Wiring The Relay Module
The Midas-M relay module contains:
Nine relays to activate external devices.
Eight gas alarm relays which indicate level 1 and level 2 alarms of each channel.
A common fault relay which indicate maintenance fault or instrument fault.
Power Supply
No separated power supply required Supplied from the Midas-M
transmitter
Power
consumption
< 1.45 W
Relay rating
1.0 A @ 30VDC or 0.5 A @ 125 VAC max, 10 uA @ 10 mV minimum
Wiring
14 AWG maximum per each channel
Specifications
Midas-M
26
User Manual
Содержание Midas-M
Страница 2: ......
Страница 6: ......
Страница 9: ...User Interface Detector s User Interface overview Midas M 9 User Manual ...
Страница 16: ...Midas M 16 User Manual ...
Страница 25: ...Generic example Midas M Isolated 4 20mA output w PoE power Midas M 25 User Manual ...
Страница 37: ...Option Operations you can Test from the selected option l Inhibit time Midas M 37 User Manual ...
Страница 55: ...3 Wait until the gas reading is stable and then click Accept Midas M 55 User Manual ...
Страница 63: ...Midas M 63 User Manual ...
Страница 64: ......
Страница 68: ......
Страница 81: ......
Страница 100: ...Midas M 100 User Manual ...
Страница 104: ...The certificate should be reinstalled when the IP address is changed Midas M 104 User Manual ...
Страница 109: ... 2019 ...