background image

H8908A/B HUMIDISTAT; H8908C/D DEHUMIDISTAT

5

69-1341EF—07

Fig. 15. Wiring H8908 in line with

air pressure switch/sail switch and humidifier.

Fig. 16. Wiring H8908 with steam humidifiers.

Fig. 17. Wiring H8908 with VisionPRO® IAQ on typical 2-stage furnace.

Fig. 18. Wiring H8908 with VisionPRO®

Thermostat for dehumidification.

Fig. 19. Typical wiring diagram for HR150, 

HR200, ER150 and ER200 Ventilator 

or DH90 Dehumidifier applications.

M24730B

L1 

(HOT)

L2

1

1

2

POWER SUPPLY.  PROVIDE DISCONNECT MEANS 

AND OVERLOAD PROTECTION AS REQUIRED.
24V WIRING.

HUMIDIFIER

TRANSFORMER

AIR 

PRESSURE SWITCH/

SAIL SWITCH

H8908

10

OFF

ON

20

30

40

50

60

2

M24731

1

1

1

FOLLOW THE INSTALLATION INSTRUCTIONS 
INCLUDED WITH THE STEAM HUMIDIFIER 
TO WIRE THE SYSTEM FAN.

NOTE: 

HUMIDIFIER

TO 
SYSTEM
FAN 

HUMIDISTAT
TERMINALS

FAN WIRING
TERMINALS

24V WIRING.

H8908

10

OFF

ON

20

30

40

50

60

EQUIPMENT INTERFACE MODULE

M24724B

H8908B

10

OFF

ON

20

30

40

50

60

1
2
3
C
R
RC
RH

1
2
3

24 VAC

H1

U

M2
D1

H

M2
V1

T2

OR

L
NOT USED
OUT1
OUT2
IN1
IN2

DATS1
DATS2

CONV. HP

W1
W2
W3
Y
Y2
G

O/B
AUX
AUX2
Y
Y2
G

TH9421 VISION PRO

THERMOSTAT

24 VOLT

TRANSFORMER

SYSTEM

TRANSFORMER

S688 AIR 

PRESSURE

SWITCH/

SAIL SWITCH

COM N.O. N.C.

C

R

L2

L1

C

R

L2

L1

HE225/HE265

HUMIDIFIER

STAGE 1

HEAT

STAGE 2

HEAT

COMPRESSOR

C7089U1006

FAN

RELAY

HEATING
RELAY OR
VALVE COIL

COOLING
CONTACTOR
COIL

FAN
RELAY
COIL

PROVIDE OVERLOAD PROTECTION 
AND DISCONNECT MEANS AS REQUIRED.

M24725

1

1

VISIONPRO®  THERMOSTAT

Y2
L
A
W2
S1
S2

RC

R

W

Y

G

C

H8908D

10

OFF

ON

20

30

40

50

60

VENTILATOR/DEHUMIDIFIER

M24732

TERMINALS

Fresh Air Ventilation System
Système de ventilation à air frais

H8908D

10

OFF

ON

20

30

40

50

60

Содержание H8908A/B

Страница 1: ...ondition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician CAUTION Personal Injury Hazard Power supply can cause electrical shock Disconnect power supply before beginning installation NOTE The H8908 electrical connections are not shared with the thermostat Fig 1 H89...

Страница 2: ... to the mounting location REMOTE MOUNT INSTALLATION 1 Choose a location in the living area NOTE Select a location clear of drafts or excessive humidity Avoid mounting near doors or win dows or in bathrooms or kitchens See Fig 6 Fig 6 Choose a location in the living area 2 Cut 1 in diameter wire hole in wall 3 Run two fan low voltage wire to the mounting loca tion in the living area IMPORTANT Use r...

Страница 3: ...ket See Fig 8 NOTE Use gasket only when mounting the control to ductwork Leave off when mounting to a wall Fig 8 Seal base bracket 5 Secure the base bracket to the duct or remote loca tion Secure to the duct with four 1 in 25 mm screws provided or to the wall with two 1 in 25 mm screws provided Fig 9 Mount base bracket to duct or remote location M24733 M24722 ...

Страница 4: ...6 Using wire nuts connect the low voltage wire to the leads on the H8908 humidistat See Fig 6 19 for different wiring configurations Fig 10 Wire the humidistat 7 Mount the humidistat by hooking the two hinges at the top of the back cover to the raised edge at the top of the base bracket Press the bottom of the humidistat in to engage the base hinge You will hear a click when the humidistat is secu...

