background image

HLS PS25 & HLS PS50 User Manual 

 

MN-DT-1305I_B                                                          

                                          6 

 

 

 

1.5 Back Box HLS PS Series fixing 

 

When a suitable location has been found for installing the HLS PS Series, proceed as follows:  

1.

 Hold th e back box a ssembly in the required p osition against the wall  and mark the p osition of th e 

fixing holes, while ensuring the panel is level. 
The drawing below shows the position of the fixing holes at the back box. 

Do NOT use the back box as a guide when drilling!

 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.

 Drill and plug the wall.  

3.

 Prepare apertures required for cable access.  

4.

 Screw the  ba ck box to  the  wall  using the  fixing  hole s 

and appropriate-sized screws.

 

 

 

 

 

 

Содержание HLSPS25-XPH

Страница 1: ...Power Supply Unit HLS PS Series HLSPS25 XPH and HLSPS50 XPH User manual Information in this document is subject to change without notice 8 APRIL 2010 HW_MN DT 1305I_B ...

Страница 2: ...HLS PS25 HLS PS50 User Manual MN DT 1305I_B 2 ...

Страница 3: ... HLS PS for damage 4 1 2 Pre installation check list 5 1 3 Transient protection 5 1 4 Cleaning 5 1 5 Back Box HLS PS fixing 6 2 Functions and indicators 7 2 1 HLS PS25 and HLS PS50 characteristics 8 2 2 Battery 9 2 3 Fault relay 9 2 4 Control Unit connections 10 2 5 Indicator leds 12 3 Specification 14 ...

Страница 4: ...ty of a ny sup plied order items follow the procedure bellow 1 If after removing the HLS PS Series a visual inspection reveals that it has bee n damaged you MUST NOT continue with the installation but conta ct you supplier for advice on what to do next Similarly if the prod uct is found to be faulty during installation contact your supplier immediately 2 To aid you r supplier you are requested to ...

Страница 5: ...operate erratically or c an be damaged i f sub jected to li ghtning induced t ransients This equipmen t contains trans ient p rotection devic es Al though no system is immune from lightning transients and interference for thes e devices to func tion co rrectly and to reduc e susceptibility this equipment must be earthed correctly The use of overhead or outside aerial wiring is not recommended due ...

Страница 6: ...y in the required p osition against the wall and mark the p osition of th e fixing holes while ensuring the panel is level The drawing below shows the position of the fixing holes at the back box Do NOT use the back box as a guide when drilling 2 Drill and plug the wall 3 Prepare apertures required for cable access 4 Screw the ba ck box to the wall using the fixing hole s and appropriate sized scr...

Страница 7: ...tions and indicators FRONT PANEL 1 2 FUS BAT FAULT LOW BAT NO BAT BAT TEST BAT CH BAT DIS IN ALARM 321087 CPU MAX LEGEND ON FAULT MAIN SUPPLY FAULT BATTERY FAULT BATTERY CHARGER FAULT OUTPUT 1 FAULT OUTPUT 2 FAULT EARTH FAULT OVERLOAD SYSTEM FAULT INTERNAL LEDS ...

Страница 8: ...ndard module control which supervises the entire power supply HLS PS25 and HLS PS50 power supplie s provide 2 5 Amp and 5 Amp respectively a nd 300mA to 600mA of th em are dedic ated to charg e batteries Th ese po wer su pplies are able to supply either up to 1 1 0 and 2 20 Amp current at each PSO1 a nd PSO2 out puts This is the default set up DIP SW1 ON up position However power supplies can also...

Страница 9: ...ote control unit Any fault has a delay of 30 seconds from the fault signal to fault relay confirmation ex cept when there is a ma ins AC loss which will be indicated afte r an 8 minut e delay to avoid faults from intermittent power cuts In stand by the fault relay is energized indicating its normal operation In case of any fault the relay deactivates after the confirmation time Fault relay operati...

Страница 10: ...m input to disable momentarily the battery charger and be able to supply 300 600mA from ba ttery loa d to the ou tputs Fo r th is i t is necessa ry to l ink both IN ALARM terminals by means of a jumper or short circuit When this input is activated the control unit will have an extra current of battery load 0 3 A or 0 6 A depending on the DIP SW2 for outputs Thus if the power supply is in Overload ...

Страница 11: ...se batteries fail a Battery fault will be report ed The HLS PS Series will supervise a utomatically t he battery ea ch 3 hours If the battery load is in normal condition the fault signal will disappear EN54 2 Section 8 2 4 requi res tha t any Earth faul t whi ch m ay affect an obligatory functi on should be indicated independently The cable size should be calculated according to th e maximum l eng...

Страница 12: ...he fault relay signal and the FAULT led do not activate until the power supply fault remains for more than 8 minutes BATTERY FAULT Led Battery is not detected by the Control Unit or the battery voltage is below 22 4 Vdc i e the 50 of its capacity The FAULT Led and the fault relay signal are also activated In case the internal le d LOW BAT is flashi ng it mea ns that the battery voltage is close to...

Страница 13: ...l not be earth fault supervision Earth fault solution Ma ke su re t hat there are n o links bet ween Earth and Output 1 and 2 y OVERLOAD Led Indicates that the equipment exceeds the maximum current 5 A A momentary peak voltage may be provide d by disa bling the battery load current in ca se of al arm by usin g the IN ALARM connection which switches the battery current of 300 or 600mA to the output...

Страница 14: ... th terminals with a jumpe r or short circuit this input allo ws the battery charger momentary di sablement in order to provide extra 300 600 mA to the outputs Battery load current 300 mA 7 Amp hour 600 mA 17 Amp hour 80 of the Battery Capacity is charged in less than 24 h and the 100 in less than 48 h Fault relay C NC NO contacts 1 Amp 24Vdc maximum Energized in normal state State Indicators 10 e...

Страница 15: ...HLS PS25 HLS PS50 User Manual MN DT 1305I_B 15 ...

Страница 16: ...ty es Honeywell Life Safety Charles Avenue Burgess Hill RH15 9UF West Sussex Tel 44 0 1444 230 300 England Avenue De L Expansion 16 D B 4432 Alleur Tel 32 0 4 247 03 00 Belgium www honeywelllifesafety com Berliner Straße 91 D 40880 Ratingen Tel 49 2102 700 69 0 Deutschland Via Grandi 22 20097 S Donato Milanese MI Tel 39 02 518971 Italia ...

Отзывы: