initiated at a Service Terminal 162 SECTION 7 Power Supply Calculations 163 7 1 Overview 163 7 2 Calculating the AC Branch Circuit 163 7 3 Calculating the System Current Draw 164 7 3 1 Overview 164 7 3 2 How to Use Table 7 3 on page 165 to Calculate System Current Draw 164 7 4 Calculating the Battery Size 166 7 4 1 NFPA Battery Requirements 166 7 4 ...

Страница 9: ...its UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired CAN ULC S524 01 Standard for Installation of Fire Alarm Systems Other EIA 232E Serial Interface Standard EIA 485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local...

Страница 10: ...lack White Red T X R C V TB8 option to DB 25 TB3 TB8 TB8 TB4 5 4 3 2 1 25 24 23 22 21 20 19 18 17 16 15 14 9 8 7 6 13 12 11 10 CAUTION HIGH VOLTAGE NC NO C 120 VAC 60 HZ 3 0 amps 220 240 VAC 50 Hz 1 5 amps 24 VDC supervised nonpower limited 18 Amp Hour maximum T X R C V D T R G N D G N D 24V NON RST POWER 24V RST POWER REMOTE PWR SUPPLY SYNC NAC 1 CLASS A NAC 1 3 CLASS B NAC 2 CLASS A NAC 2 4 CLAS...

Страница 11: ...38 AFM 16AF Doc 15210 LDM 32F Doc 50055 AFM 16ATF AFM 32AF Doc 15970 ACS Series 51480 ACM 8RF Doc 50362 Addressable Devices and SLC Wiring Doc 51309 CHG 120F Charger Doc 50888 TERM EIA 485 Annunciators ACS EIA 485 Annunciators SLC Loop Battery Connector 92udperi cdr CHG 75 Charger Doc 51315 ...

Страница 12: ...th a speed of 14 4 kbps or faster and Fire Lite Upload Download software kit PK CD may serve as a Service Terminal This allows download of the entire program or upload of the entire program history file walktest data current status and system voltages MS 9200UDLS is used in this manual to refer to both the MS 9200UDLS and the MS 9200UDLSE FACPs Fire Alarm Control Panels Inventory When the MS 9200U...

Страница 13: ...nchronization per NAC Remote Acknowledge Alarm Silence Reset and Drill via addressable modules AFM annunciators or LCD 80F Remote annunciator Auto program learn mode reduces installation time Reports two devices set to the same address Password and key protected nonvolatile memory User programmable password Fully programmable from local keypad or optional keyboard Upload Download local or remote o...

Страница 14: ...n wiring 2 0 VDC Nominal operating voltage 24 VDC Current limit fuseless electronic power limited circuitry Maximum signaling current per circuit 2 5 amps see Figure 1 1 on page 15 End of Line Resistor 4 7 kΩ watt P N 71252 UL listed for Style Y Class B NAC Refer to the Device Compatibility Document for listed compatible devices Two Programmable Relays and One Fixed Trouble Relay TB5 TB6 TB7 Conta...

Страница 15: ...s ferrite bead 1 2 1 Current Availability The following figure illustrates the maximum current that is possible for each panel circuit and the total current available from the FACP with optional second transformer Figure 1 1 Current Availability owerdist9200ud cdr Refer to the battery calculations section for additional information Note If NACs are configured as two Style Z Class A circuits each c...

Страница 16: ...y panel includes a window for the LCD display and LED indicators as listed above The key panel which is visible with the cabinet door closed has 25 keys including a 16 key alpha numeric pad similar to a telephone keypad Function keys Acknowledge Step Alarm Silence Drill Reset lamp test Service program keys Keys labeled 1 to 9 key key 0 recall key 1st Event key Clear key Escape key Mode key Four cu...

Страница 17: ... VDC resistive and 0 5 amps 30 VAC resistive The programmable relays can be programmed for the following operations fire alarm trouble supervisory supervisory auto resettable DACT communication failure process monitor process monitor auto resettable hazard alert medical alert AC loss 1 5 Digital Alarm Communicator Transmitter Two modular phone jacks allow easy connection to telephone lines Modular...

Страница 18: ...ted battery box such as the BB 55F Batteries must be ordered separately 1 6 1 Intelligent Addressable Detectors Newer Series Intelligent addressable detectors provide information to the control panel on an SLC Signaling Line Circuit refer to the SLC Wiring Manual for detailed information on device installation wiring and operation This allows the control panel to continually process the informatio...

Страница 19: ...able modules Refer to the Device Compatibility Document for a list of approved conventional notification and initiating devices 1 6 3 300 Series Intelligent Addressable Devices Fire Lite s 300 Series Intelligent Addressable Devices are fully compatible with the MS 9200UDLS FACP The address of 300 Series devices cannot be set above 99 Refer to the SLC Wiring Manual for a list of compatible addressa...

Страница 20: ... an MS 9200UDLS directly from most IBM compatible computers including laptops and portables equipped with a serial port MS 9200UDLS program files can also be created and stored on the PC and then downloaded to the control panel The PK CD Kit includes the MS 9200UDLS Windows based Programming Utility software on CD ROM with on line help file A serial cable P N PRT PK CABLE which must be purchased s...

Страница 21: ...e FACP battery charger must be disabled by removing jumper JP5 when using the CHG 75 The charger and up to 26 AH batteries can be housed in the BB 26 battery box Larger batteries and the charger can be housed in the BB 55F battery box which can be mounted up to 20 feet away from the control panel Refer to the CHG 75 Manual for additional information 1 8 4 2 CHG 120F Battery Charger The CHG 120F is...

Страница 22: ... and a local piezo sounder It also has switches for FACP Acknowledge Silence Reset and Drill It is fixed at address 1 In Canada this module must be used to annunciate the fire alarm input points zones only ACM 32AF Annunciator Control Module annunciates 32 alarm zones with 32 red LEDs In addition it has a System Trouble LED an On Line Power LED and a local piezo sounder It also has a switch for lo...

Страница 23: ... listed filtered power supply such as the FCPS Series For more detailed information refer to the LCD 80F manual LDM Series Lamp Driver Modules Graphic Annunciator The LDM Series Lamp Driver Modules which consist of the LDM 32F master and LDM E32F expander modules are used to provide an interface to a custom graphic LED annunciator The master module provides power and control for a maximum of three...

Страница 24: ...c One Fire Lite Place Northford CT 06472 203 484 7161 Product Model Number MS 9200UDLS FCC Registration Number US 1W6AL00B9200UD Ringer Equivalence 0 0B Note This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA On the inside of the FACP door is a label that contains among other information a product identifier in the format US AAAEQ TXXXX If requested this...

Страница 25: ... as soon as possible The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE GROUND START OR PARTY LINE SERVICES When the control panel activates premise phones will be disconnected Two separate phone lines are required Do not connect both telephone interfaces to the same telephone line ...

Страница 26: ...is equipment or equipment malfunctions may give the telecommunications company cause to request the user to disconnect the equipment Users should ensure for their own protection that the electrical ground connections of the power utility telephone lines and internal metallic water pipe system if present are connected together This precaution may be particularly important in rural areas CAUTION Use...

Страница 27: ...1 Mounting Backbox The circuit board contains static sensitive components Always ground yourself with a proper wrist strap before handling any boards so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies To prevent damage to the circuit board and to facilitate backbox mounting the chassis with main circuit board and transformer can be ea...

Страница 28: ...de the tabs located on the bottom of the chassis into the mounting slots in the backbox by pressing the chassis down 4 Secure the chassis to the backbox by tightening the two mounting nuts 10 32 at the top and to ensure proper grounding use a 3 8 nut driver or socket 5 If the main circuit board is not already attached to the chassis install it by positioning the ten mounting holes over the studs o...

Страница 29: ...rmer Installation MS 9200UDLS PN 52750 A 11 04 05 29 Figure 2 3 MS 9200UDLS Cabinet Mounting 9050udencl cdr Semi Flush Mounting Do not recess box more than 3 875 into wall to avoid covering venting holes on top of box ...

Страница 30: ...Installation Mounting Transformer 30 MS 9200UDLS PN 52750 A 11 04 05 Figure 2 4 MS 9200UDLS Cabinet Dimensions 9050udcab cdr ...

Страница 31: ...l before installing the battery interconnect cable refer to the following section 2 3 2 Battery Power Before connecting the batteries to the FACP make certain that the interconnect cable between the batteries is not connected Do not connect the interconnect cable until the system is completely installed Observe polarity when connecting the batteries Connect the battery cable to J9 on the main circ...

Страница 32: ...d Refer to the Device Compatibility Document for a listing of compatible notification appliances The NACs which are located on the main circuit board may be expanded via the FCPS Series field charger power supplies The following sections describe the configuration and wiring of Style Y and Style Z Notification Appliance Circuits on the MS 9200UDLS main circuit board The NACs are configured for Sty...

Страница 33: ...ass A install NACKEY into JP6 with Class A pointing down toward circuit board as illustrated to the right Style Y Class B install NACKEY into JP6 with Class B pointing down toward circuit board NACKEY must be inserted with text side facing in toward center of main circuit board and key into key slot as illustrated to the right It is keyed to prevent incorrect insertion NACKEY card slot JP6 TB3 TB4...

Страница 34: ...such as the FCPS 24FS6 8 The 24 VDC 40 mA signal from TB2 follows that is mimics the signal on NAC1 This allows the devices connected to the power supply to be synchronized with the devices connected to NAC1 on the FACP The Remote Synchronization Output is power limited and supervised and requires a ferrite bead refer to UL Power limited Wiring Requirements on page 35 A 4 7 kΩ ELR resistor must be...

Страница 35: ...typical wiring diagram for the MS 9200UDLS is shown below Figure 2 11 Typical UL Power limited Wiring Requirements Power limited Circuits Power limited Circuits Nonpower limited Circuits Power limited Circuits Nonpower limited Circuits AC Power Grounding Stud 92udulpw cdr Nonpower limited Circuits To Batteries maintain minimum 0 25 between power limited and nonpower limited circuits wiring Ground ...

Страница 36: ...nection and wiring of two phone lines is required as shown below Figure 2 12 DACT Installation Customer Premises Equipment and Wiring Telephone Line FACP with DACT Network Service Provider s Facilities Network Demarcation Point RJ31X Jack Unused RJ 11 Jack Unused RJ 11 Jack Telephone Telephone Telephone Answering System Fax Machine Computer actadact cdr Modular Female Connectors Male Plug Connecto...

Страница 37: ... Display and the main circuit board unless the unit itself is being replaced Carefully lift the Keypad Display and rest the unit at the bottom of the main circuit board 24V NON RST POWER 24V RST POWER REMOTEPWR SUPPLYSYNC NAC 1 CLASS A NAC 1 3 CLASSB NAC 2 CLASS A NAC 2 4 CLASSB RELAY3 RELAY1 HOT NEUT EARTH BATTERY LCD DISPLAY REMOVE TO DISABLE GND FLT CUT TO MONITOR 4XTMF KISSOFF PRI ACTIVE SEC A...

Страница 38: ...Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings Maximum load for each circuit 10 mA Reverse polarity output voltage 24 VDC Remote Alarm and Remote Trouble wiring can leave the building Before installing the module place the disconnect switch to the right disconnect position to prevent accidental activation of the municipal box Not...

Страница 39: ...visory Relay 3 7 When the installation has been complete enable the 4XTMF module by sliding the disconnect switch to the left 8 Test system for proper operation NOTE Jumper JP2 on the FACP main circuit board can be used to configure the FACP supervisory relay for operation with the 4XTMF module Relay 3 at TB5 must be programmed as a supervisory relay Cutting JP2 will allow the 4XTMF to generate a ...

Страница 40: ...or to the printer or PC serial EIA 232 port If a nine pin serial connector is not available on the printer or PC use a DB25 adapter Make certain that the DB25 adapter does not swap the Transmit and Receive lines Apply power to the FACP and printer or PC Note that a ground fault zero impedance to ground may occur on the FACP dependent on the printer or PC being used due to this connection For this ...

Страница 41: ...g table describes the annunciator addresses and the corresponding addressable devices that will be annunciated at each annunciator address The MS 9200UDLS must be programmed for the annunciators installed on the system Refer to Annunciators UDACT on page 96 for information on annunciator programming Make certain to program the annunciator addresses that have been physically installed on the system...

Страница 42: ...ncorporates field programmable software In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 certain programming features or options must be limited to specific values or not used at all as indicated below Program feature or option Permitted in UL 864 Y N Possible settings Settings permitted in UL 864 Trouble Call ...

Страница 43: ...ust be acknowledged before entering any other mode To access any of the programming or read status features the Enter or Mode key must be pressed which will cause the LCD to display the following Pressing 1 while this screen is being displayed will cause the control panel to enter the Read Status Mode which allows the user to view the programmed features and status of the control panel The Read St...

Страница 44: ...ens The title of the main option screen will always be displayed at the top of the subscreens for the programmer s convenience If additional subscreens exist an Up or Down arrow will be displayed in the upper right corner of the screen being viewed The programmer can then press the keypad Up or Down arrow key to view the new subscreen To select one of the choices in a screen the programmer presses...

Страница 45: ...00000 will cause the following screen to appear If the Maintenance level password default 11111 is entered the following screen will appear Note that in the two preceding screens an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key 1 READ STATUS MODE 2 PROGRAMMING MODE 3 MANUAL DIAL MODE PROGRAMMING ENTER PASSWORD PROGRAMMING 1 AUTOP...

Страница 46: ...lay indicates that additional programming choices can be viewed by pressing the down arrow key on the keypad If a down and up arrow appear in the display pressing the down arrow key will display the subsequent Programming Screens as illustrated below while pressing the up arrow key will display the previous screen PROGRAMMING 1 AUTOPROGRAM 2 POINT PROGRAM 3 ZONE SETUP Programming Screen 1 PROGRAMM...

Страница 47: ...ram is selected the control panel will begin autoprogramming the system by communicating with each addressable device installed on the SLC loop While autoprogramming the panel will display the following When Autoprogramming is completed the control panel will display the type and quantity of each device installed on the SLC loop similar to the following display In the preceding example the display...

Страница 48: ...dd Detector Pressing 1 while viewing the Detector Screen will display the following screen which allows the programmer to add a new detector address to programming A flashing cursor will appear in the position of the first asterisk to the left The programmer keys in the three digit detector address such as 005 When the last digit is keyed in the following screen will be displayed Press the down ar...

Страница 49: ...n continue deleting detectors by pressing the ESC key which will return the display to the Delete Detector Screen 3 6 2 1 3 Edit Detector The programmer can change a detectors existing or factory default programming by pressing 3 in the Detector Screen The following screen will be displayed A flashing cursor will appear in the position of the first asterisk to the left The programmer keys in the t...

Страница 50: ...alled on the SLC and is communicating with the control panel the following will be displayed To change the programming for the displayed detector press the keyboard down arrow key to view the Edit Detector screens In the preceding example Normal indicates that the detector with the selected address is physically installed on the SLC and communicating with the control panel enabled ADJ NOUN represe...

Страница 51: ...ll not be polled by the control panel preventing the detector from reporting alarms and troubles to the panel The control panel will display the device type and address which has been disabled and will turn on the Trouble LED and Disable LED EDIT DETECTOR 1D017 1 ENABLED YES 2 TYPE SMOKE PHOTO 3 VERIFICATION OFF Edit Detector Screen 2 EDIT DETECTOR 1D017 1 WALKTEST NO 2 PAS NO 3 PRE SIGNAL NO Edit...

Страница 52: ...e display reads Verification On Each time the 3 key is pressed the display will toggle between Verification On and Verification Off For a detailed description refer to Alarm Verification None or One Minute on page 139 Walktest The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel after each device activation To enable a devi...

Страница 53: ...d PAS signaling device Following the PAS delay time zone Z001 will cause its associated control module to activate and the control panel will initiate an alarm condition Pre signal The Pre signal option programs the detector to delay panel activation for a preprogrammed time delay of up to three minutes while allowing for visual verification by a person Note that the alarm relay and communicator w...

Страница 54: ...he two digit number corresponding to the zone that is to be assigned to this device The cursor moves to the next Z designation Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zone Z00 When all desired changes have been made press the Enter key to store the zone assignments The display will return to the Edit Detector Screen 4 Note that the...

Страница 55: ...the location of the detector currently being programmed When an adjective has been selected it will appear at the top of the display as indicated by the asterisks 1 STANDARD ADJECTIVE 2 STANDARD NOUN 3 CUSTOM ADJECTIVE 4 CUSTOM NOUN Noun Adjective Screen 1 NORTH 2 SOUTH 3 EAST Adjective Screen 1 1 WEST 2 FRONT 3 CENTER Adjective Screen 2 1 REAR 2 UPPER 3 LOWER Adjective Screen 3 1 MAIN 2 FIRST 3 2...

Страница 56: ...etector currently being programmed When a noun has been selected it will appear at the top of the display as indicated by the asterisks 1 STANDARD ADJECTIVE 2 STANDARD NOUN 3 CUSTOM ADJECTIVE 4 CUSTOM NOUN Noun Adjective Screen 1 BASEMENT 2 BOILER RM 3 CLASSROOM Noun Screen 1 1 CLOSET 2 CORRIDOR 3 ELECTRIC RM Noun Screen 2 1 ELEVATOR 2 ENTRANCE 3 FLOOR Noun Screen 3 1 GARAGE 2 HALLWAY 3 HVAC RM No...