Страница 5: ...THE SYSTEM FAN NOTE HUMIDIFIER TO SYSTEM FAN HUMIDISTAT TERMINALS FAN WIRING TERMINALS 24V WIRING H8908 10 OFF ON 20 30 40 50 60 EQUIPMENT INTERFACE MODULE M24724B H8908B 10 OFF ON 20 30 40 50 60 1 2 3 C R RC RH 1 2 3 24 VAC H1 U M2 D1 H M2 V1 N T2 OR L NOT USED OUT1 OUT2 IN1 IN2 DATS1 DATS2 CONV HP W1 W2 W3 Y Y2 G O B AUX AUX2 Y Y2 G TH9421 VISION PRO THERMOSTAT 24 VOLT TRANSFORMER SYSTEM TRANSFO...

Страница 6: ...relative humidity every 24 hours To increase the relative humidity increase the setpoint approximately three percent relative humidity every 24 hours Setpoint Adjustment Set the humidity setpoint according to the prevailing outdoor temperature Recommended settings are available on the control and in the table below Table 1 Recommended Humidity Controller Settings M24723 Humidity Control Régulateur...

Страница 7: ...H8908A B HUMIDISTAT H8908C D DEHUMIDISTAT 7 69 1341EF 07 ...

Страница 8: ...Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2010 Honeywell International Inc 69 1341EF 07 T D Rev 11 10 Printed in U S A ...

Страница 9: ... produit ou de constituer un danger 2 Vérifier les caractéristiques spécifiées dans les instructions et indiquées sur le produit et s assurer que celui ci correspond à l application prévue 3 L installateur doit être un technicien d expérience ayant reçu une formation pertinente MISE EN GARDE Risque de blessure Peut donner un choc électrique Couper l alimentation avant de procéder à l installation ...

Страница 10: ... DANS UNE PIÈCE 1 Choisir l emplacement de montage dans la pièce REMARQUE Choisir un emplacement à l abri des cou rants d air et de l humidité excessive Ne pas installer l appareil près des portes ou des fenêtres ni dans la salle de bain ou la cuisine Voir la figure 6 Fig 6 Choisir l emplacement dans la pièce 2 Découper un trou de 2 5 cm 1 po pour passer le fil dans le mur 3 Amener un fil double b...

Страница 11: ...tiliser la garniture seulement pour une installation sur une gaine Ne pas l utiliser dans le cas d une installation sur un mur Fig 8 Poser la garniture d étanchéité 5 Poser la plaque de montage sur la gaine ou à l emplacement choisi dans la pièce Fixer à la gaine avec les quatre vis de 25 mm 1 po fournies Fixer au mur avec les deux vis de 25 mm 1 po fournies Fig 9 Poser la plaque de montage sur la...

Страница 12: ...ux fils jaunes au régulateur Les deux fils rouges ne servent que dans le cas de régulateurs d humidité électroniques 6 Utiliser des connecteurs de fils pour raccorder les fils basse tension aux connecteurs de l humidistat H8908 Consulter les Fig 6 19 pour connaître les configurations possibles Fig 10 Raccorder l humidistat 7 Pour monter l humidistat accrocher les deux charnières au haut du couverc...

Страница 13: ...N 20 30 40 50 60 1 2 ALIMENTATION FOURNIR AU BESOIN UN DISPOSITIF DE COUPURE ET UNE PROTECTION CONTRE LES SURCHARGES CÂBLAGE 24 V c a HUMIDIFICATEUR L1 SOUS TENSION TRANSFORMATEUR MF24731 1 1 1 SUIVRE LES INSTRUCTIONS D INSTALLATION DE L HUMIDIFICATEUR À VAPEUR POUR RACCORDER LE VENTILATEUR DU SYSTÈME REMARQUE HUMIDIFICATEUR VERS LE VENTILATEUR DU SYSTÈME BORNES DE L HUMIDISTAT BORNES DE RACCORDEM...

Страница 14: ...éshumidification avec un DH90 FOURNIR AU BESOIN UN DISPOSITIF DE COUPURE ET UNE PROTECTION CONTRE LES SURCHARGES MF24725 1 1 THERMOSTAT VISIONPRO Y2 L A W2 S1 S2 RC R W Y G C H8908D 10 OFF ON 20 30 40 50 60 RELAIS DE CHAUFFAGE OU BOBINE DE LA VANNE BOBINE DU CONTACTEUR DE REFROIDISSEMENT BOBINE DU RELAIS DU VENTILATEUR VENTILATEUR DÉSHUMIDIFICATEUR MF24732 BORNES Fresh Air Ventilation System Systè...

Страница 15: ...e consigne d environ trois pourcents d humidité relative aux 24 heures Pour augmenter le taux d humidité relative augmenter le point de consigne d environ trois pourcents d humidité relative aux 24 heures Réglage du point de consigne Régler le point de consigne d humidité relative en tenant compte de la température extérieure Les réglages recommandés sont indiqués sur le régulateur et dans le tabl...

Страница 16: ...ernational Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com Marque de commerce déposée aux É U 2010 Honeywell International Inc Tous droits réservés 69 1341EF 07 T D Rev 11 10 Imprimé aux États Unis ...

Отзывы: