68-0063—3

10

L8104A,B,C,D

SETTING AND CHECKOUT

Setting and Checkout

SET CONTROL TEMPERATURE

If the potentiometer is mounted on the control module,

turn the selector knob to the desired temperature.

If the potentiometer is remotely mounted, the position of

the flat part of the shaft determines the approximate control
temperature. Fully counterclockwise 

rotation when

the shaft is towards you is the minimum setting. Fully
clockwise

rotation is the maximum setting. Actual

temperature range depends on the control module and the
potentiometer selected. See Fig. 11.

CHECKOUT

Set the L8104 above water temperature and observe the

system through one complete cycle. Make sure system
operates as desired.

To check the thermistor or thermistor/ECO assembly,

compare its resistance as measured by an ohmmeter to the
water temperature as measured by an accurate thermom-
eter. Thermistor resistance increases as the temperature
falls. See Table 1 or 2 for the correct sensor resistance at
various temperatures.

Fig. 11—Scale range for 3K remotely mounted
potentiometer when used with L8104B Dual
Bulb Controller.

MAXIMUM SETTING AT
FULLY CLOCKWISE
POSITION

200650 POTENTIOMETER

180

o

F

135

o

F

90

o

F

3

2

1

M133A

TABLE 1—THERMISTOR RESISTANCE AT VARIOUS TEMPERATURES IN FAHRENHEIT.

Temp-

erature

Resistance (K ohms)

(°F)

0

1

2

3

4

5

6

7

8

9

40

26109

25400

24712

24045

23399

22771

22163

21573

21000

20445

50

19906

19383

18876

18383

17905

17440

16990

16553

16128

15715

60

15314

14925

14548

14180

13823

13477

13140

12812

12494

12185

70

11884

11592

11308

11032

10763

10502

10248

10000

9760

9526

80

9299

9078

8862

8653

8449

8250

8057

7869

7685

7507

90

7333

7165

7000

6839

6683

6531

6383

6238

6098

5961

100

5827

5697

5570

5446

5326

5208

5094

4982

4873

4767

110

4663

4562

4464

4368

4274

4183

4094

4006

3922

3839

120

3758

3679

3602

3527

3453

3382

3312

3244

3177

3112

130

3048

2986

2925

2866

2808

2752

2697

2643

2590

2538

140

2488

2439

2391

2344

2298

2253

2209

2166

2124

2083

150

2043

2004

1966

1928

1891

1856

1820

1786

1753

1720

160

1688

1656

1625

1595

1566

1537

1509

1481

1454

1427

170

1402

1376

1351

1327

1303

1280

1257

1235

1213

1191

180

1170

1150

1129

1110

1090

1071

1053

1035

1017

999

190

982

965

949

933

917

901

886

871

857

842

200

828

814

801

788

775

762

749

737

725

713

Содержание L8104A

Страница 1: ...ed in ratios of 1 1 2 1 3 1 and 4 1 Two sensing bulbs provide temperature averaging L8104C has two sensing bulbs and manual reset pushbutton L8104D has one sensing bulb and manual reset pushbutton 68 0063 3 Temperature range is factory set to meet application requirements Maximumsettingtemperatureis200 F 93 C ECO limit setting is factory set to meet application requirements For L8104A B standing p...

Страница 2: ...h 5 Recycling or nonrecycling ECO switch 10 Additional system components if desired If you have additional questions need further information or would like to comment on our products or services please write or phone 1 Your local Honeywell Home and Building Control Sales Office please check the white pages of your phone directory 2 Home and Building Control Customer Logistics Honeywell Inc 1885 Do...

Страница 3: ...TER M413 3 4 19 3 8 10 3 8 10 5 32 4 3 8 DIA 10 1 1 4 32 15 16 24 1 1 16 27 1 3 8 35 Fig 2 Approximate dimensions in in mm of L8104A B Electronic Control Module REPLACEMENT PARTS Replacement electronic control modules sensing bulbs and remote potentiometers are 140 1 2 0 160 180 1 0 0 SEN 1 SEN 2 LOWER UPPER 24 V HOT ONLY COM RELAY NO 3 8 10 1 2 13 1 1 8 29 9 32 7 1 25 3 15 32 88 2 15 16 75 170 DI...

Страница 4: ...or Assembly 42 in 107 cm 150 C 302 F leadwires with 1 4 in quick connects 198799C Sensor Assembly 42 in 107 cm 105 C 221 F leadwires with 1 4 in quick connects 198799D Sensor Assembly 42 in 107 cm 105 C 221 F leadwires with 1 4 in quick connects 200636A Sensor Assembly 180 F to 201 F 83 C to 94 C cutoff temperature 22 in 56 cm 150 C 302 F leadwires 200636B Sensor Assembly 180 F to 201 F 83 C to 94...

Страница 5: ...response Use heat conductive compound available in 4 oz can as Honeywell part no 107408 to fill the space between the bulb and the well and improve heat transfer characteris tics Make sure the bulb is held firmly in the well If the sensor is directly immersed use a 3 8 in x 1 2 in compression to M I P coupling or O ring and clamp to prevent leaks and keep bulb leadwires dry Electronic Control Modu...

Страница 6: ... SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FACTORY INSTALLED JUMPER DO NOT REMOVE 1 4 IN TAB TERMINALS 3 3 16 IN TAB TERMINALS 3 SENSING BULB WITH ECO SWITCH 1 L1 HOT L2 1 4 4 4 5 5 5 2 3 2 L8104A BLACK BLACK RED RED SEN 1 LOWER HOT 24V ONLY COM RELAY NO 24V 3 4 5 1ST OPERATOR 2ND OPERATOR PILOT VALVE COM MAIN VALVE VR8440 OR VR844 S8600F H M S8610F H MV MV PV PV GND BURN...

Страница 7: ... 24V ONLY HOT COM RELAY NO ECO CONNECTOR TH TR VR8200 GAS VLAVE 24V Q308 1 2 3 SETPOINT POTENTIOMETER SHOWN FROM BACK UPPER SEN 2 POT M129B POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED SENSING BULB WITH ECO SWITCH SENSING BULB 1 L1 HOT L2 1 2 3 4 2 4 4 4 4 4 3 3 3 L8104B BLACK BLACK BLACK BLACK RED RED SEN 1 LOWER 24V HOT ONLY COM RELAY NO 24V UPPER SEN 2 140 1 2 0 160...

Страница 8: ...0 9M 2 L8104C SEN 1 SEN 2 LOWER UPPER 24V PV ECO ECO VALVE COM LOAD POT 5 5 1ST OPERATOR 2ND OPERATOR PILOT COM MAIN VALVE DUAL VALVE COMBINAITON GAS CONTROL S8600H MV MV PV PV GND BURNER 24V GND 24V TH W OPT SPARK VENT DAMPER PLUG OPT BLACK BLACK BLACK BLACK RED RED Q345 Q346 Q348 Q362 Q381 PILOT BURNER IGNITER SENSOR PILOT BURNER GROUND PILOT GAS SUPPLY CONTROLS IN 24V CIRCUIT MUST NOT BE IN GRO...

Страница 9: ... CABLE LENGTH 3 FT 0 9M 2 L8104D SEN 1 LOWER 24V PV ECO ECO VALVE COM LOAD POT 5 5 1ST OPERATOR 2ND OPERATOR PILOT COM MAIN VALVE DUAL VALVE COMBINATION GAS CONTROL S8600H MV MV PV PV GND BURNER 24V GND 24V TH W OPT SPARK VENT DAMPER PLUG OPT BLACK BLACK RED RED Q345 Q346 Q348 Q362 Q381 PILOT BURNER IGNITER SENSOR PILOT BURNER GROUND PILOT GAS SUPPLY CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND L...

Страница 10: ...otely mounted potentiometer when used with L8104B Dual Bulb Controller MAXIMUM SETTING AT FULLY CLOCKWISE POSITION 200650 POTENTIOMETER 180 o F 135 o F 90o F 3 2 1 M133A TABLE 1 THERMISTOR RESISTANCE AT VARIOUS TEMPERATURES IN FAHRENHEIT Temp erature Resistance K ohms F 0 1 2 3 4 5 6 7 8 9 40 26109 25400 24712 24045 23399 22771 22163 21573 21000 20445 50 19906 19383 18876 18383 17905 17440 16990 1...

Страница 11: ...perature drops below the ECO tempera ture Before the system will restart however the system must be reset On a standing pilot system the pilot must be relit On an electronic ignition system power to the 100 percent lockout ignition module must be off for one minute A nonrecycling one shot ECO switch will not remake The sensing bulb containing the switch must be replaced L8104C D The L8104C D uses ...

Страница 12: ...RESISTANCE OF POTENTIOMETER WITH OHMMETER IS RESISTANCE GREATER THAN 1000 OHMS AT MINIMUM TEMPERATURE SETTING CHECKS FOR SHORT POTENTIOMETER OK REPLACE ELECTRONIC CONTROL MODULE RECONNECT ALL LEADS AND CHECK OUT SYSTEM SENSOR S MAY BE SHORTED OR OPEN CHECK FOR LOOSE BROKEN OR SHORTED WIRES REPLACE SENSING BULB S IF NECESSARY REPLACE SENSING BULB WITH ECO LIMIT AND CHECK OUT BALANCE OF SYSTEM REPLA...

Страница 13: ...NSOR LEADS FROM ELECTRONIC CONTROL MODULE AND MEASURE RESISTANCE OF SENSOR S WITH OHMMETER SENSORS OK IS THE POTENTIOMETER REMOTE DISCONNECT POTENTIOMETER LEADS FROM ELECTRONIC CONTROL MODULE MEASURE RESISTANCE OF POTENTIOMETER WITH OHMMETER POTENTIOMETER OK REPLACE ELECTRONIC CONTROL MODULE RECONNECT ALL LEADS AND CHECK OUT SYSTEM YES NO NO YES NO YES YES YES NO NO M135B IS VOLTAGE BETWEEN 21 5 A...

Страница 14: ...S AND CHECK OUT SYSTEM YES NO NO NO REFER TO TROUBLESHOOTING IF WATER IS TOO HOT SENSOR S MAY BE SHORTED OR OPEN CHECK FOR LOOSE BROKEN OR SHORTED WIRES REPLACE SENSING BULB S IF NECESSARY REPLACE ELECTRONIC CONTROL MODULE RECONNECT ALL LEADS AND CHECK OUT SYSTEM REPLACE POTENTIOMETER RECONNECT ALL LEADS AND CHECK OUT SYSTEM REPLACE SENSING BULB WITH ECO SWITCH NO YES DISCONNECT ECO LEADS AND MEAS...

Страница 15: ...15 68 0063 3 L8104A B C D MATERIAL SAFETY DATA SHEET ...

Страница 16: ...68 0063 3 16 L8104A B C D MATERIAL SAFETY DATA SHEET ...

Страница 17: ...17 68 0063 3 L8104A B C D MATERIAL SAFETY DATA SHEET ...

Страница 18: ...68 0063 3 18 L8104A B C D MATERIAL SAFETY DATA SHEET ...

Страница 19: ...19 68 0063 3 L8104A B C D MATERIAL SAFETY DATA SHEET ...

Страница 20: ...nd Building Control Home and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A customer honeywell com ...

Отзывы: