background image

E529 Product Guide 

 

Rev 2.0 3/20/2017

 

7

 

 

 

Installation  

CAUTION! 

 

The E529.4G is intended for indoor use only. 

 

The E529.4G installer must be a trained, experienced service 

technician. 

 

All wiring must comply with local codes and ordinances. 

 

Failure to follow the instructions provided with the product could 

damage the product or cause a hazardous condition. 

Placement 

Since the E529.4G has the sensor to measure room temperature, it should  

be installed in a location that represents the desired room temperature. In 

addition, select a location that minimizes exposure to conditions that interfere 

with room temperature measurement, such as away from external doors or 

windows and areas in direct sunlight. 
RF is critical to the E529.4G’s operation, so placement of the device and 

careful consideration of possible sources of radio interference are important. 

For instance, the unit should not be placed close to floor or ceiling or near pipe 

or other metallic items. 

                                  

 

Mounting Instructions 

1.  Separate the E529.4G body and the mounting plate by pulling the bottom 

of the mounting plate away from the E529.4G body and then pull the 

mounting plate down. NOTE: If the back-mounting plate is rotated more 

than 2 or 3 degrees, the plastic tabs at the top of the plate may fracture 

or break off. 

2.  Attach the mounting plate to the wall or electrical box with the arrow 

embossed on the mounting plate pointing upward. The E529.4G is 

provided with four 6-32 ¾” sheet metal screws for mounting the plate to 

an existing 4” × 4” electrical box. If attaching the mounting plate to 

sheetrock or a similar wall surface, install four 6-8 × ¾ anchors. The four 

holes on the mounting plate can be used to mark the location for the 

anchors. 

3.  Install the four AA alkaline batteries (NOTE: Use alkaline batteries only) 

provided into the battery compartment located on the rear of the 

E529.4G. Depress the battery clamp latch at the top of the battery 

compartment and then swing open the battery clamp. Insert the 4 AA 

alkaline batteries, matching the “+” terminals on the batteries to the “+” 

symbols in the battery compartment. Close the battery clamp and verify 

the latch is securely fastened. 

4.  Verify that the E529.4G display is now showing information. At power ON 

(ie inserting the 4 AA batteries), confirm all segments and characters are 

displayed on the E529 LCD display. If the display is blank, verify that the 

Содержание INNCOM E529

Страница 1: ...Page 1 Overview and General Concept Page 2 Application Page 3 Features Page 4 LCD Item Descriptions Page 5 Back and Bottom Features Page 6 Wireless Communication Page 6 Installation Page 7 Placement Page 7 Mounting Instructions Page 7 Technical Specifications Page 8 FCC Statement Page 8 Document Revision History Page 9 ...

Страница 2: ...ol the room HVAC unit It can only measure temperature an optionally humidity and report this to its HVAC controller partner The E529 4G has no IR Eye or S5 Bus installed and only communicates with other devices via RF The HVAC partner in the room must be equipped with a Deep Mesh Layer X radio or S5 Bus connected to a radio equipped device such as a PC502 4G Appendix 4 shows typical installations ...

Страница 3: ...equirements to central servers It comes standard with five relays and can be equipped with a radio frequency RF transceiver and Passive Infrared PIR motion detector The e529 interfaces with all common HVAC unit voltage configurations 24 volt to 277 volt The e529 can be installed in a wireless INNCOM guestroom control system which makes installation feasible and affordable in either new constructio...

Страница 4: ...gain sets medium MED and another press sets high HI The fan speed cycle begins again with the next push 7 DISPLAY Cycles the LCD between the Set selected temperature and the measured Room temperature Outdoor temperature may also be displayed if the system is networked to a server or the Web broadcasting readings from an outside sensor 8 ecoMODE button Optional Feature Pressing this button allows t...

Страница 5: ...nline and connected to the INNCOM server NOTE As of 6 2016 this feature DOES NOT currently work if using a CBL32 Room Gateway such as an E528 4G or PC502 4G You will NOT get a Dot on the E529 display You must use the E529 rUn2 WAN Test to check that the room is connected to the network 7 HVAC Control Mode AUTO displayed when HVAC control is in AUTO Mode 8 Fan Speed LO MED or HI Displayed when FAN ...

Страница 6: ... room to be used for energy management 4 ES 1 Key Header Used to copy new software from the ES 1 Key to the E529 Wireless Communication 2 4HHz Wireless RF Table 1 E529 RF Performance 0dB 20dB RF Data Rate 250kbps 250kbps Antenna Type SMT SMT Indoor Range 70ft 100ft Outdoor RF line of site range 540ft 1000ft Transmit Power 1mW 10mW Receive Sensitivity 94 6dBm 94 6dBm Frequency Band 2 4GHz 2 4GHz En...

Страница 7: ... from the E529 4G body and then pull the mounting plate down NOTE If the back mounting plate is rotated more than 2 or 3 degrees the plastic tabs at the top of the plate may fracture or break off 2 Attach the mounting plate to the wall or electrical box with the arrow embossed on the mounting plate pointing upward The E529 4G is provided with four 6 32 sheet metal screws for mounting the plate to ...

Страница 8: ...the E529 4G housing Technical Specifications Table 7 Technical Specifications FCC Statement This equipment has been tested and found to comply with the limits for Class B digital device pursuant of part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequen...

Страница 9: ...tions or warranties with respect to this document In no event shall Honeywell be liable for technical or editorial omissions or mistakes in this document nor shall it be liable for any damages direct or incidental arising out of or related to the use of this document No part of this document may be reproduced in any form or by any means without prior written permission from Honeywell Copyright 201...

Отзывы: