MINIPEEPER® ULTRAVIOLET FLAME DETECTORS

60-2026—10

6

Mounting a  C7027A, C7927 or C7035A

Locate the Sight Pipe

The location of the sight pipe is the most critical part of the 
installation. A black iron pipe is recommended. Do not use a 
stainless steel or galvanized pipe because its internal surface 
blackens with use as deposits from the combustion chamber 
settle on it. Initially, its shiny internal surface reflects ultraviolet 
radiation, which could result in a satisfactory flame signal, 
even though the pipe may be improperly located. As it 
blackens, less ultraviolet radiation is reflected and the flame 
signal may become marginal.

Under optimum sighting conditions, the C7027A , C7927 and 
C7035A Flame Detectors can detect most common gas and 
oil combustion flames at a distance of six feet. The critical 
factors in determining the flame-detector distance separation 
are the optimized flame signal (current or voltage) and the 
flame detector temperature. Other factors may be influential 
and are associated with the specific installation. For minimum 
flame signals, see Table 1 and for ambient operating 
temperatures, refer to Specifications, page 2.

Use 1/2 in. pipe for a C7027 or C7927,  and 1 in. pipe for a 
C7035. Since no two situations are likely to be the same, 
length and sighting angle of the pipe must be determined at 
the time and place of installation. Generally, it is desirable to 
have the sight pipe tilting downward to prevent soot or dirt 
buildup.

If a C7027A or C7927A is to be used for a blast tube 
installation, its location should be determined by the burner 
manufacturer; contact the manufacturer before making any 
modifications to the installation.

In locations where water is usually sprayed on the body of the 
detector, use a C7035A. Internal threads in its base permit the 
use of waterproof flexible conduit for this type of application.

Prepare Hole In Wall Of Combustion Chamber

Cut a hole of the proper diameter for the sight pipe in the wall 
of the combustion chamber at the selected location. Flare the 
hole to leave room for small adjustments of the sighting angle. 
The taper of the hole should be about 1 in. for every 3 in. 
(25 mm for every 76 mm) of wall thickness.

Mounting The Sight Pipe (Fig. 6)

Thread one end of the pipe to fit the mounting collar on the 
detector. Cut the pipe to the desired length (as short as 
practicable), and at an angle so it fits flush with the wall of the 
combustion chamber. Tack-weld the pipe to the wall in a trial 
position. Do not permanently weld the sight pipe in place until 
after completing the Adjustments and Checkout beginning on 
page 7.

NOTE:

 If you use a swivel mount (part no. 118367A) and 
you are positive about the location and sighting 
angle, you can permanently weld the pipe.

Fig. 5. Mounting sight pipe.

Sight Pipe Ventilation

It may be necessary to ventilate the sight pipe to cool the 
flame detector or to clear the sight pipe of UV radiation 
absorbing substances such as smoke, excessive moisture or, 
in some instances, unburned fuel.

For a negative pressure combustion chamber, drilling a few 
holes in the section of the sight pipe outside of the combustion 
chamber will allow air at atmospheric pressure to flow through 
the sight pipe into the chamber. A perforated pipe nipple 
between the sight pipe and the detector can also be used (see 
Fig. 7).

For a positive pressure combustion chamber, connect a 
supply of pressurized air from the burner blower through the 
sight pipe into the chamber. The supply air pressure must be 
greater than the chamber pressure.

FLARED HOLE

REFRACTORY

BOILER
PLATE

BLACK IRON
SIGHT PIPE

TEMPORARY
TACK WELD

M3019A     

Содержание Minipeeper C7027A

Страница 1: ...nting on a one inch sight pipe C7035A housing meets Underwriters Laboratories Inc requirements for rain tightness and complies with NEMA enclosure standards types 4 and 4X C7044A mounts with a two screw bracket The UV sensor tube is enclosed in a stainless steel housing C7044A has the capability of side or end viewing in flame monitoring applications Because of their compact size the C7027A and C7...

Страница 2: ... rated for 221 F 105 C C7027A1064 has 24 ft 7 32 m leadwires Rear of detector has a clamp type connector for 1 2 in flexible metallic conduit Models are available with 1 2 in internally threaded spud connector instead of the clamp C7027A1114 has 44 in 1 118 m leadwires and 22 in 558 mm flexible conduit Dimensions See Fig 1 Replacement Part 129685 Flange Gasket NOTE The ultraviolet radiation sensin...

Страница 3: ...ls C7027A1056 C7035A1049 C7035A1064 Accessory 118367A Swivel Mount provides adjustable positioning of the C7027A or C7035A Fig 3 Installation dimensions of C7044A in in mm C7044A Minipeeper Ultraviolet Flame Detector Flame Detection Housing has two openings to permit either side or end viewing Side viewing is 1 8 as sensitive as end viewing Mounting Bracket included in 4074BVK Bag Assembly secured...

Страница 4: ... hours of continuous use within the flame detector s specified ambient temperature and voltage ratings Wearout of an ultraviolet radiation sensing tube results in failure of the UV sensor to properly discriminate between flame conditions The C7027A C7035A and C7044A Flame Detectors should only be used on burners that cycle on off periodically or in the absence of cycling are periodically checked f...

Страница 5: ...ng the axis of the pilot flame The smallest pilot flame that can be sighted must be capable of igniting the main burner see Pilot Turndown Test page 9 2 Main flame only Sighting must be at the most stable part of the flame for all firing rates 3 Pilot and main flame Sighting must be at the junction of both flames Other Radiation Sources Sensed By The UV Detector Examples of radiation sources other...

Страница 6: ...prayed on the body of the detector use a C7035A Internal threads in its base permit the use of waterproof flexible conduit for this type of application Prepare Hole In Wall Of Combustion Chamber Cut a hole of the proper diameter for the sight pipe in the wall of the combustion chamber at the selected location Flare the hole to leave room for small adjustments of the sighting angle The taper of the...

Страница 7: ...separately onto the sight pipe before mounting the detector Fig 6 Mounting a C7027A or C7927A on a combustion chamber viewed from above C7035A mounting is similar Fig 7 Mounting dimensions of 136733 Heat Block in in mm Mounting a C7044A On a Blast Tube Fig 9 The C7044 is designed to be mounted on the blast tube of a burner The exact location should be determined by the burner manufacturer Contact ...

Страница 8: ...properly supervise the combustion flame 1 Disconnect power supply before beginning installation to prevent electrical shock and equipment damage All wiring must comply with applicable electrical codes ordinances and regulations Use NEC Class 1 wiring 2 If the leadwires are not long enough to reach the terminal strip or wiring subbase make the required splices in a junction box 3 If splicing is nec...

Страница 9: ...al location or before tightening the C7044A clamp screw complete both the adjustments and checkout tests that follow and any required by the burner manufacturer Uv Sensor Tube Test NOTE For initial burner lightoff consult the burner manufacturer instructions or the instructions for the flame safeguard control During the initial burner lightoff make sure the flame safeguard control starts i e the l...

Страница 10: ... or voltage reading is desirable The flame signal must be above the minimum acceptable level for the flame safeguard control and associated amplifier as indicated in Table 1 Measure the flame signal for the pilot alone the main burner flame alone and both together unless monitoring pilot only when using an intermittent pilot or supervising the main flame only when using direct spark ignition Also ...

Страница 11: ... the leads on the Q624 or Q652 Response to Other Ultraviolet Sources Some sources of artificial light produce small amounts of ultraviolet radiation Under certain conditions an ultraviolet detector will respond to them as if it is sensing a flame Do not use an artificial light source to check the response of an ultraviolet detector To check for proper flame detector operation test for flame failur...

Страница 12: ...ll of the combustion chamber and the detector c add a shield or screen to reflect radiated heat away from the detector or d add cooling refer to Sight Pipe Ventilation page 6 4 Remove the detector and clean the viewing window with a soft clean cloth 5 Clean the inside of the sight pipe if one is used before reinstalling the detector 6 If the flame signal continues to be too low replace the plug in...

Отзывы: