
BCU 480 · Edition 03.16l
30
Parameters
Description
Parameter
Value range
Factory
default setting
Adjustable*
High temperature operation**
2; 3
Manual mode limited to 5 minutes
0; 1
1
UVS check (1 x in 24 hours)
0; 1
0
Low fire over-run time**
0; 5; 15; 25 s
0 s
* Adjustable using BCSoft software and a PC opto-adapter
** Please quote in your order.
0 = Function inactive,
1 = Function active.
On parameterization, ensure that the program se-
quence started matches the application. This param-
eter may be set in this way only if the burner can restart
as intended in all operating phases.
4 .1 Scanning the parameters
During operation, the 7-segment display shows the pro-
gram status, see page 27 (Program status and fault
messages).
The flame signal and all following parameters of the
BCU can be scanned one after the other by repeatedly
pressing the Reset/Information button (for 2 s).
In the event of a fault, the BCU halts the program run,
the display blinks and it then displays the cause of the
fault in coded form.