8 Periodic Redundancy Tests
8.4 Redundant 8-Channel Analog Output IOPs
R688
HPM High-Performance Process Manager Service
461
December 2020
Honeywell
Step
Action
1
Select the
<SYST STATS>
(SYSTEM STATUS) key on the console and then select the
PROCESS NETWORK STATUS
target on the display for the network that contains the
High-Performance Process Manager (HPM) or Process Manager (PM) of interest. The
UCN Status display is produced on the console screen.
2
Choose the status box containing the HPM of interest and then select the
DETAIL
STATUS
target on the UCN Status display. The HPM Detail Status display is produced
on the screen.
3
Select the
RUN STATES
target on the HPM Detail Status display. The
SWAP
PRIMARY
target along with other targets appear at the bottom of the display.
4
Select the
SWAP PRIMARY
target. This produces the
ENTER
and
CANCEL
targets to
the right of the
SWAP PRIMARY
target.
5
Note the status in the IOP status box on the display for the redundant pair of IOPs that
are of interest. The status box should contain an “
OK/BKP
” label. Choose the IOP
status box of interest. Then, select the
ENTER
target. The “
OK/BKP
” label in the IOP
status box should switch to
“
BKP/OK
,” respectively after approximately 5 seconds,
indicating the IOP redundancy is functional.
The orientation of the redundant IOPs should be returned to their original positions by
selecting the
ENTER
target a second time.
6
Repeat step 5 for any other redundant pairs of IOPs.
8.4 Redundant 8-Channel Analog Output IOPs
Introduction
Redundancy for the 8-channel Analog Output IOPs is biased toward the IOP A to maximize reliability.
Hardware bias is preferred because IOP B (the physical secondary) is connected to the Analog Output
FTA through a switching module on the FTA, while IOP A (the physical primary) is connected directly
to the FTA circuitry that interfaces the FTA’s field wiring output terminals. Use of the procedure in this
subsection tests a redundant pair of Analog Output IOPs for proper operation.
Hardware identification
Locate the following components.
Analog Output IOP A
Analog Output IOP B
The redundant Analog Output FTA
An Analog Output Standby Manual device
Devices that are being controlled by the analog output of the FTA
Control algorithms that are driving the analog outputs
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...