HPTV2416(CB) and HPTV2416-1(CB) Installation Instructions P/N 52406:B 08/17/2005
•
Power ON/OFF switch on each Distribution Board.
•
AC line cord included.
•
Unit maintains camera synchronization.
•
Vented enclosure with hinged door and five convenient knockouts.
•
Design for quick installation.
•
Maximum temperature range: 32°F to 120°F (0°F to 49°C); indoor use only.
•
Cabinet dimensions: 11.5 " W x 4.875 " D x 10 " H (29.21 cm W x 12.38 cm D x 25.4 cm H).
3 Installation Instructions
1.
Unpack product. Do not discard packing materials until installation and checkout are successfully completed.
2.
Pre-drill holes where enclosure is to be mounted. Choose a vertical surface, strong enough to support the full weight
of the assembly, located in an area without excessive moisture. This unit is for indoor installation only.
3.
Secure enclosure to the desired location, using appropriately sized fasteners that can support the full weight of the
assembly.
4.
Disconnect power to the branch circuit to which the product will be connected.
5.
On each Distribution Board, Slide SW1 switch to OFF position
6.
Connect incoming AC power (115 V, 60 Hz):
– Hot (black) to terminal marked “L”.
– Neutral (White) to terminal marked “N”.
– Ground to terminal marked “G”.
7.
Use the knockout in bottom of cabinet for 115 VAC wiring on HPTV2416 and HPTV2416CB.
Use the Right slide knockout for 115 VAC wiring on HPTV2416-1 and HPTV2416-1CB.
Route the 115 VAC wiring at least 3/8" (0.953 cm) from 24 VAC (low voltage) wiring.
8.
Keep a ¼" (0.635 cm) separation between power limited wiring (output circuits on HPTV2416CB and
HPTV2416-1CB) and non-power limited wiring. Use separate knockouts for power limited wiring.
9.
Connect CCTV cameras (or other external loads) to appropriate terminals. Connect circuit #1 to terminals marked
“1+” and “–”. Connect circuit #2 to terminal is marked “2+” and “–”. Continue to connect the remaining circuits
carefully observing polarity. Terminals marked with “–” are of the same polarity.
10. Power the branch circuit and slide SW1 on each Distribution Board to the ON position. All eighteen green LEDs
should illuminate.
11. Upon completion of wiring, secure cabinet door with screws supplied, to prevent access by unauthorized personnel.
Terminal Block Fuse
Secondary Fuse
Individual Outputs
HPTV2416
3 A (250 V)
5 A
3 A Fuse
HPTV2416CB
3 A (250 V)
N.A.
PTC*
HPTV2416-1
6 A (125 V)
10 A
5 A Fuse
HPTV2416-1CB
6 A (125 V)
N.A.
PTC*
*PTC hold current rating: 2.0 A at 50°C