Wiring

 

PROFIBUS installation guidelines, see 
www.profibus.com.

  

 Do not confuse data cables A and B in the 

 PROFIBUS  plug.

BCU..B1/1

PROFIBUS DP

1B

1A

2B

2A

OFF

ON

OFF

ON

  

 Connect the shield on both sides and over a 

wide area with shield clips in the plug.

 

Ensure an equipotential bond between the units.

  

 Switch on the terminal resistors on the first and 

last subscriber in the segment.

 4 

 Wire control signals that are relevant for safety, 

such as the safety interlocks and digital input, 
separately.

 

The purge signals can be transferred via the 

bus communication or by a separate cable via 
terminal.

 

Protect the communications network against 
unauthorized access.

Commissioning

 WARNING

Risk of explosion! Do not enable the BCM and 
control unit (BCU) for operation until the parameter 
settings and wiring are correct and the faultless 
processing of all input and output signals has been 
ensured.
If the control unit is activated via the inputs at the 
terminals in the event of faulty or interrupted bus 
communication, invalid communications data, or 
during initialization, the normal program runs. Be 
sure to take the settings of parameters A085 to 

A089 into account.

 

Fieldbus communication can be configured using 
the engineering tool of the automation system.

 

The BCSoft operating instructions and software 

can be downloaded from www.docuthek.com.

  

 Set parameter A080 = 2 (Fieldbus communica-

tion without address check).

  

 Check the code switch settings (001 to 125) on 

the BCM for PROFIBUS communication between 
BCSoft and the control unit.

 

Each code switch setting combination may only 
exist once within the fieldbus system.

 

Each device name/network name may only be 
allocated once within the fieldbus system.

 

All the device-specific parameters for the 

BCM..B1 are saved in a device master data 
file (GSD): download from www.docuthek.com.

  

 Copy the GSD file.

 

The steps required to copy the file are described 

in the instructions for the automation system.

 4 

  Configure the PROFIBUS DP using the appropri-

ate tools of the automation system you are using.

 

The BCM..B1 will automatically identify the baud 

rate (max. 1.5 Mbit/s).

 

The max. range per segment depends on the 

baud rate:

Baud rate [kbit/s]

93.75

187.5

500

1500

Range [m (ft)]

1200 

(3937)

1000 

(3280)

400

(1312)

200

(656)

 

For instructions on commissioning the control 
unit, see operating instructions “Burner control 
unit BCU 46x, 480”.

 

The ranges can be increased by using repeaters. 

No more than three repeaters should be con-
nected in series.

 

The BCU with BCM..B1 indicates 

  –– 

 when the 

mains switch has been switched off. This signals 
Standby mode. Bit 6 = 0. The bus interface is 
still supplied with voltage to maintain the func-
tion of the communications system. The control 
outputs of the BCU (valves, ignition transformer) 
are electrically isolated from the mains voltage.

Содержание Kromschroder BCM 400 B1 Series

Страница 1: ...ctions Information that is relevant for safety is indicated in the instructions as follows DANGER Indicates potentially fatal situations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts ...

Страница 2: ...tandard communication SafetyLink B1 B2 B3 B4 PROFIBUS DP PROFINET EtherNet IP Modbus TCP 1 3 9 pin D Sub Two RJ45 sockets 0 3 Three point step control via bus Part designations 3 4 1 2 1 BCM 1 with 9 pin D Sub connection 2 9 pin D Sub connection 3 Code switches 4 Type label Ambient temperature A B see type label Elster GmbH Osnabrück Made in Germany A B Installation 1 Disconnect the BCU from the e...

Страница 3: ... and software can be downloaded from www docuthek com 1 Set parameter A080 2 Fieldbus communica tion without address check 2 Check the code switch settings 001 to 125 on the BCM for PROFIBUS communication between BCSoft and the control unit Each code switch setting combination may only exist once within the fieldbus system Each device name network name may only be allocated once within the fieldbu...

Страница 4: ...P 4 ϑ2 5 Reserved 6 Reserved 7 Reserved P A A P DI on on on 1 2 Operating signal pilot burner P A A P DI on on on 1 2 Operating signal main burner P A A P DI on on on 1 2 Fault signal P A A P DI on on on 1 2 Operating signal air actuator P A A P DI on on on 1 2 Purge operating signal P A A P DI on on on 1 2 High temperature operation P A A P DI on on on 1 2 Ready for operation P A A P DI on on on ...

Страница 5: ...missioning If the transfer rate is reduced remember that this will increase the signal running times to and from the individual units Poor shielding Check whether the shield is connected to the shield clips in the PROFIBUS DP plugs in full and over a wide area Poor equipotential bond Check whether the PROFIBUS DP shield is con nected at all points to the same ground potential via the grounding sys...

Страница 6: ... location min IP 65 for installation in BCU 4xx Permitted operating altitude 2000 m AMSL Mechanical data Dimensions W H D 96 63 23 mm 3 78 2 48 0 91 inch Weight 0 3 kg Electrical data Power consumption 1 2 VA Power loss 0 7 W Designed lifetime Max service life under operating conditions 10 years after date of production Logistics Transport Protect the unit from external forces blows shocks vibrati...

Отзывы: