5) Additional Installation Information

5.1 Binding / Rebinding Procedure

The binding operation described below is required if:

•  Any of the system components (room thermostat or receiver box) are replaced.
•  The receiver box has incorrect or no binding data stored (e.g. when pre-bound system pack components 

have been mismatched).

NOTE:

 During the binding procedure keep approximately 1m distance between the room thermostat and 

the receiver box.

To bind/rebind:

1.

  Press and hold the receiver box push button for 15 seconds to reset any previously stored data. After 

15 seconds the red LED will change to flashing 0.1sec on/0.9sec off. 

 

NOTE:

 After 5 seconds the red LED will start to flash 0.5sec on/0.5sec off, but continue to hold the 

button).

2.

  Release the push button.

3. 

Press and hold the receiver box push button for 5 seconds to enter the binding mode. The Red LED will 

start flashing at 0.5sec on/0.5sec off to confirm the binding mode has been entered.

4. 

Move the room thermostat slider to the 

OFF

 position and press the     and   buttons together along 

with the   button. The unit will display InSt and ‘CONTROL BINDING’.

5.

  Press the green   button to send the binding signal out to the receiver box. The red LED is switched off 

to confirm successful binding operation. If the red LED still flashes push the button again until binding 

is successful.

6. 

Now go to Section 

2) Installing the CM900 Wireless System

 to setup the system.

5.2 Multi-Zone System

Multiple room thermostats and receiver box sets can also be used to control multi-zone systems and the 

CM927/921  room  thermostat  is  compatible  with  a  variety  of  other  Honeywell  products  including  HR80 

radiator controllers and HCE80 underfloor heating controllers. If you intend to use it in this way additional 

installation and user instructions can be obtain by contacting the address at the end of this guide. 

NOTE:

 Some of the labels supplied with the pack are for use in multizone applications.

Содержание HC60NG

Страница 1: ... INCLUDE THIS PAGE IN THE PRINTING Folding Sequence Finished Size 42011076 003 CM900 RF INSTALLATION GUIDE UK English 0024168 08 06 MF BM A3 A4 A5 A6 A7 OTHER SIZE WHEN PRINTED x booklet SIZE WHEN FOLDED X CARTRIDGE x MATT ART WEIGHT 70g 80g 100g 115g 150g OTHER x SINGLE SIDE DOUBLE SIDE x ONE COLOUR TWO COLOUR THREE COLOUR FULL COLOUR X black R2 08 06 Back Front 105mm 148mm 12 page A5 saddle stit...

Страница 2: ...d easy but if products from individual system packs are separated or mixed with other pre configured system packs during installations please refer to section 5 1 Binding Rebinding Procedure to bind the desired units together and allow them to communicate with each other Table of Contents Section Page 1 Installation Information 2 2 Installing the CM900 Wireless System 3 2 1 Installing the Receiver...

Страница 3: ...ength of the RF signal reaching the receiver box depends on the number of walls and ceilings separating it from the room thermostat as well as the building construction the diagram below illustrates an example of typical signal strength reduction Walls and ceilings reinforced with steel or plasterboard walls lined with metal foil reduce the RF signal significantly more Once a position is selected ...

Страница 4: ...performance install in an open space Leave at least 30cm distance from any metal objects including wall boxes and boiler housing Do not mount on metal wall boxes NOTE The receiver box contains no user serviceable parts It should be opened and installed by qualified installer only WARNING Electrostatic sensitive device Do not touch the circuit board NOTE All wiring must be in accordance with IEE re...

Страница 5: ...een button to confirm 2 2 2 RF Communication Check Test Mode To check the RF communication hold the room thermostat about 2 3 metres from the installed receiver box Move the slider on the room thermostat to the OFF position then press the and buttons together with the button for 3 seconds The unit will display TEST TRANSMIT and it will send test signals to the receiver box flashing the green LED o...

Страница 6: ...lider switch to the MAN mode 4 Adjust the setpoint up to the maximum 35 C by pressing the button The boiler should come on green LED ON on receiver box after a few seconds and the symbol appears on the room thermostat LCD display 5 Set the slider switch to the OFF mode The boiler will go off green LED OFF on receiver box after a few seconds and the symbol disappears 6 Check the system operation by...

Страница 7: ...d of 1 hour the red LED will illuminate to indicate that no RF messages have been received during the last hour The receiver box will also enter the failsafe mode as selected in Installer Mode see section 4 2 HC60 Receiver Box Fail Safe Mode Setup To allow manual control of the receiver box output manual override is available in fail safe mode When RF communication is restored the receiver box wil...

Страница 8: ...to accept the change 6 Attach appropriate label to the receiver box to indicate the selected fail safe mode IMPORTANT To enable the frost protection when RF communication is lost select the fail safe mode 1 For systems with separate frost protection thermostat or where frost protection is not required select fail safe mode 0 COPY DAY DAY 1 6 CM927 DATE PROG AUTO MAN OFF OFF Move the slider switch ...

Страница 9: ...ter 3 tC category 1 to 1 Temperature Offset If the thermostat is located in a particularly hot cold location for reliable signal transmission reasons then the measured displayed temperature can be adjusted by 3 C This is useful if the homeowner wants the reading to match another appliance temperature display Set parameter 12 tO category 1 to the required offset value Upper Lower Temperature Limit ...

Страница 10: ...rammed To restore the factory profile set to 1 Auto Summer Winter Time Change 3 tC 1 Auto Summer Winter Time Change Enabled 0 Auto Summer Winter Time Change Disabled LCD Backlighting 5 bL 1 Backlighting Enable 0 Backlighting Disabled Upper Temp Limit 6 uL 35 35 C Upper Temp Limit 21 to 34 21 C to 34 C adjustment in 1 C steps Lower Temp Limit 7 LL 5 5 C Lower Temp Limit 5 to 21 6 C to 21 C adjustme...

Страница 11: ...abled 1 Pump exercise enabled System Synchronisation 6 Sn 0 Standard operation of the Room Unit 1 Room unit configured as Synchroniser Loss of Communications Instruction 7 LC 0 Relay Off 1 Relay 20 on 80 off The following Parameters are for the control of other Honeywell Wireless products such as Wireless Underfloor Heating controls and Wireless Radiator controls For more information please contac...

Страница 12: ...ED will start flashing at 0 5sec on 0 5sec off to confirm the binding mode has been entered 4 Move the room thermostat slider to the OFF position and press the and buttons together along with the button The unit will display InSt and CONTROL BINDING 5 Press the green button to send the binding signal out to the receiver box The red LED is switched off to confirm successful binding operation If the...

Страница 13: ... is on and the green one is flashing once every 3 sec on the receiver box Incorrect or incomplete binding procedure Incorrect position of the room thermostat during binding Repeat the binding procedure Repeat the binding procedure keeping approx 1 m distance between the receiver box and the room thermostat The red LED on the receiver box is illuminated Communication loss The receiver box receives ...

Отзывы: