Honeywell HEAT PUMP THERMOSTAT T8411R Скачать руководство пользователя страница 3

T8411R ELECTRONIC HEAT PUMP THERMOSTAT

3

68-0185—2

INSTALLATION

When Installing this Product…

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous condi-
tion.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 
application.

3.

Installer must be a trained, experienced service technician.

4.

After installation is complete, check out product opera-
tion as provided in these instructions.

CAUTION

Damage to Heating/Cooling System Possible.

Be careful when handling wires during 
installation.

Disconnect power at furnace or main breaker/fuse 

box.

MERCURY NOTICE

If this control is replacing a control that contains 

mercury in a sealed tube, do not place your old control 
in the trash.

Contact your local waste management authority for 
instructions regarding recycling and the proper 

disposal of an old control containing mercury in a 
sealed tube.

If you have questions, call Honeywell Inc. at 
1-800-468-1502.

Location

Install the thermostat about 5 ft (1.5m) above the floor in an 
area with good air circulation at average room temperature. 

See Fig. 2. Do not install the thermostat where it can be 

affected by:
— drafts or dead spots behind doors and in corners.

— hot or cold air from ducts.

— radiant heat from the sun or appliances.
— concealed pipes and chimneys.

— unheated (uncooled) areas such as an outside wall behind 

the thermostat.

This thermostat is a precision instrument and was adjusted at the 

factory. Handle it carefully.

Mounting Wallplate to Wall

IMPORTANT

Level for appearance only. The thermostat functions 

normally even when not mounted level.

Mount wallplate, T8411R and the screws provided (see Fig. 3) 

as follows: 

1.

Position the wallplate at the desired location on the wall.

2.

Use a pencil to mark the mounting holes.

3.

Remove the wallplate from the wall and drill two 3/16 in. 
holes in the wall (if drywall) and two 7/32 in. holes for 

firmer material such as plaster or wood. Gently tap the 

anchors (provided) into the holes until flush with the wall.

4.

Position the wallplate over the holes.

5.

Pull the thermostat wire through the entrance hole on 

the wallplate.

Fig. 2. Typical location of thermostat.

5 FEET

[1.5 METERS]

YES

NO

NO

NO

M11338

Содержание HEAT PUMP THERMOSTAT T8411R

Страница 1: ...in a variety of locations Keys are located by the display for easy access Fan and system switches are located on the lower edge to eliminate accidental setting changes Easy installation setup and self test saves installer time and increases their productivity Manual changeover from heat to cool eliminates unexpected system operation F or C temperature display for added model flexibility Selectable...

Страница 2: ...1R TRADELINE model includes a thermostat wallplate for wiring and mounting thermostat and owner s guide Power T8411R 24 Vac nominal 18 to 30 Vac 50 60 Hz Electrical Ratings First Stage Heating 0 02 to 1 5A run 7 5A inrush Second Stage Heating 0 02 to 1 5A run 3 5A inrush Cooling 0 02 to 1 5A run 7 5A inrush Fan 0 02 to 0 5A run 2 5A inrush Emergency Heat Output E 0 02 to 1 5A run 3 5A inrush Heati...

Страница 3: ...on Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average room temperature See Fig 2 Do not install the thermostat where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from the sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the therm...

Страница 4: ...ate and con nect the system wires See Fig 4 2 Securely tighten each terminal screw 3 Push the excess wire back into the hole 4 Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat Mounting Thermostat to Wallplate 1 Engage the tabs at the top of the thermostat and wall plate 2 Swing down the thermostat and press the lower edge of the thermostat onto the wallpla...

Страница 5: ... TERMINALS SYSTEM SWITCH HEAT OFF COOL R W2 L B O Y EM HT W1 E AUXILARY HEAT RELAY CHANGEOVER VALVE HEAT CHANGEOVER VALVE COOL COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR HEAT FAN RELAY RELAY EMERGENCY HEAT RELAY G C THERMOSTAT LOGIC THERMISTOR SENSOR POWER SUPPLY ON AUTO STAGE 2 RELAY STAGE 1 RELAY FAN SWITCH M11333A 3 3 M18577 SYSTEM Cool Off Heat Em Ht Auto On FAN DASHED LINES INDICATE TABS ON BA...

Страница 6: ...heating load Set Temperature Setpoint NOTE Temperature setpoint range is 40 to 99 F 4 to 39 C The temperature setpoint and the room temperature are shown separately on the display The indicator points to Set when the temperature setpoint is displayed and to Room when the room temperature is displayed To set temperature setpoint 1 Select Heat or Cool by sliding the SYSTEM switch in the lower right ...

Страница 7: ... displayed A typical example is shown but CC varies by model This informa tion is for factory use only 10 Press to save all changes exit installer setup mode and return to normal operation NOTE After exiting installer setup mode change the set point to the desired room temperature OPERATION The T8411R Thermostat provides two stage heat and one stage cool temperature control with proportional plus ...

Страница 8: ...ting and cooling Table 1 Sequence of Operations a The O terminal is powered continuously in cooling the B terminal is powered continuously in heating and the L terminal is powered continuously in emergency heat as a function of the system switch position even without a call for heat or cool CHECKOUT Heating 1 Slide the SYSTEM switch to Heat and the FAN switch to Auto 2 Press and hold the s key to ...

Страница 9: ... THERMOSTAT PARTIAL DISPLAY INOPERATIVE THERMOSTAT SEE THE SETTINGS AND ADJUSTMENTS SECTION FOR INSTRUCTIONS ON INSTALLER SETUP MODE STILL IN INSTALLER SETUP MODE RECONFIGURE THE DISPLAY SEE SETTINGS AND ADJUSTMENTS SECTION TEMPERATURE DISPLAY IS INCORRECT THERMOSTAT IS CONFIGURED FOR F OR C DISPLAY CHECK THAT C TERMINAL IS CONNECTED TO THE SYSTEM TRANSFORMER CHECK POWER TO HEATING AND COOLING EQU...

Страница 10: ...68 0185 2 10 ...

Страница 11: ...11 68 0185 2 ...

Страница 12: ...ilding Control Home and Building Control Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Отзывы: