M7261,M7272,M7274,M7281,M7282,M7284,M7285,M7286,M7294

INSTALLATION

WIRING

Disconnect power supply before beginning wiring to

prevent electrical shock or equipment damage. All wir-
ing must comply with applicable local codes, ordi-
nances, and regulations.

Make sure that the voltage and frequency stamped on

the motor correspond to the characteristics of the power
supply. When several motors are to be connected in paral-
lel, make sure that the power supply VA rating is large
enough to provide power to all the motors to be used
without overloading. An integral transformer is used to

supply 24 Vac power to the motor. Make sure that the
power requirements stamped on the motor correspond to
the characteristics of the power supply.

The motor terminals are quick-connects located on top

of the printed circuit wiring board inside the wiring com-
partment. Access to the wiring compartment is gained by
removing the four screws on the top of the wiring box and
lifting off the cover. See Fig. 5 for terminal locations. See
Fig. 6 for the internal schematic. Fig. 7 shows connections
for typical system applications. Fig. 8 shows parallel
motor connections.

Fig. 5—Terminals and adjustments.

RIGHT/INNER 
AUXILIARY
SWITCH

INNER AUXILIARY
SWITCH CAM (BLUE)

POWER
END

OUTER AUXILIARY
SWITCH CAM (RED)

LEFT/OUTER 
AUXILIARY
SWITCH

NOTE:  FEATURES AVAILABLE ON SOME MODELS ONLY.

M5777

(+)

(-)

T2

T1

F

RIGHT/INNER 
AUXILIARY
SWITCH

INNER AUXILIARY
SWITCH CAM (BLUE)

POWER
END

OUTER AUXILIARY
SWITCH CAM (RED)

LEFT/OUTER 
AUXILIARY
SWITCH

NOTE:  FEATURES AVAILABLE ON SOME MODELS ONLY.

Y(+)

T2

T1

F (TEST)

A

B

V(-)

2 TO 10 VDC INPUT MOTORS

4 TO 20 mA NONADJUSTABLE INPUT MOTORS

NOTE:  FEATURES AVAILABLE ON SOME MODELS ONLY.

4 TO 20 mA ADJUSTABLE INPUT MOTORS

C

SPAN ADJUST
POTENTIOMETER

START ADJUST POTENTIOMETER

START ADJUST

MIN          MAX

SPAN ADJUST

MIN        MAX

RIGHT/INNER 
AUXILIARY
SWITCH

INNER AUXILIARY
SWITCH CAM (BLUE)

POWER
END

OUTER AUXILIARY
SWITCH CAM (RED)

LEFT/OUTER 
AUXILIARY
SWITCH

T1

T2

(–)

(+)

F

Содержание Modutrol IV M72 Series

Страница 1: ... Actuator motor and circuitry operate from 24 Vac Models available with factory installed transformer or an internal transformer can be field added Quick connect terminals standard screw termi nal adapter available Adapter bracket for matching shaft height of older motors is standard with replacement motors Nominal timing of 30 seconds for 90 stroke and 60 seconds for 160 stroke Valve and damper l...

Страница 2: ...wiserotationasviewed from the power end of the motor Open The limit of clockwise rotation as viewed from the power end of the motor MechanicallyNormallyClosed Springreturn normally closed motors rotate to the closed position on loss of power Mechanically Normally Open Spring return normally open motors rotate to the open position on loss of power Electrically Normally Closed Both spring return and...

Страница 3: ...P VIEW OF BRACKET ONLY 3 93 100 4 22 107 2 3 58 64 16 67 17 4 88 124 43 11 5 54 141 27 7 5 82 148 2 POWER END 4 5 37 136 1 FOR HIGH TORQUE 60 LB IN SPRING RETURN MODELS 3 9 98 FOR LOW TORQUE 25 LB IN SPRING RETURN MODELS 3 4 85 5 FOR NON SPRING RETURN MODELS 2 4 61 2 FOR HIGH TORQUE 60 LB IN SPRING RETURN MODELS 8 76 222 5 FOR LOW TORQUE 25 LB IN SPRING RETURN MODELS 8 26 209 8 NON SPRING RETURN M...

Страница 4: ...e use of an adapter bracket Ap proximately0 75in 19mm shorterthanthe7616BR Crank Arm 220741A Screw Terminal Adapter converts the stan dard quick connect terminals to screw terminals Transformers Mountedinternally provide24Vacpower to the motor 198162JA 24 Vac 50 60 Hz for electrical isolation 198162EA 120 Vac 50 60 Hz 198162GA 220 Vac 50 60 Hz 198162AA 120 208 240 Vac 50 60 Hz 4074ERU Weatherproof...

Страница 5: ...he bolts through the outer set of back slots of the motor flange and into the outer threaded holes of the bracket LINKAGES Use of the 220738A Adapter Bracket packed with the motor is optional for many damper applications Use the bracket in damper applications requiring the crank arm to rotate through the bottom plane of the motor If you do not use the bracket you will have to adjust the damper lin...

Страница 6: ...unting the motor with an adapter bracket M452D EQUIPMENT BASE ADAPTER BRACKET STANDARD BOLTS 4 MOTOR BOLTS PROVIDED 4 WIRING BOX POWER END POWER END NON SPRING RETURN SPRING RETURN 1 12 OR 1 4 ZINC PLATED MACHINE SCREWS OR BOLTS 1 P O W E R E N D P O W E R E N D P O W E R E N D ...

Страница 7: ...LVE STANDARD BOLTS M5776 MOTOR WIRING BOX BOLTS PROVIDED 4 POWER END OF MOTOR MOTOR BOLTS PROVIDED 4 WIRING BOX POWER END OF MOTOR NON SPRING RETURN SPRING RETURN 1 2 1 12 OR 1 4 ZINC PLATED MACHINE SCREWS OR BOLTS 2 FASTEN ADAPTER BRACKET TO VALVE LINKAGE AND HAND TIGHTEN BOLTS SECURE MOTOR TO BRACKET USING FOUR BOLTS PROVIDED THEN TIGHTEN BRACKET TO LINKAGE BOLTS ...

Страница 8: ...ring compartment is gained by removing the four screws on the top of the wiring box and lifting off the cover See Fig 5 for terminal locations See Fig 6 for the internal schematic Fig 7 shows connections for typical system applications Fig 8 shows parallel motor connections Fig 5 Terminals and adjustments RIGHT INNER AUXILIARY SWITCH INNER AUXILIARY SWITCH CAM BLUE POWER END OUTER AUXILIARY SWITCH...

Страница 9: ...TOR MOTOR MOTOR 2 F T1 T2 2 F T1 T2 2 F T1 T2 2 When used with liquid tight conduit connectors the wiring box provides NEMA 3 weather resistance for the motor The wiring box standard with replacement motors also provides knockouts for wiring conduits and encloses terminals The wiring box is required for housing an inter nal transformer or internal auxiliary switches Wire the motor as follows 1 Rem...

Страница 10: ...UST ZERO ADJUST AND SPAN ADJUST POTENTIOMETERS TO ACHIEVE DESIRED SEQUENCE 2 3 SEQUENTIAL OPERATION OF THREE M91XX MOTORS USING Q7230 M2893 AUXILIARY SWITCH SETTING PROCEDURE See Fig 10 CAUTION 1 Live circuits are exposed during the auxiliary switch adjustment procedure Always turn off the power before adjusting switch cams 2 Do not turn motor shaft by hand or with a wrenchbecausedamagetothemotorc...

Страница 11: ... from the controller changes and unbalance is amplified to energize the Triac switching to run the motor in the proper direction to correct the change in the temperature or the pressure The motor turns the feedback potentiometer to rebalance the circuit and stop the motor CHECKOUT After installation and linkage adjustment operate the motor through the controller Make sure that The motor properly o...

Страница 12: ...ome and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Отзывы: