© 2019 Elster GmbH · Edition 04.19

Safety

Operating instructions

D

GB

F

NL

I

E

GB-1

03251434

Translation from the German

Pressure switches for air 

DL..H, DL..N

Please read and keep in a safe place

 Please read through these instructions 

carefully before installing or operating. Following the 
installation, pass the instructions on to the opera-
tor. This unit must be installed and commissioned 
in accordance with the regulations and standards 
in force. These  instructions can also be found at 
www.docuthek.com.

Explanation of symbols
 • ,  1 ,  2 ,  3 

... = Action

 

= Instruction

Liability

We will not be held liable for damage resulting from 
non-observance of the instructions and non-com-
pliant use.

Safety instructions

Information that is relevant for safety is indicated in 
the instructions as follows:

 DANGER

Indicates potentially fatal situations.

 WARNING

Indicates possible danger to life and limb.

 CAUTION

Indicates possible material damage.

All interventions may only be carried out by qualified 
gas technicians. Electrical interventions may only be 
carried out by qualified electricians.

Conversion, spare parts

All technical changes are prohibited. Only use OEM 
spare parts.

Changes to edition 09.18

The following chapters have been changed:
– Installation
–  Technical Data
– Logistics
– Certification

Checking the usage

DL..H, DL..N

For monitoring increasing and decreasing air or flue 
gas pressure.
DL..H switches and locks off with rising pressure, 
DL..N switches and locks off with falling pressure. 
They can be unlocked using the manual reset.
This function is only guaranteed when used within 
the specified limits – see page 5 (Technical data).
Any other use is considered as non-compliant.

Type code

Code

Description

DL

Air pressure switch

10 – 150

Max. setting in mbar

K

Rp ¼, tube connection and hand wheel 

Tube connection and hand wheel 

N

Locks off with rising pressure 

Locks off with falling pressure

G

With gold-plated contacts

 

-3 

-4 

-5 

-6 

-9

Electrical connection 

via screw terminals 

via screw terminals, IP 65 

4-pin plug, without socket 

4-pin plug, with socket 

4-pin plug, with socket, IP 65

K2 

T2 

N

Red/green pilot LED for 24 V DC/AC 

Blue pilot lamp for 230 V AC 

Red/green pilot LED for 230 V AC 

Blue pilot lamp for 120 V AC

A

External adjustment

Part designations

T est

1

2

3

5

4

1

  Upper housing section with cover

2

  Lower housing section

3

  Hand wheel

4

  M16 cable gland

5

  DL..H, DL..N with manual reset

Содержание kromshroeder DL H Series

Страница 1: ...d electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 09 18 The following chapters have been changed Installation Technical Data Logistics Certification Checking the usage DL H DL N For monitoring increasing and decreasing air or flue gas pressure DL H switches and locks off with rising pressure DL N switches and locks off with falli...

Страница 2: ...heel Installation position as required preferably with vertical diaphragm Then the switching point pS corresponds to the scale value SK set on the hand wheel In other installation positions the switching point pS will change and no longer correspond to the scale value SK set on the hand wheel Check the switching point pS SK pS SK 0 18 mbar pS SK 0 18 mbar Connection facilities For 1 mm thick mount...

Страница 3: ...t damaged during opera tion note the switching capacity see page 5 Technical data In the case of low switching capacities such as 24 V 8 mA for example we recommend us ing an RC module 22 Ω 1 μF in air containing silicone or oil NO C 1 µF 2 NC 1 COM 3 1 Disconnect the system from the electrical power supply M16 x 1 5 ø 4 10 mm 3 4 2 5 6 7 Contacts 3 and 2 close when subject to increas ing pressure...

Страница 4: ...imultaneously TEST TEST Accessories Z angle bracket 50 1 97 30 1 18 20 0 79 25 0 98 45 1 77 2 11 3 0 44 7 0 27 7 5 0 3 10 0 4 40 1 6 59 2 3 ø 5 5 0 22 ø 6 0 22 ø 4 2 0 17 10 0 39 1 0 04 DL K Order No 74916158 DL A Order No 74913661 Fastening set with screws U shape bracket M4 x 10 M4 x 12 50 1 97 47 5 1 87 75 2 95 30 1 18 20 0 79 25 0 98 45 1 77 20 0 79 24 0 94 43 0 3 1 69 64 2 52 40 1 57 6 0 24 1...

Страница 5: ...max withstand pressure 300 mbar Diaphragm pressure switch silicone free Diaphragm NBR Housing glass fibre reinforced PBT plastic with low gas release Max tightening torque see Technical Information bulletin DL D GB F www docuthek com Weight DL A 200 g 7 1 oz DL K 190 g 6 7 oz Electrical data Micro switch to EN 61058 1 Contact gap 3 mm μ Switching capacity U I cos φ 1 I cos φ 0 6 DL 24 250 V AC 0 0...

Страница 6: ...g for the first time If stored for longer than this the overall service life will be reduced by the corresponding amount of extra storage time Packaging The packaging material is to be disposed of in ac cordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Declaration of conformity We the manufacturer hereby declare ...

Отзывы: