background image

HPL624

Power Supply/Battery Charger

PN 52263:C 1/10/08 ECN 08-029

Honeywell
12 Clintonville Road 
Northford, CT 06472-1610
http://www.honeywellpower.com

Product Installation Document

1 Introduction

The 

HPL624

 power supply/battery charger converts a low voltage AC input into an output of 6 VDC or 12 VDC @ 1.2 

amps of continuous supply current or 24 VDC @ 750 mA of continuous supply current.  This general purpose linear 
power supply can provide additional power for a variety of applications such as access control, security and CCTV system 
accessories.

2 Specifications

Switch selectable for 6 VDC, 12 VDC or 24 VDC output.

1.2 amps of continuous supply current at 6 VDC or 12 VDC.*

750 mA of continuous supply current at 24 VDC.*

Output that is filtered and electronically regulated.

Built-in charger for sealed lead acid or gel type batteries.

Maximum charge current of 500 mA.
If a battery charger is used, subtract max charge current of 
500 mA from total to determine allowable load.

Automatic switchover to stand-by battery upon AC fail.

PTC battery protection.

Thermal and short circuit protection with auto reset.

LED indicators for AC input and DC output.

Compact design (board dimension 3"L x 2.5"W x 1.5"H).

Battery leads and foam mounting tape included.

*Specified at 25ºC ambient.

3 Voltage Output  and Transformer Selection 

Output Voltage/Current

Switch

Transformer Requirements

SW1

SW2

  12 VDC @ 1.2 amps continuous supply current

Closed

Closed

16.5VAC / 40 VA

(model HTP1640)

24 VDC @ 750 mA continuous supply current

Open

Closed

24VAC / 40 VA

(model HTP2440)

6 VDC @ 1.2 amps continuous supply current

Closed

 Open

12VAC / 20 VA

(model HTP1220)

DC +

DC –

BAT +

AC

AC

HP

L6

24

.w

mf

TB1

DC LED

AC LED

Отзывы: