background image

GB-7

D

GB

F

NL

I

E

Standard socket set

1

3

2

L1

N

N

NO

NO

1

2

COM

L1

33333333

Order No.: 74915388

Standard coupler plug

Order No.: 74920412

Pilot lamp set, red or blue

Pilot lamp, red: 

110/120 V AC, I = 1.2 mA, Order No.: 74920430; 

220/250 V AC, I = 0.6 mA, Order No.: 74920429. 
Pilot lamp, blue: 

110/120 V AC, I = 1.2 mA, Order No.: 74916121; 

220/250 V AC, I = 0.6 mA, Order No.: 74916122.

2

3

1

4

NC

1

COM

3

NO

NO 2

N

NO

2

NC

1

COM

3

L1

N

NC

1

COM

3

NO

NC

2

N

NO

2

NC

1

COM

3

L1

N

LED set, red/green

24 V DC, I = 16 mA; 24 V AC, I = 8 mA, 
Order No.: 74921089; 
230 V AC, I = 0.6 mA, Order No.: 74923275.

2

3

1

4

NC

1

COM

3

NO

2

N

NO

2

1 NC

3 COM

+

Technical data

Ambient conditions

Maximum medium, ambient and transport tem-
peratures:
DG..H, DG..N: -15 to +60°C,
DG..I: -20 to +80°C.
Storage temperature: -20 to +40°C.
Long-term use in the upper ambient temperature 
range accelerates the ageing of the elastomer ma-
terials and reduces the service life (please contact 
manufacturer).
Enclosure: IP 54 or IP 65. Safety class: 1.

This unit is not suitable for cleaning with a high-

pressure cleaner and/or cleaning products.

Mechanical data

Gas type: natural gas, town gas, LPG (gaseous), 
flue gas, biogas (max. 0.1 %-by-vol. H

2

S) and air.

Max. inlet pressure p

max.

 = withstand pressure, 

see page 5 (Adjustment). 
Max. test pressure for testing the entire system: 
temporarily (< 15 minutes) 2 bar.
Diaphragm pressure switch, silicone-free.
Diaphragm: NBR.
Housing: glass fibre reinforced PBT plastic with 
low gas release.
Lower housing section: AlSi 12.
Max. tightening torque, see Technical Information 
DG (D, GB, F) – www.docuthek.com.
Weight: 270 to 320 g depending on equipment.

Electrical data

Switching capacity:

I (cos φ = 1) I (cos φ = 0.6)

DG

24 – 250 V AC 0.05 – 5 A

0.05 – 1 A

DG..G 5 – 250 V AC 0.01 – 5 A

0.01 – 1 A

5 – 48 V DC

0.01 – 1 A

Conductor diameter: 0.5 to 1.8 mm 
(AWG 24 to AWG 13).
Line entrance: M16 x 1.5, clamping range: diam-
eters of 4 to 10 mm. Type of connection: screw 
terminals. 

Содержание Krom Schroder DG H Series

Страница 1: ...tes possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 11 17 The following chapters have been changed Adjustment Technical da...

Страница 2: ... Installation CAUTION Please observe the following to ensure that the DG is not damaged during installation and operation Continuous operation with gases containing more than 0 1 by vol H2S or ozone concentrations exceeding 200 µg m accelerate the ageing of elastomer materials and reduce the service life Dropping the device can cause permanent dam age In this event replace the entire device and as...

Страница 3: ...et at port 3 4 On IP 65 units the filter pad is fitted as standard see type label 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply 3 Ensure that the pipeline is clean 4 Purge the pipe Installing DG H DG N Positive pressure measurement at port 1 5 Seal port 2 1 2 Rp 1 4 1 2 0 Positive pressure measurement at port 2 5 Seal port 1 1 Rp 1 2 pmax Rp 1 4 2 Rp 1 4 0 Nega...

Страница 4: ...maged during opera tion note the switching capacity see page 7 Technical data In the case of low switching capacities such as 24 V 8 mA for example we recommend using an RC module 22 Ω 1 μF in air containing silicone or oil NO C 1 µF R 22 2 NC 1 COM 3 1 Disconnect the system from the electrical power supply M16 x 1 5 ø 4 10 mm 3 4 2 5 6 7 Contacts 3 and 2 close when subject to increas ing pressure...

Страница 5: ...essure and pos sible reset Mean switching differential at min and max set ting Deviation from the switching point during testing pursuant to EN 1854 Gas pressure switches 15 Air pressure switches Deviation DG H N I 15 DG 1 5I 15 or 0 4 mbar DG 12I 15 or 0 5 mbar DG 18I 15 or 0 5 mbar If the DG does not trip at the desired switch ing point correct the adjusting range using the hand wheel Relieve th...

Страница 6: ...tion of condensation the cover with pressure equalization element can be used The diaphragm in the screw connector is designed to ventilate the cover without allowing water to enter Order No 74923391 Restrictor orifice In the case of high pressure fluctuations we recom mend using a restrictor orifice contains non ferrous metals R Rp Hole diameter 0 2 mm Order No 75456321 hole diameter 0 3 mm Order...

Страница 7: ...of the elastomer ma terials and reduces the service life please contact manufacturer Enclosure IP 54 or IP 65 Safety class 1 This unit is not suitable for cleaning with a high pressure cleaner and or cleaning products Mechanical data Gas type natural gas town gas LPG gaseous flue gas biogas max 0 1 by vol H2S and air Max inlet pressure pmax withstand pressure see page 5 Adjustment Max test pressur...

Страница 8: ...ithout delay Check that the delivery is complete see page 2 Part designations Storage Storage temperature see page 7 Technical data Storage is subject to the ambient conditions de scribed Storage time 6 months before using for the first time If stored for longer than this the overall service life will be reduced by the corresponding amount of extra storage time Packaging The packaging material is ...

Отзывы: