21
HWF2-COM Trouble Detection Information
Telco 1 is used for the Fire Panel to output contact ID messages to the HWF2-COM, and Telco 2 is used by the HWF2-COM
to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to report events if there are no
faults in the Communicator.
Fault Condition
Indication to Fire Panel
PowerBoost1 fault
Telco 2 is cut.
AC Loss
Telco 2 is cut.
Power Supply fault
Telco 2 is cut.
Low Battery
Telco 2 is cut.
Loss of ECP (Wiring or Addressing)
Telco 1 and 2 are cut.
Radio not registered
Telco 1 and 2 are cut.
Communicator fault
•
Failure of the communications path when IP only or Cell only is
programmed as a communications path.
Telco 1 and 2 are cut.
•
Failure of both communications paths when IP&Cell is pro-
grammed as a communications path.
Telco 1 and 2 are cut.
•
Failure of one of the communication paths when IP and Cell
are enabled as the communications path.
Telco 2 is cut.
Dialer Capture Module buffer is full.
Hang up. (Panel will retry, giving the buffer a
chance to empty.)
HWF2-COM Specifications
ITEM
SPECIFICATION
Cabinet Dimensions:
Width 12 3/4 inches, Height 14 7/8 inches, Depth 3 inches
Transformer:
N8167 or
N8167-1
Primary – 120VAC, 60Hz, Secondary – 18VAC, 50VA
Battery:
12V, 7Ah sealed lead acid type (not supplied)
Use a Honeywell 712BNP, Yuasa NP7-12 or equivalent.
Battery Charging Current:
maximum 1A
Battery Discharge Current:
standby 210mA, active 290mA
Environment:
Operating temperature: 0ºC to +49ºC
Storage temperature: –40º to +70ºC
Altitude: to 10,000 ft. operating, to 40,000 ft. storage
Supervision:
The Radio (communicator), battery, and AC power, conditions are monitored by the
cabinet indicator LEDs:
RADIO TROUBLE lights when any of these conditions exist.
•
Both IP and Cell communication paths are lost.
•
Communicator radio is not registered.
•
Old Alarm Time has been exceeded. (Message has not been delivered within the
fixed 10-minute window.)
LOW BATTERY lights when the battery voltage is less than 11.5VDC.
AC LOSS lights when the AC power is less than 90VAC.