Model RPS-1000 Installation Manual
151153
2-3
* Regulated/special application when used for releasing.
Table 2-1: Terminal Strip Description and Electrical Ratings
Terminal # and Label
Description
Rating
Voltage
Current
1
L
AC input (hot)
120/240 VAC,
50/60 Hz
2.7 A
1.4 A
2
G
Earth ground
N/A
N/A
3
N
AC input (neutral)
120/240 VAC,
50/60 Hz
2.7 A
1.4 A
4
X
I/O 6*
Flexput™ Circuit
24 VDC
3.0 A Notification Circuits
5
O
100 mA Initiation Circuits
6
X
I/O 5*
Flexput™ Circuit
24 VDC
3.0 A Notification Circuits
7
O
100 mA Initiation Circuits
8
X
I/O 4*
Flexput™ Circuit
24 VDC
3.0 A Notification Circuits
9
O
100 mA
Initiation Circuits
10
X
I/O 3*
Flexput™ Circuit
24 VDC
3.0 A Notification Circuits
11
O
100 mA Initiation Circuits
12
X
I/O 2*
Flexput™ Circuit
24 VDC
3.0 A Notification Circuits
13
O
100 mA Initiation Circuits
14
X
I/O 1*
Flexput™ Circuit
24 VDC
3.0 A Notification Circuits
15
O
100 mA Initiation Circuits
16
B
SBUS OUT
SBUS communication
5 VDC
100 mA
17
A
18
+
SBUS power
24 VDC
1.0 A
19
-
20
B
SBUS IN
Used for Class A installations
21
A
22
+
23
-
24
N.C.
RELAY 2
General Purpose Relay 2
24 VDC
2.5 A
25
C
26
N.O.
27
N.C.
RELAY 1
General Purpose Relay 1
24 VDC
2.5 A
28
C
29
N.O.
30
B
SBUS IN/
OUT
RPS-1000 communication with
main panel or to controlling
RPS-1000 if daisy-chained
5 VDC
100 mA
31
A
32
+
MAIN
RPS-1000 SBUS power (from
IFP-1000 or IFP-1000ECS)
24 VDC
10 mA
33
-