Assistance in the event of 
malfunction

 DANGER

Electric shocks can be fatal! Before working on 
possible live components, ensure the unit is discon-
nected from the power supply.
Fault-clearance must only be undertaken by author-
ized trained personnel.

 

Faults may be cleared only using the measures 
described below.

 

If the control unit (BCU) does not respond even 
though all faults have been remedied: remove 
the unit and return it to the manufacturer for 
inspection.

 

If a fault message (

   0

) is active, the control unit 

can continue to be operated via its digital inputs.

 ? 

 

Faults

 ! 

 

Cause

 • 

 

Remedy

0

  ?   The display blinks and indicates 

 0

.

 !  

No connection established between BCU and 
PLC (controller).

 • 

 Check the wiring.

 • 

 Check the PLC program to ensure that the net-

work name and IP configuration of the BCU are 
valid.

 • 

 Switch on the PLC.

Or
 ?  A bus fault is indicated on the automation 

system.

 ! 

 The PROFIBUS DP data traffic has suffered a 

fault.

 ! 

 Bus cable interrupted.

 • 

 Check cable.

 ! 

 Incoming and outgoing bus cables confused in 

the plug.

 • 

 Check the wiring.

 ! 

 A and B cables confused.

 • 

 Check the wiring.

 ! 

 Terminal resistors connected incorrectly.

 • 

 Switch on the terminal resistors on the first and 

last subscriber in the segment and switch them 
off for all other subscribers.

 ! 

 Incorrect PROFIBUS address set.

 • 

 Correct the address setting – switch the unit off 

and then on again to save the address.

 ! 

 Bus cables too long.

 • 

 Reduce cable length or baud rate – see 

page 3 (Commissioning).

 

If the transfer rate is reduced, remember that 
this will increase the signal running times to and 
from the individual units.

 ! 

 Poor shielding.

 • 

 Check whether the shield is connected to the 

shield clips in the PROFIBUS DP plugs in full and 
over a wide area.

 ! 

 Poor equipotential bond.

 • 

  Check whether the PROFIBUS DP shield is con-

nected at all points to the same ground potential 
via the grounding system of the units.

 • 

  If necessary, an equipotential bonding cable must 

be laid.

 

If faults occur sporadically in the PROFIBUS DP 
system, and are only indicated briefly in the bus 
master, the following points in particular should 
be checked: 

 

– Terminal resistors,

 

– Shield,

 

– Cable lengths/routes,

 

– Equipotential bond,

 

–  Use of interference-suppressed spark electrode 

terminal boots (1 kΩ).

 

For information on planning and the structure of 
a PROFIBUS network and the components to 
be used (e.g. cables, lines and switches), see 
www.profibus.com or the instructions for the 
automation system.

E

E

 ? 

 

The display on the control unit blinks and 
indicates 

E   E

.

 ! 

 Internal communication with bus module has 

suffered a fault.

 • 

  Connected control elements must be equipped 

with protective circuits in accordance with the 
manufacturer’s instructions.

 

This prevents high voltage peaks which can 

cause malfunctioning of the BCU.

 • 

 Use interference-suppressed terminal boots 

(1 kΩ).

 • 

 If the fault cannot be remedied by doing this, 

remove the unit and return it to the manufacturer 
for inspection.

 ! 

 Bus module is defective.

 • 

 Replace the bus module.

For other control unit fault messages, see 
BCU 46x, 480 operating instructions, section 
entitled “Assistance in the event of malfunction”.

Содержание Kromschroder BCM 400 B1 Series

Страница 1: ...ctions Information that is relevant for safety is indicated in the instructions as follows DANGER Indicates potentially fatal situations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts ...

Страница 2: ...tandard communication SafetyLink B1 B2 B3 B4 PROFIBUS DP PROFINET EtherNet IP Modbus TCP 1 3 9 pin D Sub Two RJ45 sockets 0 3 Three point step control via bus Part designations 3 4 1 2 1 BCM 1 with 9 pin D Sub connection 2 9 pin D Sub connection 3 Code switches 4 Type label Ambient temperature A B see type label Elster GmbH Osnabrück Made in Germany A B Installation 1 Disconnect the BCU from the e...

Страница 3: ... and software can be downloaded from www docuthek com 1 Set parameter A080 2 Fieldbus communica tion without address check 2 Check the code switch settings 001 to 125 on the BCM for PROFIBUS communication between BCSoft and the control unit Each code switch setting combination may only exist once within the fieldbus system Each device name network name may only be allocated once within the fieldbu...

Страница 4: ...P 4 ϑ2 5 Reserved 6 Reserved 7 Reserved P A A P DI on on on 1 2 Operating signal pilot burner P A A P DI on on on 1 2 Operating signal main burner P A A P DI on on on 1 2 Fault signal P A A P DI on on on 1 2 Operating signal air actuator P A A P DI on on on 1 2 Purge operating signal P A A P DI on on on 1 2 High temperature operation P A A P DI on on on 1 2 Ready for operation P A A P DI on on on ...

Страница 5: ...missioning If the transfer rate is reduced remember that this will increase the signal running times to and from the individual units Poor shielding Check whether the shield is connected to the shield clips in the PROFIBUS DP plugs in full and over a wide area Poor equipotential bond Check whether the PROFIBUS DP shield is con nected at all points to the same ground potential via the grounding sys...

Страница 6: ... location min IP 65 for installation in BCU 4xx Permitted operating altitude 2000 m AMSL Mechanical data Dimensions W H D 96 63 23 mm 3 78 2 48 0 91 inch Weight 0 3 kg Electrical data Power consumption 1 2 VA Power loss 0 7 W Designed lifetime Max service life under operating conditions 10 years after date of production Logistics Transport Protect the unit from external forces blows shocks vibrati...

Отзывы: