TROUBLESHOOTING
Alarms
The Economizer module provides alarm messages that
display on the 2-line LCD.
NOTE:
Upon power up, the module waits 60 minutes
before checking for alarms. This allows time for
all the configured devices (e.g. sensors, actuator)
to become operational. The exception is the MA
sensor which will alarm immediately.
If one or more alarms are present and there has been no
keypad activity for at least 5 minutes, the Alarms menu
displays and cycles through the active alarms.
You can also navigate to the Alarms menu at any time.
Clearing Alarms
Once the alarm has been identified and the cause has
been removed (e.g. replaced faulty sensor), the alarm can
be cleared from the display.
To clear an alarm, perform the following:
1.
Navigate to the desired alarm.
2.
Press the
button.
3.
ERASE? displays.
4.
Press the
button.
5.
ALARM ERASED displays.
6.
Press the
button (MenuUp/Exit) to complete
the action and return to the previous menu.
NOTE:
If an the alarm still exists after you clear it, it re-
displays within 5 seconds.