![Honeywell IFP-2100 Скачать руководство пользователя страница 116](http://html.mh-extra.com/html/honeywell/ifp-2100/ifp-2100_installation-and-operation-manual_148864116.webp)
LS10143-001SK-E
IDP, SK, SD and SWIFT™ SLC Device Installation
7-8
in Figure 7-4.
Figure 7-4 IDP or SK SLC Device Addressing Using Rotary Dials
7.8
Wiring SD Detectors
The information in this section applies to SD Detectors.See Table 7-3 for P/N’s.
To Wire SD Detectors
1.
Wire device bases as shown in Figure 7-5.
2.
Set the address for each device as described in Section 7.9.
Figure 7-5 Heat or Smoke Detector Connection to the FACP
7.9
Addressing SD Devices
This section explains how to address SD detectors and modules. See Table 7-3 for a list of SD devices.
An access code with the option to set SLC Device Address enabled is required to perform this task.
To address a SD detectors:
Example 2: Device Set to 105.
All dials labeled for ONES
or TENS position.
Содержание IFP-2100
Страница 95: ...LS10143 001SK E Networking 5 8 Figure 5 9 Fiber Optic Wiring Single Mode Example Class A wiring ...
Страница 127: ...LS10143 001SK E Programming Overview 8 8 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns ...
Страница 256: ...Cut Along the Dotted Line ...
Страница 258: ...Cut Along the Dotted Line ...
Страница 260: ...Cut Along the Dotted Line ...
Страница 262: ...Cut Along the Dotted Line ...
Страница 263: ......