R7426D UNIVERSAL INPUT CONTROLLER
11
EN1B-0204GE51 R0403
Selecting Parameters
The parameter/configuration selection mode is used to select
control and configuration parameters (Fig. 7) for adjustment.
The displayed parameter no. corresponds with the number in
Table 3 and Table 4. Default programming is indicated by a
display of
def
.
Pushing the
+
or
-
button scrolls through the parameter list.
Pushing the
SET
button enters the adjustment mode.
Adjusting Configuration / Parameter Values
The adjustment mode is used to adjust configuration and
parameter values (Fig. 8). In this mode the selected
parameter no. is displayed and the corresponding value
flashes.
Pushing the
+
or
-
button increments or decrements the value
of the selected parameter. Parameter ranges are shown in
Table 3 and Table 4. An adjustment example is shown in
Pushing the
SEL
button retains the old parameter value.
Pushing the
SET
button accepts the parameter value and
returns to parameter/configuration selection mode.
Resetting Parameter Values to Default
Values
Pushing simultaneously the
+
or
-
button during the power up
or setting the control parameter
DefProg
(C.26) to 1 resets
all control and configuration parameters to defaults (see
Table 3 and and Table 4). Default programming is indicated
by a display of
def
.
Actual
Parameter
Value
Note: Control or Configu-
ration Parameters which
are not available
are skipped.
SET
to adjust
Parameter
Value
or
no Parameter
Value Change
SET
SEL
or
Parameter
Value Change
Fig. 8. Parameter/Configuration Adjustment Mode
Fig. 7. Parameter/Configuration Selection Mode