State at input terminals
Message to the system
Short circuit
Alarm
X ohms (EOLR value)
Ready
Open circuit
Trouble
3.9
Wiring Alarm Sounders
3.9.1
Overview
The following alarm sounder outputs are available on the control panel:
l
Two outputs, BELL 1 and BELL 2, for 2-wire external sirens. For details, see
Installing Supervised External Sirens (2-Wire Sirens BELL1/BELL2)
l
An output to a self-activating bell (SAB). For details, see
3.9.2
Installing Supervised External Sirens (2-Wire Sirens BELL1/BELL2)
3.9.2.1
Features
The control panel provides a bell output, also called alarm output, for operating
fire and burglary alarm notification appliances (E on page 34). The output is
rated 12 VDC, 1.8 A max. (each).
The output has the following options (MAXPRO Cloud):
l
Selectable for supervision.
l
Selectable for confirmation of arming ding.
l
Selectable for a timeout of 2–30 minutes.
UL
Burglary bell circuits must be programmed for a timeout of 16
minutes or longer.
UL
This control panel complies with National Fire Protection Association
(NFPA) requirements for temporal 3 pulse sounding of fire
notification appliances, and for temporal 4 pulse sounding for CO
alarm signalling (on keypad only).