Honeywell Modutrol IV Motors Series 90 Скачать руководство пользователя страница 5

SERIES 90 MODUTROL IV™ MOTORS

5

63-2190—3

Table 5. Series 90 Modutrol Motor Timing and Torque Ratings.

a

Timings apply to all TRADELINE models. Some OEM models are available with non-standard timing/torque.

b

The torque rating for dual-ended shaft motors is the sum of the shaft torques (power-end torque plus auxiliary-end torque).

c

Breakaway torque is maximum torque available to overcome occasional large loads such as a seized damper or valve.

d

Low timing is for M9184D1005 only.

NOTE: Some 150 lb-in. and 300 lb-in. torque adjustable stroke motors have timings that are twice that of their fixed stroke 

counterparts.

IMPORTANT

Never use a Modutrol Motor continuously at the Breakaway Torque rating.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

CAUTION

Electrical Shock or Equipment Damage Hazard.

Can shock individuals or short equipment 

circuitry.

Disconnect all power supplies before installation.

Motors with auxiliary switches can have more than 

one disconnect.

CAUTION

Equipment Damage Hazard.

Can damage the motor beyond repair.

Never turn the motor shaft by hand or with a wrench.

Forcibly turning the motor shaft damages the gear 

train and stroke limit contacts.

IMPORTANT

Always conduct a thorough checkout when 

installation is complete.

Location

Allow enough clearance for installing accessories and motor 

servicing when selecting a location (see Fig. 1). If located 

outdoors, use liquid-tight conduit connectors with the junction 

box to provide NEMA 3 weather protection. If mounted 

outdoors in a position other than upright, install a 4074ERU 

Weatherproofing Kit and liquid-tight connectors to provide 

NEMA 3 protection.

CAUTION

Motor Damage Hazard.

Deteriorating vapors and acid fumes can damage 

metal parts.

Install motor in areas free of acid fumes and other 

deteriorating vapors.

In excessive salt environments, mounting base and screws 

should be zinc or cadmium plated, not stainless steel or brass. 

Use the 220738A Adapter Bracket for mounting on these 

surfaces.

Mounting

CAUTION

Equipment Damage Hazard.

Can damage the motor beyond repair.

Always install motors with the crankshaft horizontal.

Improper motor mounting can result in inadequate 

motor gear train lubrication.

Use the following guidelines for proper motor mounting:

• Always install motors with the crankshaft horizontal.

• Mounting flanges extending from motor housing base are 

drilled for 1/4 inch (6.4 mm) machine screws or bolts.

• Non-Spring Return Motors are shipped from the factory in 

the closed position (at the limit of counterclockwise 

rotation, as viewed from the power end of the motor).

• Spring Return Motors are shipped from the factory in their 

normal position:

— Normally closed models: shipped at limit of 

counterclockwise rotation, as viewed from the power 

end of the motor.

— Normally open models: shipped at limit of clockwise 

rotation, as viewed from the power end of the motor.

NOTE: Refer to Fig. 2 for graphical representation of full 

open and full closed.

Nominal Timing

a

 in sec

Rated Torque in lb-in. (N•m)

b

Normal Running Torque

Breakaway Torque

c

90°

160°

Spring Return

Non-Spring Return

Spring Return

Non-Spring Return

30

60

25 (2.8)

35 (4)

50 (5.7)

70 (8)

15

d

/30

30

d

/60

60 (6.8)

75 (8.5)

120 (13.6)

150 (17)

30

60

150 (17)

300 (34)

60

120

300 (34)

600 (68)

Содержание Modutrol IV Motors Series 90

Страница 1: ...inal adapter available Adapter bracket for matching shaft height of older motors standard with TRADELINE motors Field adjustable stroke 90 to 160 models available Nominal timing of 30 seconds for 90 stroke and 60 seconds for 160 stroke standard Other timings available Die cast aluminum housing Integral auxiliary switches available factory mounted or can be field added to TRADELINE models Integral ...

Страница 2: ...1 Modutrol IV Order Number Guide a Electrically normally closed Shaft rotates clockwise as viewed from the power end with control signal increase Motor drives to normally closed position when powered with control wiring not connected b Electrically normally open Shaft rotates counterclockwise as viewed from the power end with control signal increase Motor drives to normally open position when powe...

Страница 3: ... control of two or three Series 90 Motors from a W973 Single zone Logic Panel or W7100 Discharge Air Controller 4074EDC 4 20 mA Resistor Kit drives one Series 90 Motor from a 4 20 mA controller 4074EED Unison Control 4 20 mA Resistor Kit provides for control of up to four Series 90 Motors from one 4 20 mA controller 4074ERU Weatherproofing Kit provides NEMA 3 rating for Modutrol IV Motors mounted ...

Страница 4: ...4 1 16 103 1 4 7 1 1 2 37 4 1 16 103 4 1 16 103 WIRING BOX MOTOR AUXILARY END POWER END ADAPTER BRACKET 2 9 16 66 5 3 8 137 6 7 16 164 9 16 15 3 4 19 TOP VIEW OF BRACKET TOP VIEW 4 5 8 116 4 1 4 107 2 5 16 58 11 16 17 4 7 8 124 5 9 16 141 1 4 7 5 13 16 148 2 POWER END 1 3 4 5 1 1 2 37 3 4 19 SPRING RETURN MODEL SHOWN SOME MODELS DO NOT HAVE AN AUXILIARY SHAFT ALL OTHER DIMENSIONS ARE THE SAME FOR ...

Страница 5: ...d motor servicing when selecting a location see Fig 1 If located outdoors use liquid tight conduit connectors with the junction box to provide NEMA 3 weather protection If mounted outdoors in a position other than upright install a 4074ERU Weatherproofing Kit and liquid tight connectors to provide NEMA 3 protection CAUTION Motor Damage Hazard Deteriorating vapors and acid fumes can damage metal pa...

Страница 6: ...ut obstruction Valve Linkages The Q100 Linkage requires the 220738A Adapter Bracket for all valve applications Applications with the Q5001 Valve Linkage do not require the 220738A Adapter Bracket see Fig 4 Junction Box When used with liquid tight conduit connectors the junction box provides NEMA 3 weather protection for the motor The junction box standard with replacement motors encloses the termi...

Страница 7: ...e Linkage M452E EQUIPMENT BASE ADAPTER BRACKET STANDARD BOLTS 4 MOTOR BOLTS PROVIDED 4 WIRING BOX NON SPRING RETURN SPRING RETURN 1 12 OR 1 4 ZINC PLATED MACHINE SCREWS OR BOLTS 1 P O W E R E N D P O W E R E N D P O W E R E N D 1 4 20 UNC 1 in LONG MOUNTING BOLTS Q5001 VALVE LINKAGE M17092 MOTOR WIRING BOX POWER END OF MOTOR VALVE ...

Страница 8: ...ewdriver top as far as possible counterclockwise viewed from power end See Fig 9 Repeat in successive cam slots until inner cam is against the counterclockwise stop 2 For low torque motors 75 lb in or less skip to step 4 3 Insert 1 8 in screwdriver blade into an outer cam slot and move screwdriver top as far as possible clockwise viewed from power end See Fig 9 Repeat in successive cam slots until...

Страница 9: ...B Internal Auxiliary Switch Kits Refer to form 63 2228 for 220736A B installation instructions L1 HOT L2 1 1 2 R W B R W B T1 T2 TRANSFORMER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TRANSFORMER MAY BE INTERNAL OR EXTERNAL M770A SERIES 90 CONTROLLER MOTOR L1 HOT L2 1 1 2 R W B R W B T1 T2 TRANSFORMER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS R...

Страница 10: ...e differential from 1 to 10 reverses the switching action For example with a 10 differential switch contacts R B make and R W break on a counterclockwise closed rotation With a 1 differential switch contacts R W make and R B break on a counterclockwise closed rotation OPERATION Use Series 90 Modutrol IV Motors for standard Series 90 operation see Table 6 1 Two potentiometers one in the controller ...

Страница 11: ...FF MOTOR OPEN MOTOR CLOSE POWER END OUTER AUXILIARY CAM BLUE LEFT OUTER AUXILIARY SWITCH FAST RISEPORTION APPROX 1 DIFF 1 8 INCH STRAIGHT BLADE SCREWDRIVER RIGHT INNER AUXILIARY SWITCH SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM RED FAST RISE PORTION APPROX 1 DIFF FAST RISE PORTION APPROX 1 DIFF SLOW RISE PORTION APPROX 10 DIFF MOTOR OPEN MOTOR CLOSE POWER END OUTER AUXILIARY CAM RED LEFT...

Страница 12: ...out procedures 5 For spring return motors ensure that the valve or damper returns to normal position upon power interruption 6 Return the controller to the desired setting before leaving the job REPLACEMENT Damper Application 1 Turn off power and remove wiring from the old motor 2 Remove the crank arm from shaft of old motor and remove the old motor 3 Determine necessity of the mounting bracket If...