Страница 57: ...t and repeat the process to enter the next character To enter a space press the QZ key four times until a blank appears in the desired position When all characters have been entered press the Enter key to store the information The display will return to the Edit Detector Screen 5 displaying the new information at the bottom of the screen Recall Increment Function In addition the user may use the R...

Страница 58: ... zone Z01 through Z99 may be selected to link software zones 3 6 2 2 Module Programming Pressing 2 while viewing Point Program Screen 2 will allow the programmer to add delete or change the programming of an addressable module The following screen will be displayed by the control panel 3 6 2 2 1 Add Module Pressing 1 while viewing the Modules Screen will display the following screen which allows t...

Страница 59: ...ng cursor will appear in the position of the first asterisk to the left Using the panel keypad key in the module address such as 005 When the last digit is keyed in the following confirmation that the module has been deleted will be displayed 3 6 2 2 3 Edit Module Screen for Monitor Module The programmer can change a modules existing or factory default programming by pressing 3 in the Modules Scre...

Страница 60: ...d address is physically installed on the SLC and is communicating with the control panel the following screen will be displayed To change the programming for the displayed module press the keyboard down arrow key to view the following Edit Monitor screens In the preceding example Normal indicates that the module with the selected address is physically installed on the SLC and communicating with th...

Страница 61: ...he selected address corresponds to a monitor module a screen displaying information about the module with the selected address will be displayed as illustrated in the following See Page NORMAL MONITOR ADJ NOUN ZNNN 1M012 EDIT MONITOR 1M012 1 ENABLED YES 2 TYPE MONITOR Edit Monitor Screen 2 EDIT MONITOR 1M012 1 PRE SIGNAL NO Edit Monitor Screen 3 EDIT MONITOR 1M012 1 WALKTEST YES 2 ZONE ASSIGNMENT ...

Страница 62: ...he FACP response to the activation of a user defined type is the same as most previous standard types in the list thus allowing a variety of user defined types and responses To select the type of monitor module being programmed press the 2 key while viewing the Edit Monitor Screen 2 This will cause the control panel to display the following Monitor Type Screens Pressing the down arrow key will dis...

Страница 63: ...visory latching User Defined 8 same as previous Hazard Alert Tornado Alert Supervisory latching User Defined 9 same as previous Tornado Alert Future not used Future not used Tamper Supervisory nonlatching tracking User Defined 11 same as previous Tamper Supervisory Supervisory latching User Defined 12 same as previous Supervisory Supervisory AR Supervisory nonlatching tracking User Defined 13 same...

Страница 64: ...e following screen Note that Z represents the Zone Number s corresponding to this device The factory default for an unprogrammed device is Z00 for general alarm zone A flashing cursor will appear on the first 0 to the left Enter the two digit number corresponding to the zone that is to be assigned to this device The cursor moves to the next Z designation Continue entering zone assignments or the r...

Страница 65: ...djective that is to be used as a descriptor for the location of the monitor module currently being programmed 1 STANDARD ADJECTIVE 2 STANDARD NOUN 3 CUSTOM ADJECTIVE 4 CUSTOM NOUN Noun Adjective Screen 1 NORTH 2 SOUTH 3 EAST Adjective Screen 1 1 WEST 2 FRONT 3 CENTER Adjective Screen 2 1 REAR 2 UPPER 3 LOWER Adjective Screen 3 1 MAIN 2 FIRST 3 2ND Adjective Screen 4 1 3RD 2 4TH 3 5TH Adjective Scr...

Страница 66: ...ctive Screen will display screens similar to the previous Adjective and Noun Screens The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PK CD programming kit 1 STANDARD ADJECTIVE 2 STANDARD NOUN 3 CUSTOM ADJECTIVE 4 CUSTOM NOUN Noun Adjective Screen 1 BASEMENT 2 BOILER RM 3 CLASSROOM Noun Screen 1 1 CLOSET 2 CORRIDOR 3 ELECTRIC RM Noun...

Страница 67: ... appears in the desired position When all characters have been entered press the Enter key to store the information The display will return to the Edit Monitor Screen 4 displaying the new information at the bottom of the screen Recall Increment Function In addition the user may use the Recall Increment function at any time when the cursor is on the first letter of the Adjective or Noun field as fo...

Страница 68: ...t asterisk to the left The programmer keys in the three digit module address such as 002 When the last digit is keyed in if the selected address corresponds to a control module a screen displaying information about the control module with the selected address will be displayed as illustrated in the following In the preceding example Normal indicates that the module with the selected address is phy...

Страница 69: ...een Enabled Yes and Enabled No If Enabled No is selected the module will not be polled by the control panel preventing the module from activating its output devices The control panel will indicate a system trouble condition and the Disable LED will turn on if any devices are disabled EDIT CONTROL 1 ENABLED YES 2 TYPE CONTROL 3 SILENCEABLE YES Edit Control Screen 2 EDIT CONTROL 1 WALKTEST YES 2 ZON...

Страница 70: ...ew type selection Note A control module set to the Resettable Power type will follow the main circuit board 24 VDC resettable power unless the control module is disabled The following table contains control module type codes and their functions which are displayed in the Control Type screens Note For HVAC SHUTDN description refer to Control Module Operation on page 179 Control Type Special Functio...

Страница 71: ...sable control module Pressing 2 while viewing Edit Control Screen 3 displays the following screen Note that Z represents the Zone Number s corresponding to this device The factory default for an unprogrammed device is Z00 for general alarm zone A flashing cursor will appear on the first 0 to the left Enter the two digit number corresponding to the zone that is to be assigned to this device The cur...

Страница 72: ...djective that is to be used as a descriptor for the location of the control module currently being programmed 1 STANDARD ADJECTIVE 2 STANDARD NOUN 3 CUSTOM ADJECTIVE 4 CUSTOM NOUN Noun Adjective Screen 1 NORTH 2 SOUTH 3 EAST Adjective Screen 1 1 WEST 2 FRONT 3 CENTER Adjective Screen 2 1 REAR 2 UPPER 3 LOWER Adjective Screen 3 1 MAIN 2 FIRST 3 2ND Adjective Screen 4 1 3RD 2 4TH 3 5TH Adjective Scr...

Страница 73: ...ctive Screen will display screens similar to the previous Adjective and Noun Screens The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PK CD programming kit 1 STANDARD ADJECTIVE 2 STANDARD NOUN 3 CUSTOM ADJECTIVE 4 CUSTOM NOUN Noun Adjective Screen 1 BASEMENT 2 BOILER RM 3 CLASSROOM Noun Screen 1 1 CLOSET 2 CORRIDOR 3 ELECTRIC RM Noun...

Страница 74: ...r is on the first letter of the Adjective or Noun field as follows If the zero key is pressed a 0 is placed in the first letter position If the zero key is then pressed a second time with no intervening key actions the entire Adjective field is replaced with the field entered for the previous device programmed and the cursor moves to the last character of the field Recall function The Recalled Adj...

Страница 75: ...Z prompting the programmer to enter a two digit zone number 01 99 When the second digit is entered the zone will be enabled and the cursor returns to the original position next to the Z Another zone can then be enabled PROGRAMMING 1 AUTOPROGRAM 2 POINT PROGRAM 3 ZONE SETUP Programming Screen 2 ZONE SETUP 1 ENABLE 2 DISABLE 3 ZONE 97 98 99 Zone Setup Screen 1 ZONE SETUP 1 ZONES INSTALLED 2 ZONES EN...

Страница 76: ...dule in the Programming Zone Assignment Screen an output device connected to the control module can be used to indicate a PAS condition in the control panel Do not assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condition Attempting to do so will generate an error message and will be prevented by software checks Pressing 2 will cause the display to change ...

Страница 77: ...anel Note that an up and or down arrow may appear in the upper right corner of the display indicating that additional screens of zone information exists Press the up or down arrow keys to view the additional zones 3 6 3 6 Zones Disabled Pressing 3 for Zones Disabled while viewing Zone Setup Screen 2 will display a screen similar to the following This display will show all of the zones that are dis...

Страница 78: ...til Zone Type Program Screen 2 is displayed Press 2 to program zone Z02 as a Pull Station zone The display will return to the Zones Installed Screen showing zone Z02 and the Pull Station program type Repeat the procedure for each zone to be changed IMPORTANT In Zone Type Program Screen 1 selecting WATERFLOW will assign a Waterflow silenceable zone type to the selected zone Any signaling devices pr...

Страница 79: ... Loop Setup for Style 6 Style 7 wiring is the same as Style 6 with the added requirement that each addressable device on the loop must have a pair of isolator modules one on each side Note on SLC Troubles If the FACP reports an open fault on an SLC Loop programmed for Style 6 the trouble condition will latch at the FACP When the SLC Loop has been repaired the Reset button must be pressed at the FA...

Страница 80: ...Y to a user defined readout when the control panel is in Normal condition Time Date This feature allows the programmer to set the time display format 24 hr or 12 hr date and daylight savings time feature into the FACP memory Timers This option allows the programmer to set the PAS Positive Alarm Sequence time delay Pre Signal time delay and Waterflow time delay NACs This feature allows the programm...

Страница 81: ... displayed Pressing 1 while viewing the Banner Screen will select the factory default banner setting and display the following screen Pressing the Enter key will store this selection in nonvolatile memory and return the display to the Banner Screen Pressing 2 while viewing the Banner Screen will cause the following screens to be displayed These screens allow the programmer to enter a two line cust...

Страница 82: ...e The control panel time and date can be changed by pressing 3 while viewing the System Setup Screen 1 The following screen will be displayed 3 6 5 3 1 Time To change the time press 1 while viewing the Time Date Screen The following screen will be displayed A flashing cursor is located toward the top left of the display Below the cursor is the current time To change the time enter the two digit ho...

Страница 83: ...etween 12HR and 24HR Select 12HR for 12 hour display or 24HR for 24 hour display Note If the clock is changed to 24 hour military format the date will change to the European standard of Day Month Year for display purposes only 3 6 5 3 4 Daylight Savings Time Pressing 1 while viewing Time Date Screen 2 will cause the following screens to be displayed Pressing 1 while viewing Daylight Savings Screen...

Страница 84: ... the second week and 3 will select the third week while in the second sub screen pressing 4 will select the fourth week and 5 will select the last week of the selected month 3 6 5 4 Timers Timer delays for PAS Pre signal and waterflow activation can be programmed by pressing 1 while viewing System Setup Screen 2 The following screen will be displayed 3 6 5 4 1 PAS Positive Alarm Sequence Delay The...

Страница 85: ...set with a value greater than 000 the PAS Delay timer will be automatically reset to 000 Only one of the two timers can have a delay time set for it 3 6 5 4 3 Waterflow Delay A delay can be added prior to declaring a waterflow type of alarm Be careful to include any built in delays of the waterflow device The factory default setting for Waterflow delay is 000 for no delay To select a Waterflow del...

Страница 86: ...ours For Remote Station applications AC Loss Reporting Delay must be set to a delay value ranging from 15 to 23 hours Note AC Loss Delay also applies to any programmable output relay programmed for AC Loss 3 6 5 5 NAC Notification Appliance Circuit The options for the NACs on the control panel main circuit board can be configure by pressing 2 while viewing System Setup Screen 2 The following scree...

Страница 87: ...t the selected main circuit board NAC from activating its devices Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No Note The programming for NAC 1 will determine the operation of the remote power supply sync NAC 1 ENABLED YES 2 TYPE BELL 3 SILENCEABLE YES NAC Screen 1 NAC 1 ZONE 00 00 00 00 00 2 SIL INHIBITED NO NAC Screen 2 NAC 1 AUTO SILENCE 00 2 CODING ...

Страница 88: ... the Alarm Silence key or by the Auto Silence feature Each press of the 3 key will cause the display to toggle between Silenceable Yes and Silenceable No Important When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the Synced Strobe feature is selected only the audible devices will be turned off if the Silence key is pressed or if the A...

Страница 89: ...ored in memory and the display will return to NAC Screen 2 Note All silenceable control modules as well as the remote power supply sync will be controlled by the Autosilence timer for NAC 1 3 6 5 5 5 Coding only for NACs not programmed as Sync Strobe Type The Coding feature allows the programmer to select the type of output that the main circuit board notification appliances will generate when act...

Страница 90: ...ed to an on board NAC that NAC will go directly to 2nd stage coding output All other NACs not directly mapped to the activated alarm point s zone but assigned to Zone 0 will activate with a 1st stage output 3 If after the programmed time of 3 or 5 minutes the Acknowledge switch has not been pressed all NACs presently in 1st stage activation will go to 2nd stage activation 4 If an Acknowledge switc...

Страница 91: ...lay to change from the factory default of Silence Inhibit No to Silence Inhibit Yes Each press of the 2 key will cause the display to toggle between the two options 3 6 5 5 8 Sync Type If synchronized strobes were selected as the Type of device installed the type of synchronization must be selected in this option Pressing 1 while viewing NAC Screen 4 will cause the following screen to be displayed...

Страница 92: ... main circuit board relay The choice will be stored in memory and the display will return to the Relay Type Screen which will show the programmed type choice Press the Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays Note AR in SUPERVISORY AR and PROCMON AR indicates AutoResettable which means that the relay will not latch when either ...

Страница 93: ...pe input device will be nonsilenceable When Waterflow Sil Yes is selected all output devices associated with a waterflow type input device will be silenceable 3 6 6 Verify Loop Pressing 3 while viewing Programming Screen 2 will select the Verify Loop option During loop verification the FACP polls each device on the SLC to determine if the device is communicating and whether or not it responds with...

Страница 94: ...6 7 2 Erase History The Erase History option allows a user to erase all events from the history file This will provide a clean slate in order to use the history file to track future events Pressing 2 while viewing the History Screen will display the following screen Pressing 1 while viewing the Erase History Screen will erase all events from the History file During this process the display will re...

Страница 95: ... the activated device as shown below Note that the colon in the time is replaced with an asterisk to distinguish the walktest screen from an actual alarm screen After completion of the Walktest press the Esc Escape key to exit Walktest Mode and return to the Walktest Screen The results of the Walktest can now be viewed by pressing 3 while viewing the Walktest Screen The following screen will be di...

Страница 96: ...ystem To enable any of these devices press the number corresponding to the selected device shown in Annunciator Screen 1 so that Yes appears in the display to the right of the device Each press of the corresponding number key will cause the display to toggle between Enabled Yes and Enabled No Notes 1 The LCD 80F is a Terminal Mode annunciator To enable the MS 9200UDLS for LCD 80F operation program...

Страница 97: ...etween No and Yes 3 6 9 2 Onboard DACT The Onboard DACT Digital Alarm Communicator Transmitter provides communication to a central station Pressing 2 while viewing the Option Module Screen will cause the following screens to be displayed 3 6 9 2 1 Onboard DACT Enable To enable the onboard DACT press 1 while viewing Onboard DACT Screen 1 until the display reads Enabled Yes The display will toggle b...

Страница 98: ...reen 1 to program the type of secondary phone line being connected to the DACT The following screen will be displayed To select the type press 1 while viewing the Secondary Phone Line screen The following screen will be displayed Press 1 to select Touchtone dialing 2 to select Rotary dialing with a make break ratio of 67 33 or 3 to select Rotary dialing with a make break ratio of 62 38 ON BOARD DA...

Страница 99: ...the first time that downloading is performed so that the called Service Terminal can identify the control panel The factory default is 0000 To program the Panel ID press 1 while viewing Service Terminal Screen 1 The following screen will be displayed A flashing cursor will appear in the lower left corner of the display Enter a 4 digit code using the digits 0 9 and or the letters A F by entering th...

Страница 100: ...pear in the lower left corner Enter the phone number for the service terminal by keying in the first digit pressing the left arrow key and entering the second digit Continue this process until all desired numbers have been entered maximum of 20 characters Press the Enter key to store the phone number in memory and return the display to the Service Terminal Screen Valid entries are 0 9 and A F with...

Страница 101: ...igit is entered the display will return to the Service Terminal screen 3 6 9 2 5 Central Station Central Station programming configures the control panel DACT for contacting the central station Pressing 2 while viewing On Board DACT Screen 2 will cause the following screens to be displayed 3 6 9 2 5 1 Reporting Enable To enable the DACT for reporting FACP activity to the central station press 1 wh...

Страница 102: ...med amount between 0 and 99 for each unique trouble within a 24 hour period Separate limit counters keep track of each unique type of trouble Note that the number of phone line communication faults called to the Central Station are not limited by this feature No subsequent restoral message is sent to the Central Station s for a particular trouble whose call limit has been reached Local DACT annunc...

Страница 103: ...must be entered for both the Primary and Secondary Central Station Phone Numbers CENTRAL STATION 1 PRIMARY 2 SECONDARY 3 REPORT STYLE Central Station Screen 2 CENTRAL STATION 1 TEST TIME INT 24 2 ACCOUNT CODE 0000 3 24HR TST TIME 0021 Primary Secondary Screen 1 CENTRAL STATION 1 PHONE NUMBER Primary Secondary Screen 2 CENTRAL STATION 1 COMM FORMAT ADEMCO CONTACT ID Primary Secondary Screen 3 CENTR...

Страница 104: ...essing 2 while viewing Primary Secondary Screen 1 will cause the following screen to be displayed The Account Code which is assigned by a Central Station depends on the communication format being used The Account Code screen will have a flashing cursor in the lower left corner Enter the supplied account code using 0 9 and A F keys CENTRAL STATION 1 TEST TIME INT 2 ACCOUNT CODE 3 24HR TST TIME Prim...

Страница 105: ...e for up to 2 seconds then dial anyway D 3 second pause E 5 second pause and F end of phone number must be entered at end of phone number A flashing cursor will appear in the lower left corner of the screen Enter the first digit then press the right arrow key to move the cursor to the right one position Enter the second digit and repeat the process until all digits are entered Press the Enter key ...

Страница 106: ...mary Secondary Screen 3 COMM FORMAT 1 ADEMCO EXPRESS 4P1 2 ADEMCO EXPRESS 4P2 3 3P1S C18 A23 Comm Format Screen 1 COMM FORMAT 1 3P1E C18 A23 2 3P1S C19 A14 3 3P1E C19 A14 Comm Format Screen 2 COMM FORMAT 1 4P1S C18 A23 2 4P1E C18 A23 3 4P1S C19 A14 Comm Format Screen 3 COMM FORMAT 1 4P1E C19 A14 2 4P2S C18 A23 3 4P2E C18 A23 Comm Format Screen 4 COMM FORMAT 1 4P2S C19 A14 2 4P2E C19 A14 3 ADEMCO C...

Страница 107: ...value The tables on the following pages list all of the Events and their default Event Codes for the various Communication Formats Table 3 1 Communication Formats Screen Selection Communication Format Description ADEMCO EXPRESS 4P1 4 1 Ademco Express Standard DTMF 1400 2300 ACK ADEMCO EXPRESS 4P2 4 2 Ademco Express Standard DTMF 1400 2300 ACK 3P1S C18 A23 3 1 Standard 1800 Hz Carrier 2300 Hz ACK 3...

Страница 108: ...SER DEF 2 1 E HEAT DETECT 1 E DET USER DEF 3 1 E SMOKE DUCT P 1 E DET USER DEF 4 1 E DUCT SUPERVISORY 8 E DET USER DEF 5 8 E not used 0 0 not used 0 0 not used 0 0 not used 0 0 MONITOR 1 E MON USER DEF 3 1 E not used 0 0 not used 0 0 SMOKE CONVEN 1 E MON USER DEF 5 1 E HEAT DETECT 1 E MON USER DEF 6 1 E MEDIC ALERT 0 0 MON USER DEF 7 0 0 HAZARD ALERT 0 0 MON USER DEF 8 0 0 TORNADO ALRT 0 0 MON USE...

Страница 109: ...COMM FLT 0 0 PRINTER FAULT 6 A NAC 1 FAULT 6 A NAC 2 FAULT 6 A NAC 3 FAULT 6 A NAC 4 FAULT 6 A not used 0 0 VOICE EVACUATION 6 A ACS FAULT 6 A LCD_80F FAULT 6 A NAC 1 DISABLE 4 5 NAC 2 DISABLE 4 5 NAC 3 DISABLE 4 5 NAC 4 DISABLE 4 5 MEMORY FAULT 6 A CHARGER FAULT 6 A OPTION CARD 1 FAULT 6 A REMOTE SYNC FAULT 6 A not used 0 0 ZONE DISABLE 4 5 NAC_KEY_FLT 6 A NO_DEVICES_INSTLLD 6 A OFF_NORMAL_MESSAG...

Страница 110: ...HEAT DETECT 11 E1 DET USER DEF 3 11 E1 SMOKE DUCT P 11 E1 DET USER DEF 4 11 E1 DUCT SUPERVISORY 81 E1 DET USER DEF 5 81 E1 not used 00 00 not used 00 00 not used 00 00 not used 00 00 MONITOR 11 E1 MON USER DEF 3 11 E1 not used 00 00 not used 00 00 SMOKE CONVEN 11 E1 MON USER DEF 5 11 E1 HEAT DETECT 11 E1 MON USER DEF 6 11 E1 MEDIC ALERT 00 00 MON USER DEF 7 00 00 HAZARD ALERT 00 00 MON USER DEF 8 ...

Страница 111: ... 00 PRINTER FAULT 6C AC NAC 1 FAULT 66 A6 NAC 2 FAULT 67 A7 NAC 3 FAULT 68 A8 NAC 4 FAULT 69 A9 not used 00 00 VOICE EVACUATION 00 00 ACS FAULT 6D AD LCD_80F FAULT 6E AE NAC 1 DISABLE 4B 5B NAC 2 DISABLE 4C 5C NAC 3 DISABLE 4D 5D NAC 4 DISABLE 4E 5E MEMORY FAULT 46 56 CHARGER FAULT 47 57 OPTION CARD 1 FAULT 48 58 REMOTE SYNC FAULT 49 59 not used 00 00 ZONE DISABLE 42 52 NAC_KEY_FLT 4B 5B NO_DEVICE...

Страница 112: ...F 2 111 HEAT DETECT 114 DET USER DEF 3 114 SMOKE DUCT P 116 DET USER DEF 4 116 DUCT SUPERVISORY 200 DET USER DEF 5 200 not used 000 not used 000 not used 000 not used 000 MONITOR 110 MON USER DEF 3 110 not used 000 not used 000 SMOKE CONVEN 111 MON USER DEF 5 111 HEAT DETECT 114 MON USER DEF 6 114 MEDIC ALERT 100 MON USER DEF 7 100 HAZARD ALERT 150 MON USER DEF 8 150 TORNADO ALRT 150 MON USER DEF ...

Страница 113: ...COMM FLT 000 PRINTER FAULT 336 NAC 1 FAULT 321 NAC 2 FAULT 322 NAC 3 FAULT 326 NAC 4 FAULT 327 not used 000 VOICE EVACUATION 337 ACS FAULT 333 LCD_80F FAULT 334 NAC 1 DISABLE 521 NAC 2 DISABLE 522 NAC 3 DISABLE 526 NAC 4 DISABLE 527 MEMORY FAULT 304 CHARGER FAULT 300 OPTION CARD 1 FAULT 331 REMOTE SYNC FAULT 332 not used 000 ZONE DISABLE 570 NAC_KEY_FLT 300 NO_DEVICES_INSTLLD 380 OFF_NORMAL_MESSAG...

Страница 114: ...e reported as Point 258 3 6 9 2 7 Manual Dial Mode Pressing 3 while viewing On Board DACT Screen 2 will cause the following screen to be displayed Pressing 1 for Primary Phone or 2 for Secondary Phone will display the following screen Pressing 1 for Go Off Hook will cause the DACT to access the selected phone line similar to taking the phone handset off the cradle The selected phone line s red Act...

Страница 115: ...e for the printer communication Pressing the number key corresponding to the desired baud rate 2 for 4800 Baud for example will program the control panel for the selected baud rate and return the display to the Option Module Screen which will indicate Printer PC PR4800 for a supervised printer installed at 4800 baud rate Pressing 3 while viewing the Printer PC Screen will program the control panel...

Страница 116: ...F annunciators The following screen will appear when either change option is selected A flashing cursor will appear in the center of the display Enter a new five digit password such as 10101 for the Master Level After the fifth digit is entered the following screen will be displayed Pressing the Enter key will program the new password into the control panel and return the display to the Password C...

Страница 117: ...ng Note that it is necessary to autoprogram after using the Clear Whole System function Pressing 2 for ALL POINTS while viewing the Clear Program Screen 1 will clear all programming related to the SLC loop and connected addressable devices Before executing any of the Clear commands listed above the control panel will provide a warning to the user by prompting with the following display Pressing 1 ...

Страница 118: ...o the following The example above indicates that NAC 1 has been programmed to Zones 25 31 44 55 and 67 but no input devices have been programmed to any of these zones Use the up and down arrow keys to view all the NAC zones without input assignments for NAC 1 NAC2 NAC 3 and NAC 4 Note If the NACs have been configured for Class A in the Setup option only NAC1 and NAC 2 will display test information...

Страница 119: ...grammed to any input devices Use the up and down arrow keys to view all the zones without input assignments Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be displayed The Zone No Output feature allows the programmer to view the zones which have not been programmed to at least one output device not including general alarm Zone 00 The example in the pr...

Страница 120: ...display will read as follows When the Maintenance level password default 11111 is entered the following screen will appear Note that in the preceding screens an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key as shown in the following screen 1 READ STATUS 2 PROGRAMMING PROGRAMMING ENTER PASSWORD PROGRAMMING 1 POINT PROGRAM 2 HISTOR...

Страница 121: ...or A flashing cursor will appear in the bottom left corner of the display prompting for the three digit device address When the third digit is enter 001 for example a screen will appear which will allow enabling or disabling of the selected point as illustrated in the following example Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled No PROGRAMMING 1 POINT PRO...

Страница 122: ...ew events other than alarms press 3 The most recent event will be displayed on the screen To view all of the selected events press the up or down arrow keys to scroll through the list of events If no events have occurred the display will read NO EVENTS IN HISTORY Pressing 2 while viewing the History Screen will cause the following screen to be displayed Pressing 1 while viewing the Erase History S...

Страница 123: ...C 2 NAC 3 and NAC 4 Note If the NACs have been configured for Class A in the Setup option only NAC 1 and NAC2 will display test information NAC 3 and NAC 4 will display asterisks and will not be included in the test Pressing 2 while viewing the Program Check screen will display a screen similar to the following The Zone No Input screen allows the programmer to view the zones which have not been pr...

Страница 124: ... to view all the zones without output assignments 3 7 4 Walktest To perform a walktest press 1 while viewing Maintenance Screen 2 The following screen will be displayed The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest The display will read UNIT IN WALKTEST To end the Walktest press the Esc Escape key Pressing 3 after the walktest has been completed will all...

Страница 125: ...ering the time The display will return to the Time and Date Screen displaying the new time To change the date press 2 while viewing the Time and Date Screen The following screen will be displayed A flashing cursor will appear on the left side of the display Enter the two digit month two digit day and four digit year The cursor will move one position to the right after each entry When the fourth di...

Страница 126: ... zone to be enabled can then be entered Press Esc Escape to return to the previous screen Pressing 2 while viewing Zone Setup screen will display the following screen A flashing cursor appears to the right of the Z To disable a zone enter the two digit zone number 00 99 After the second digit is entered the zone will be disabled and the cursor will return to the original position The next zone to ...

Страница 127: ... module can be used to indicate a PAS condition in the control panel Do not assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condition Pressing 2 will cause the display to change to Pre signal 98 On Each press of the 2 key will cause the display to toggle between Pre signal 98 On and Pre signal 98 Off When Zone 98 is programmed On a Pre signal activation of...

Страница 128: ...ilenced LED to turn on It also sends an alarm silenced message to the printer history file and optional annunciators A subsequent new alarm will resound the system NACs Note that the Alarm Silenced LED is turned off by pressing the Reset key the Drill key or subsequent activation of the NACs 4 1 3 Drill Hold 2 Sec When the Drill key is held for a minimum of two seconds time required to prevent acc...

Страница 129: ...y is pressed The LED turns off when all trouble conditions are cleared This LED will also illuminate if the microprocessor watchdog circuit is activated Maintenance This is a yellow LED that flashes to indicate that a smoke detector requires cleaning or replacement due to an invalid chamber reading or excessive drift Alarm Silenced This is a yellow LED that turns on after the Alarm Silence key is ...

Страница 130: ...key presses Performs autotest for all SLC devices Tests memory Updates and reads all communications busses EIA 485 EIA 232 etc 4 4 Trouble Operation With no alarms in the system the detection of a trouble will cause the following The piezo to pulse 1 second On and 1 second Off The system Trouble LED to flash one second On and one second Off The trouble relay to activate TROUBL with device type nou...

Страница 131: ...y via PC Third line in display INVREP indicates an invalid reply from the addressable device Other possible troubles include SHORT indicating a shorted circuit on an addressable device OPEN indicating an open circuit on an addressable device DIRTY1 maintenance alert indicating that a detector is near but below the allowed alarm limit and is in need of maintenance before the performance is compromi...

Страница 132: ...arms are scrolled on the display 4 5 Alarm Operation Alarm operation is similar to trouble operation with the following differences The piezo sounder produces a steady output as opposed to a pulsed output The Fire Alarm LED flashes 1 second On and 1 second Off The LCD displays Alarm along with the device name type address adjective noun associated zones and time date Communicate the alarm to the C...

Страница 133: ...on Supervisory operation is similar to alarm operation but with the following differences The piezo sounder pulses second On and second Off The Supervisory LED flashes second On and second Off The LCD displays the status label Active Supervisory along with the device name type address adjective noun associated zones and time date Communicate the supervisory condition to the Central Station The sup...

Страница 134: ...tral Station Relays programmed for hazard will be activated The alarm relay is not activated Silenced alarms are resounded Timers are not started Store event in history buffer Supervisory LED flashes second On second Off Hazard conditions latch They can be assigned to software zones 4 9 Medical Alert Condition Operation Medical Alert Condition operation will initiate the following events The piezo...

Страница 135: ...by the control panel for its maintenance status If a detector is near but below the allowed alarm limit a maintenance alert message will automatically be displayed signaling that the detector is in need of servicing Automatic Test Operation An automatic test of an addressable detector is performed each minute resulting in a complete SLC loop test in approximately 5 hours if the loop has the maximu...

Страница 136: ...device to delay the activation of NACs and or control modules while allowing visual verification by a person Once a detector or monitor module triggers an alarm the onboard piezo sounds immediately but the NACs are not activated for a user programmed time duration of up to three minutes Note that the alarm relay and communicator will respond to the initial alarm immediately In addition Zone 98 wil...

Страница 137: ...e delay the alarm will be processed immediately causing activation of the appropriate output zones The events which occur upon PAS activation are as follows onboard piezo sounds immediately control panel LCD display will indicate a presignal event and the active point control points programmed to Zone 97 will activate annunciators if enabled will sound the local piezo and pulse the alarm LED and z...

Страница 138: ...er Autosilence operation requires the approval of the local Authority Having Jurisdiction 4 20 3 Trouble Reminder If selected this feature causes a reminding beep every 15 seconds during an alarm after the Alarm Silence key is pressed and every two minutes during a trouble condition after the Acknowledge Step or Alarm Silence key is pressed The beeps from the onboard piezo sounder will occur until...

Страница 139: ...building and store the walktest information in a file at the panel A silent walktest will not sound the NACs but will store the walktest information in a file which can be viewed at the panel Disabled NAC devices will not activate during walktest Alarm Shorted Condition When in audible Walktest the panel responds to each new alarm and activates its programmed control outputs for four seconds if th...

Страница 140: ...ing Pressing 1 while this screen is being displayed will cause the control panel to enter the Read Status mode which allows the user to view and print the programmed features and status of the control panel The following screens will be displayed 1 READ STATUS MODE 2 PROGRAMMING MODE 3 MANUAL DIAL MODE READ STATUS 1 SYSTEM POINT 2 ZONES 3 POWER READ STATUS 1 TROUBLE REMINDER 2 TIMERS 3 NACS Read S...

Страница 141: ...y similar to the following will appear The information in the preceding display includes NORMAL the present status could also be ALARM TROUBL DISABL etc SMOKE PHOTO the device type which is a photoelectric smoke detector could also be ION for ionization smoke detector NORTH CLASSROOM the Adjective Noun label for this device Z005 the first of five possible assigned software zones 1D001 1 SLC Loop D...

Страница 142: ... Read Status Screen 1 will cause the following screens to be displayed From the preceding screens the control panel operator can view Zones Installed all software zones programmed into the system 99 maximum Zones Enabled all software zones that are enabled Zones Disabled all software zones that have been disabled Special Purpose on or off programming for Special Purpose Zones 97 reserved for PAS 9...

Страница 143: ...B operation The following table lists the circuit being measured possible conditions and their respective voltage ranges Circuit Condition Voltage Range Battery Normal Battery nominal 27 05 to 28 15 VDC Low Battery 20 0 to 20 8 VDC No Battery 0 to 18 36 VDC 24V Resettable Normal 21 25 to 27 50 VDC 24V Nonresettable Normal 21 25 to 27 50 VDC Charger Normal 21 87 to 29 84 VDC NAC 1 or NAC 2 Normal 1...

Страница 144: ...r Off 4 22 5 Timers Pressing 2 while viewing Read Status Screen 2 will cause the following Timer screens to be displayed These screens will indicate the delay time in seconds for each of the first three possible delay options The AC Loss Delay time is displayed in hours READ STATUS 1 TROUBLE REMINDER 2 TIMERS 3 NAC Read Status Screen 2 TROUBLE REMINDER TROUBLE REM ON TIMERS PAS DELAY 000 PRE SIGNA...

Страница 145: ...C 4 The resulting screens will display the following information Enable Disable Status Circuit Type Bell Strobe etc Silenceable Nonsilenceable Auto Silence Enable Disable and time delay in minutes Coding Selection Temporal Steady etc Zone Assignments Silence Inhibit Enabled Disabled Synchronization Type System Sensor Wheelock or Gentex 4 22 7 Relays Pressing 1 while viewing Read Status Screen 3 wi...

Страница 146: ...f any output zones have not been programmed to at least one input zone Use the up and down arrow keys to view all zones Pressing 3 while viewing the Program Check screen will display a screen which will indicate if any input zones have not been programmed to at least one output zone Use the up and down arrow keys to view all zones 4 22 9 History Pressing 3 while viewing Read Status Screen 3 will d...

Страница 147: ...ode Annunciator addresses which have been programmed into the control panel 4 22 11 Phone Line Pressing 2 while viewing Read Status Screen 4 will display the following screen This screen indicates the both the Primary and Secondary phone lines have been configured for touchtone dialing operation READ STATUS 1 ANNUNCIATORS 2 PHONE LINE 3 CENTRAL STATION Read Status Screen 4 ANNUNCIATORS TERM ENABLE...

Страница 148: ...ral Station phone numbers and the Call Limit for DACT trouble calls within a 24 hour period Central Station Screen 2 provides information on the Primary and Secondary Central Station programming which includes Test Time Interval Account Code 24 Hour Test Time Phone Number Communication Format Event Codes READ STATUS 1 ANNUNCIATORS 2 PHONE LINE 3 CENTRAL STATION Read Status Screen 4 CENTRAL STATION...

Страница 149: ...Screen 2 4 22 14 Printer PC Pressing 2 while viewing Read Status Screen 5 will display the following screens The display will inform the operator as to whether the control panel is configured for a printer or a PC In the example above PR4800 indicates that the panel is configured for a printer with a baud rate of 4 800 READ STATUS 1 SERVICE TERMINAL 2 PRINTER PC 3 PRINT Read Status Screen 5 SERVIC...

Страница 150: ...be within the indicated range for the following smoke detectors SD350 T D350P R and SD300 T Addressable Photoelectric Smoke Detectors 405 2100 obscuration of 1 00 ft to 3 66 ft CP350 and CP300 Addressable Ionization Smoke Detectors 750 2100 obscuration of 0 50 ft to 1 44 ft If the addressable smoke detector s Chamber reading is not within the acceptable range clean the detector and check the Chamb...

Страница 151: ...sient noise signals usually caused by electrical interference Maintenance Alert The software determines when the drift compensation for a detector reaches an unacceptable level that can compromise detector performance When a detector reaches an unacceptable level the control panel indicates a maintenance alert Table 4 1 summarizes the three levels of maintenance alert Figure 4 1 illustrates a grap...

Страница 152: ...ght savings time and the month and week when daylight savings time will begin and end Pressing 1 while viewing Read Status Screen 6 will display the following screens READ STATUS 1 TIME DATE Read Status Screen 6 DAYLIGHT SAVINGS ENABLED YES START MONTH APR START WEEK WEEK 1 DAYLIGHT SAVINGS END MONTH OCT END WEEK LAST W ...

Страница 153: ...ime that the control panel needs to make a call to a Central Station line seizure will disconnect any local premises phones sharing the same telephone line All transmissions to the Central Stations will be sent over the primary phone line In the event of noisy phone lines transmissions will be sent over the backup secondary phone line Two phone numbers must be programmed the primary Central Statio...

Страница 154: ...RTZ2 SSSS RTZZ System Trouble SSS S TS SSS S TS TSTSTS TS Y SSSS TSTS2 SSSS TSY System Trouble Restore SSS S RTS SSS S RTS RTSRTSRTS RTS Y SSSS RTSRTS2 SSSS RTSY Zone Disable SSS S DZ SSS S DZ DZDZDZ DZ Z SSSS DZDZ2 SSSS DZZ Zone Disable Restore SSS S RDZ SSS S RDZ RDZRDZRDZ RDZ Z SSSS RDZRDZ2 SSSS RDZZ Low Battery SSS S L SSS S L LLL L L2 SSSS LL2 SSSS LL2 Low Battery Restore SSS S RL SSS S RL RL...

Страница 155: ...Z Zone Disable Restore 1st digit RDZ2 Zone Disable Restore 2nd digit L Low Battery 1st digit L2 Low Battery 2nd digit RL Low Battery Restore 1st digit RL2 Low Battery Restore 2nd digit P AC Loss 1st digit P2 AC Loss 2nd digit RP AC Loss Restore 1st digit RP2 AC Loss Restore 2nd digit FD Fire Drill 1st digit FD2 Fire Drill 2nd digit RFD Fire Drill Restore 1st digit RFD2 Fire Drill Restore 2nd digit...

Страница 156: ...ppliance Circuits fault Communication trouble Annunciator trouble System off normal 4 Restoral Reports Zone alarm Supervisory Zone s enabled Fire drill AC Zone fault Earth Battery Telephone line Notification Appliance Circuits Communication Annunciator trouble System off normal 5 24 Hour Test lowest priority Red LEDs are provided on the circuit board to identify which telephone line is activated A...

Страница 157: ...able provides a list of compatible receivers and associated software versions for the receivers Changes in the hardware and or software by the receiver manufacturers may affect the receiver compatibility with the FACP DACT After completing the installation communication between the DACT and Central Station Receiver must be tested and verified Table 5 3 Compatible UL Listed Receivers Format Address...

Страница 158: ... of a successful download the green Kissoff LED will turn on steady for five seconds and the red phone line active LED will turn off In order to download the panel whether initiated at the jobsite or remotely the following must be true The control panel must be in the Normal Mode of operation Downloading is not possible if the panel is in any other mode There cannot be any active communications on...

Страница 159: ... system trouble or alarm condition occur the control panel immediately terminates downloading and processes the trouble or alarm locally and transmits the information to the Central Station s 6 1 1 Security Features Remote site upload and download with the control panel has been carefully designed to include key security features to ensure proper functionality The key features are listed and expla...

Страница 160: ...ad download was not successful is called to the Central Station s Central Station Acknowledge There is an option referred to as the callback option whereby the control panel will report to one or both Central Stations that a request for uploading or downloading has been received prior to processing the call If the Central Station s does not acknowledge receipt of this request uploading or download...

Страница 161: ...fy secret code and panel identification number 3 Verify callback vs no callback request from the service terminal If callback is requested steps 4 through 9 will occur If no callback is requested only steps 8 and 9 will occur 4 Identify the Service Terminal location 5 Hang up disconnect call 6 Call the Central Station s and transmit a request for upload download message if programmed to do so If t...

Страница 162: ...coming call is accepted answered by the control panel the panel will 1 Establish basic modem connection 2 Verify secret code and panel identification number 3 Verify callback vs no callback request from the service terminal If callback is requested steps 4 through 9 will occur If no callback is requested only steps 8 and 9 will occur 4 Identify the Service Terminal location 5 Hang up disconnect ca...

Страница 163: ...ction to a separate dedicated AC branch circuit which must be labeled FIRE ALARM This branch circuit must connect to the line side of the main power feed of the protected premises No other non fire alarm equipment may be powered from the fire alarm branch circuit The branch circuit wire must run continuously without any disconnect devices from the power source to the control panel Overcurrent prot...

Страница 164: ...A Table 7 2 shows how to convert milliam peres and microamperes to full amperes 7 3 2 How to Use Table 7 3 on page 165 to Calculate System Current Draw Use Table 7 3 on page 165 to calculate current draws as follows 1 Enter the quantity of devices in all three columns 2 Enter the current draw where required Refer to the Device Compatibility Document for compatible devices and their current draw 3 ...

Страница 165: ...PL X 0 00030 X 0 00030 D350RP D350RPL X 0 00030 X 0 00030 B501BH B501BHT7 X 0 001 X 0 001 B224RB Relay Base X 0 00050 X 0 00050 B224BI Isolator Base X 0 00045 X 0 00045 MMF 300 X 0 00040 X 0 00040 MMF 300 10 X 0 00350 X 0 00350 MDF 300 X 0 00075 X 0 00075 MMF 301 X 0 000375 X 0 000375 MMF 302 X 0 00027 X 0 00027 MMF 302 6 X 0 00200 X 0 00200 BG 12LX X 0 00023 X 0 00023 CMF 300 X 0 00039 X 0 00039 ...

Страница 166: ... standby power followed by 5 minutes in alarm NFPA 72 Central Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby followed by 5 minutes in alarm Batteries installed in a system powered by a generator need to provide at least 4 hours of standby power 7 4 2 Selecting and Locating Batteries Select batteries that meet or exceed the total ampere hours calculated in Table 7 4 The...

Страница 167: ...ned to it and from 1 to 99 addressable output devices assigned to it Monitor and control modules comprise one group of 99 addresses with each module having a unique address from 1 to 99 Detectors comprise a separate group of 99 addresses each detector having a unique address from 1 to 99 in its group Be careful not to duplicate addresses within any one group modules and detectors Refer to the foll...

Страница 168: ...ically above are also presented in Table A 1 on page 169 and Table A 2 on page 170 Input Devices Zones Output Devices ZONE 01 ZONE 02 ZONE 03 SD350 01 SD350 02 MMF 300 01 MMF 302 02 MMF 302 03 CP350 03 CP300 04 SD350 05 SD350 06 SD350 07 MMF 302 04 CMF 300 06 CMF 300 05 CMF 300 07 CMF 300 09 CMF 300 08 CMF 300 10 CMF 300 11 CMF 300 12 CMF 300 13 ...

Страница 169: ...SD350 1 FIRST HALL 51 02 SD350 1 ELEV LOBBY 52 03 CP350 2 2ND FLOOR 53 04 CP350 2 ROOM 210 54 05 SD350 3 3RD FLOOR 55 06 SD350 3 MEZZANINE 56 07 SD350 3 MECH ROOM 57 08 58 09 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 73 24 74 25 75 26 76 27 77 28 78 29 79 30 80 31 81 32 82 33 83 34 84 35 85 36 86 37 87 38 88 39 89 40 90 41 91 42 92 43 93 44 94 45 95 46 96 ...

Страница 170: ... MMF 300 1 51 02 MMF 302 1 2 52 03 MMF 302 1 2 53 04 MMF 302 3 54 05 CMF 300 1 55 06 CMF 300 1 56 07 CMF 300 1 57 08 CMF 300 2 58 09 CMF 300 1 2 3 59 10 CMF 300 2 60 11 CMF 300 3 61 12 CMF 300 3 62 13 CMF 300 1 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 73 24 74 25 75 26 76 27 77 28 78 29 79 30 80 31 81 32 82 33 83 34 84 35 85 36 86 37 87 38 88 39 89 40 90 41 91 42 92 43 93 44 94 ...

Страница 171: ... Zone Number ADJ NOUN Address Device Type Zone Number ADJ NOUN 01 51 02 52 03 53 04 54 05 55 06 56 07 57 08 58 09 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 73 24 74 25 75 26 76 27 77 28 78 29 79 30 80 31 81 32 82 33 83 34 84 35 85 36 86 37 87 38 88 39 89 40 90 41 91 42 92 43 93 44 94 45 95 46 96 47 97 48 98 49 99 50 ...

Страница 172: ...e Type Zone Number ADJ NOUN Address Device Type Zone Number ADJ NOUN 01 51 02 52 03 53 04 54 05 55 06 56 07 57 08 58 09 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 73 24 74 25 75 26 76 27 77 28 78 29 79 30 80 31 81 32 82 33 83 34 84 35 85 36 86 37 87 38 88 39 89 40 90 41 91 42 92 43 93 44 94 45 95 46 96 47 97 48 98 49 99 50 ...

Страница 173: ...pe Monitor Waterflow Retard Timer 0 Module Walktest Yes NAC 1 2 3 4 Enable Enabled not used NAC 1 2 3 4 Silenceable Yes Module Presignal No NAC 1 2 3 4 Type Bell Module Zone Assign 000 only NAC 1 2 3 4 Sync Type System Sensor Module Adj Noun none NAC 1 2 3 4 Autosilence 0 Zone 0 Enable Enabled NAC 1 2 3 4 Coding Steady Zone 1 Enable Enabled NAC 1 2 3 4 Zones Zone 000 only Zone 2 Enable Enabled NAC...

Страница 174: ... the NFPA 72 standards listed below NFPA 72 NATIONAL FIRE ALARM STANDARDS FOR NFPA 72 Central Station Service Protected Premises Unit or Remote Station Service Onboard Digital Alarm Communicator Transmitter for connection to a compatible listed Central Station DACR or Protected Premises Receiving Unit This unit must be installed as outlined in Digital Alarm Communicator Transmitter on page 17 OR 4...

Страница 175: ...rol panel to Municipal Box 2 Cut JP3 on the MS 9200UDLS main circuit board to supervise placement of 4XTMF module and circuit 3 Cut JP2 on the MS 9200UDLS main circuit board to enable FACP Supervisory relay 4 Refer to 4XTMF Transmitter Module Installation on page 38 for detailed information Figure C 1 Municipal Box Connected to F Transmitter Module FIRE Gamewell Model M34 56 Local Energy Municipal...

Страница 176: ...le Installation on page 38 for detailed information RS82 Remote Station Receiver UL listed Refer to Instruction Manual for Remote Station Receiver Model RS82 Polarity Shown is Normal Standby 4XTMF Transmitter Module Cutting TBL Jumper allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists Power limited Figure C 2 Remote Station Connection Using 4XT...

Страница 177: ...pervisory condition Form C Trouble contact which will automatically activate on any Trouble condition Form C Alarm contact programmed to activate on General Alarm MS 9200UDLS Main Board MS 9200UDLS Addressable Fire Control Panel Notes 1 Connection between the MS 9200UDLS and the transmitter are supervised by the transmitter 2 This MS 9200UDLS Transmitter arrangement can be employed for NFPA 72 Pro...

Страница 178: ...30 mm2 Genesis WG 4311 WG 4511 Belden 5220UL 6220UL 18 AWG 0 78 mm2 Genesis WG 4306 WG 4506 Belden 5320UL 6320UL Untwisted unshielded pair 3 000 900 m 12 18 AWG 3 25 0 75 mm2 ACS TERM EIA 485 power limited Connects to annunciator modules Twisted shielded pair with a characteristic impedance of 120 ohms 6 000 1 800 m 18 AWG 0 75 mm2 EIA 232 power limited connects to remote printer and PC computer T...

Страница 179: ...ill indicate a supervisory condition at the FACP and the display should indicate the HVAC is shut down Once activated the HVAC SHUTDN control module remains activated even if the FACP is silenced or reset After the alarm condition on the FACP has been cleared and the panel reset the HVAC SHUTDN control module remains activated and the fans remain off The monitor module programmed for Supervisory A...

Страница 180: ...e code to the monitor module which will be used to override the HVAC SHUTDN control module and prevent the fans from turning off refer to Type Monitor under the section titled Edit Module Screen for Monitor Module on page 59 The HVAC OVRRIDE monitor module does not latch when activated Activating a switch connected to the monitor module will override all HVAC SHUTDN control modules in the system p...

Страница 181: ...AF Annunciator 22 AFM annunciator 41 AFM 16AF Annunciator 22 AFM 16ATF Annunciator 22 AFM 32AF Annunciator 22 Alarm 132 Alarm Silence 16 128 alarm verification 13 52 135 139 annunciator 22 ACM 13 41 ACM 8RF 13 LCD 80F 13 LDM Graphic 13 annunciator addressing 41 annunciator graphic see also LDM Series 23 annunciator remote see also LCD 80F 23 Automatic Test Operation 135 Autoprogramming 13 43 47 Au...

Страница 182: ...tion control module 74 detector label 57 monitor module 67 Detector add 48 adding description 54 delete 49 edit 49 enable disable 51 screen display 50 type 52 verification 52 detector data 135 150 151 acceptable range 150 printout 150 Detector Programming 48 device addressing 79 Digital Communicator 24 dimensions cabinet 29 DIRTY1 151 DIRTY2 151 Disable 76 Disable Point Maintenance Level 121 Downl...

Страница 183: ...l Dial Mode 114 Manual programming 43 Master Program Level 1 44 46 Medical Alert 134 Mode key 45 Module add 58 addressing 19 delete 59 edit monitor 59 enable disable 62 see also addressable modules 19 Module Programming 58 Monitor module 19 adjective 65 enable disable 62 noun 66 noun adjective 64 type 62 type action 63 Type list 62 type selection 63 Mounting cabinet 27 main circuit board 27 munici...

Страница 184: ...nfiguration 40 connection 40 ground fault 40 Phone Number 105 Piezo see also sounder 16 PK CD Programming Utility 20 Point Program 48 Positive Alarm Sequence 53 137 see also PAS 13 power NAC 12 nonresettable 14 resettable smoke 14 system 12 power supply calculations 163 power limited relay connections 32 Power up first time 44 Pre signal 13 53 76 function 136 selection 64 Pre signal Delay timer 85...

Страница 185: ...e detector sensitivity 135 Service Terminal 99 100 Signal rate 13 Signaling Line Circuit see also SLC 14 Silence Inhibit 13 91 138 Silenceable control module 71 NAC 88 waterflow 93 silenceable circuits synchronized signals 88 Silenceable waterflow 78 SLC 12 17 current 14 reference manual 14 resistance 14 see also Signaling Line Circuit 12 14 Style 17 voltage 14 wiring length 14 SLC Loop Protocol 7...

Страница 186: ...5 see also power limited and nonpower limited 32 Upload Download 158 Uploading 162 V Verification detector 52 Verify Loops 93 View Events 94 voltage measurements 143 ranges 143 W Walktest 13 52 71 95 audible 95 Maintenance Level 124 operation 139 selection 64 silent 95 waterflow nonsilenceable 78 93 silenceable 78 93 Waterflow Delay timer 84 85 Waterflow Retard Timer 138 Waterflow Silenceable 80 W...

Страница 187: ...ure a Return Material Authorization form from our Return Authorization Department This writing constitutes the only warranty made by the manufacturer with respect to its products The manufacturer does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges th...

Страница 188: ...arters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com 2005 by Honeywell International Inc All rights reserved Unauthorized use of this document is strictly prohibited ...

Отзывы: