EMM-3U UNIVERSAL ELECTRONIC MINIZONE™ PANEL

68-0237-2

12

Sequence of Operation

• When there is no call for heat, cool, or fan, the EMM-3U is 

in the Idle mode. No system LEDs are illuminated and the 

damper LEDs are green to indicate open.

• On a call for heat, cool, or fan, the calling zone damper 

stays open, and the other zone dampers close:

— Panel energizes the HVAC equipment and conditioned 

air is delivered to the calling zone.

— Heat LED (red), cool LED (green), or fan LED (green) 

illuminates to indicate equipment operation.

— Fan LED illuminates only during a call for circulation; it 

does not illuminate during a call for heat or cool.

• When the call is satisfied, the system enters the Purge 

mode. After Purge, all dampers return to the Open position

• Any zone thermostat can call for heating or cooling. If there 

are co-existing calls for heat and cool, the panel accepts 

the first call.

• Once a call is satisfied, or a maximum of 20 minutes has 

elapsed, the panel switches to allow the opposite call after 

completing Purge mode.

Purge Mode

• At the end of every call for heat or cool, the panel enters a 

Purge mode that holds open the calling zone damper for 

two minutes (default) or three and one-half minutes.During 

this time, the panel or the HVAC equipment can be 

configured to operate the fan. 

• The Purge LED lights to signal that the system is in the 

Purge mode. Pressing the purge override button overrides 

the Purge mode.

• Unless there is a new call for heat or cool during the Purge 

mode, all dampers are moved to the Open position at the 

end of Purge.

• The panel can be configured to open all dampers during 

purge mode.See Table 4 to configure the Purge mode 

using DIP switches 8, 9 and 10.

Individual Zone Fan Control

• The fan switch of each thermostat controls the fan 

operation for that zone.

• When the Fan switch is in the On position, the fan is 

energized, and dampers close to zones where the Fan 

switch is in Auto position.

• During a call for heat or cool at this time, the circulation 

mode ceases, and the heat or cool call is honored.

• When the zone calling is satisfied, the circulation call 

resumes.

Single- and Multi-Stage Operation

The panel can control up to two stages of heat and cool:

• First stage is energized by the thermostat

• Second stage of heating or cooling can be energized by 

the thermostat or timer.

Single-Stage

Select a single stage thermostat, see

 

Table 1.

 

Set DIP 

switches 1, 2, and 3 to Off to disable the stage timer.

Multi-Stage

THERMOSTAT-CONTROLLED STAGES

• Select a multi-stage thermostat, see Table 1, that 

energizes W2 and Y2 for second stage of heat and cool.

• Configure DIP switches 1, 2 and 3 to Off to disable the 

stage timer.

Timer Controlled Stages

• The panel stage timer energizes the second stage of heat 

or cool after the first stage has been calling for a specified 

amount of time.

• Second stage remains energized until the call for heat or 

cool is satisfied.

• See Table 5 for stage timer configuration.

Heat Pump Operation

The panel can control single or two stage heat pumps with or 

without auxiliary heat:

• Set DIP switch 4 to Off for heat pump control. This 

energizes the Y1 on a call for first stage heat or cool.

• Set DIP switch 7 to Off to engage the fan with a call for 

heat.

Thermostat Controlled Stages

• Select a thermostat from Table 1. Configure DIP switches 

1,2, and 3 to off to disable the stage timer. 

— When thermostat calls for first stage, panel energizes 

Y1, G and the correct reversing valve terminal. 

— When the thermostat calls for second stage heat on 

W2, the panel energizes the equipment W2 terminal.

• Recommended heat pump thermostats can switch the 

panel to emergency heat:

— In this mode, Y1 equipment terminal is disabled and E 

is energized on a call for heat. 

— If the same source of heat is used for emergency heat 

and auxiliary heat, W2 and E equipment terminals 

must be jumpered. 

• Emergency heat can be energized by the Em Heat switch 

on the panel.

• If the equipment is a two-stage heat pump, W2 and Y2 

equipment terminals must be jumpered and wired to the 

second stage compressor contactor. 

• If the equipment is a two-stage heat pump with auxiliary 

heat, select the TZ-4 TotalZone™ panel.

Timer Controlled Stages

If single-stage thermostats are used, the EMM-3U can 

energize second stage using stage time:

• The timer can be set to engage second stage heat or cool 

after the first stage has been calling for the specified length 

of time. 

• See Table 5 for DIP switch configuration.

Thermostat Operation

Conventional Thermostats

Conventional (R,W,Y,G) heat/cool thermostats can be used 

with the EMM-3U to control single or multi-stage gas, electric, 

or oil systems and heat pumps with or without auxiliary heat.

• For two stage heat or cool equipment, configure the stage 

timer with DIP switches 1, 2 and 3. See Table 5.

 

This 

enables the panel to engage second stage after stage one 

has been calling for the specified length of time.

Содержание MiniZone EMM-3U

Страница 1: ...rature Sensor for capacity control with adjustable high and low limits System and Zone LEDs indicate system status Automatic zone changeover with 20 minute changeover timer Individual zone fan control Thermal circuit breaker protects panel and transformer from damage if miswired Purge timer protects equipment between calls for heating and cooling Uses spring open power closed spring closed power o...

Страница 2: ...ensing Temperature Ratings Shipping 20 to 120 F Operating 40 to 150 F LED SYSTEM mode LED 5 used to communicate equipment status Red Heat Heat mode Green Cool Cool mode Yellow Purge Purge mode Green Fan Fan mode Red EM Heat Emergency Heat mode Flashing Red Heat System exceeds high DATS input Flashing Green Cool System exceeds low DATS input Flashing Yellow Purge No DATS or DATS failure Off Idle mo...

Страница 3: ...nded Thermostats System Non Programmable Programmable Single Stage T87F1859 Q539A1014 T87F4010 Q539A4026 T8501D1046 T8400C1016 T8400C1040 T8400C1099 T8501D1111 T8601D2027 T8600D2069 T8600D2028 T8601D2019 T8602D2018 T8602D2000 T8000C1002 T8000C1010 T8001C1019 PC8900 W8900A C Heat Pumpb Y594R1243a c d Y594G1252a e T8411R1002 T8411R1028 T8611G2051a T8011R1006 T8011R1014 T8011F1002 Multi Stageb T8424D...

Страница 4: ...ostat jumper on the EMM 3U disconnected The PC8900 can be used as a zone thermostat See Fig 4 for hookup The PC8900 with the W8900A or C controls up to 2 heat and 2 cool stages of conventional equipment The PC8900 with the W8900A also controls heat pump equipment Connect a jumper on the W8900 from Rc to Rh as shown Wire terminals R and C to a transformer Alternately if the zone control system curr...

Страница 5: ... LEAVE O B JUMPER ON EMM 3U DISCONNECTED EMM 3U THERMOSTAT CONNECTORS TYPICAL SINGLE STAGE THERMOSTAT WIRING 1 2 3 3 1 R C G W2Y2 O B M6M4M1 Y1 W1 E C R L 24VAC 40VA 2 M20781A W8900A C IS RECOMMEDED FOR CONVENTIONAL AND HEAT PUMP APPLICATIONS THE W8900B CANNOT SWITCH THE PANEL TO EMERGENCY HEAT LEAVE O B JUMPER ON EMM 3U DISCONNECTED 1 2 1 S1 S T1 T OUT OUT LED G Y2 Y1 W1 W2 1 2 3 4 GND C R RH RC ...

Страница 6: ...N EMM 3U DISCONNETED HEAT PUMP THERMOSTAT WITH SEPARATE W1 AND Y1 THERMOSTAT WIRING 1 2 3 1 2 EMM 3U THERMOSTAT CONNECTORS 3 R C G W2Y2 M6M4M1 Y1 C R L 24VAC 40VA O B W1 E M20783A G C R Y1 L W2 E B O COMMON C TERMINAL IS USED ONLY BY THERMOSTATS THAT REQUIRE A COMMON WIRE NORMALLY CONNECT E ON THERMOSTAT TO W1 E ON PANEL ALTERNATELY INSTALL JUMPER FROM E TO Y1 ON THERMOSTAT CONNECT O B TERMOSTAT J...

Страница 7: ... a problem with the DATS sensor 3 There is a problem with the DATS wiring The zone control panel will continue to operate correctly when the purge LED is flashing but without the high and low limit protection Equipment Wiring Conventional Equipment Wire the heating and cooling equipment to the equipment terminals on the EMM 3U Panel as shown in Fig 17 Conventional Equipment Leave DIP switch 4 set ...

Страница 8: ...ee Fig 17 and 18 for heat pump equipment wiring Refer to the manufacturer instructions for additional wiring details and substitute the EMM 3U equipment terminals for the thermostat terminals shown If the same heat source is used for auxiliary heat and emergency heat Connect the auxiliary heat to W2 Wire a jumper from W2 to E Set DIP switch 12 to Off If auxiliary heat is separate from emergency he...

Страница 9: ...ling systems require a jumper to be installed connecting RH and RC factory installed 1 C terminal connection is not required on battery powered power stealing or some electromechanical thermostats 2 Leave jumper disconnected for conventional thermostats Discharge Air Temperature Sensor See C7735 Installation Instructions for further information R C DATS DATS OFF ON EM HEAT B O Y1 Y2 G Cooling Tran...

Страница 10: ...RELAY COOLING CONTACTOR M14765A REMOVE FACTORY INSTALLED RH TO RC JUMPER 1 RC RH W1 W2 E B O Y1 Y2 G PANEL 1 TRANSFORMER L1 HOT L2 SECOND STAGE HEAT RELAY EM HEAT RELAY COOLING CHANGE OVER VALVE FIRST STAGE COMPRESSOR RELAY FAN RELAY M14767A LEAVE FACTORY INSTALLED RH TO RC JUMPER IN PLACE 1 RC RH W1 W2 E B O Y1 Y2 G PANEL 1 TRANSFORMER L1 HOT L2 SECOND STAGE HEAT RELAY COOLING CHANGE OVER VALVE F...

Страница 11: ...e switches are shipped in the On Up position See Fig 13 and Tables 4 and 5 M20888 ZONE DAMPER MOTORS M1 common M4 power open M6 power closed 24 Volt Equipment MOMENTARY PUSHBUTTON SWITCHES BOOT USED TO CLEAR THE SYSTEM AND MICROPROCESSOR PURGE OVERRIDE USED TO BYPASS THE PURGE CYCLE WHILE TROUBLESHOOTING DIP Switches see Installation Instructions for details 1 2 3 Set to off for 1 stage heat and c...

Страница 12: ...t a single stage thermostat see Table 1 Set DIP switches 1 2 and 3 to Off to disable the stage timer Multi Stage THERMOSTAT CONTROLLED STAGES Select a multi stage thermostat see Table 1 that energizes W2 and Y2 for second stage of heat and cool Configure DIP switches 1 2 and 3 to Off to disable the stage timer Timer Controlled Stages The panel stage timer energizes the second stage of heat or cool...

Страница 13: ...or heat and the second stage of emergency heat is then W2 Multi Stage Thermostats Use multi stage thermostats to control up to two stages of heat or cool with the Y2 and W2 thermostat terminals on the panel Manual and Automatic Changeover Thermostats Manual or automatic changeover thermostats can be used The panel determines the call for heat or cool based on which was called for first Subsequent ...

Страница 14: ...ontrols fan in heat Panel engages fan in heat 8 Purge Fan Purge Fan controlled by HVAC Panel engages Purge Fan 9 Purge Damper Purges into last zone calling Purges into all zones 10 Purge Time Two minutes 3 1 2 minutes 11 EM Heat Fan HVAC controls fan in EM heat Panel engages fan with heat 12 2nd Stage Em Heat Yes No Table 5 Stage Timer Configuration Time Minutes DIP Switch 1 DIP Switch 2 DIP Switc...

Страница 15: ...r W1 G on the thermostat If there is voltage there then it is a bad Y or Y1 or O B if you are using O B wire If no voltage at R any other terminal on the thermostat then it is a bad R wire Jumper the R wire to the Y or Y1 and O B if you have a wire on O B wire on the thermostat If the COOL light comes on you have a bad thermostat Replace thermostat If you jumper R Y or Y1 on the thermostat and the...

Страница 16: ... R G on the thermostat If there is voltage it is a bad W or W1 or B if you are using B wire If there is no voltage at R any other terminal on the thermostat it is a bad R wire Jumper the R wire to the W or W1 and O B if your thermostat uses it for heat changover wire on the thermostat If the HEAT light comes on you have a bad thermostat Replace thermostat If you jumper R W or W1 and O B if you hav...