INSTALLATION INSTRUCTIONS

62-0208—3

H7625A, H7635A 

Humidity/Temperature Sensors

WALL-MOUNT MODELS

APPLICATION

The H7625A, H7635A Wall-Mount Humidity/Temperature 
Sensors are universal Relative Humidity transmitters that 
can be powered with either a +18 to 36 Vdc or 24 Vac 
supply. The sensors use a half-wave bridge rectifier to 
convert AC power to a usable DC voltage. The device 
also includes a 20K ohm temperature sensor for optional 
use.

The humidity sensors are designed with a field selectable 
4 to 20 mA, 0 to 5 Vdc, or 0 to 10 Vdc output signal 
equivalent to 0 to 100% RH. All units are shipped from 
the factory with a default setting to accept AC power with 
three-wire, 0 to 10 Vdc loop-powered output.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a 
hazardous condition.

2.

Check ratings given in instructions and on the 
product to ensure the product is suitable for your 
application.

3.

Installer must be a trained, experienced service 
technician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

CAUTION

Electrical Shock or Equipment Damage 
Hazard.
Can shock individuals or short equipment 
circuitry.

Disconnect power supply before installation.

CAUTION

Equipment Damage Hazard.
Improper wiring can damage the sensor 
beyond repair.

Follow the wiring instructions carefully.

Location

Install the device where it cannot be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall 

behind the device.

Mounting

The housing base mounts over standard 2 in. x 4 in. 
single gang junction box or flush to the wall:

1.

Install the sensor about 5 ft (1.5m) above the floor 
in an area with good air circulation at average 
humidity and temperature. (See Fig. 1.)

2.

Ensure the device receives adequate airflow.

3.

Wire the device. (See Fig. 4 through 3.)

4.

Ensure proper DIP switch settings.

5.

Apply power to the unit.

6.

Snap the cover into position.

7.

Turn out the 1/16 in. allen screws at the bottom of 
the enclosure until the cover cannot be removed.

Fig. 1. Typical sensor location.

5 FEET

(1.5 METERS)

YES

NO

NO

NO

M4823A

Содержание H7625A

Страница 1: ...ician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation CAUTION Equipment Damage Hazard Improper wiring can damage the sensor beyond repair Follow the wiring instructions carefully Location Install the device...

Страница 2: ...g shielded cable ground the shield only at the controller end see Fig 3 Grounding both ends can cause a ground loop NOTE See Table 2 for terminal designations Table 2 Terminal Designations Fig 3 Typical wiring diagram for transducer with two wire mA output with external DC power supply Controller Required Sensor Output Setting 4 Switch Block Settings Blueand White Output Switch LONSPEC Setting 4 3...

Страница 3: ...ISCHARGE AIR SENSOR OUTDOOR AIR SENSOR MOTION SENSOR HUMIDITY SENSOR M OS OS AS AS M HC HP HS Gnd Vin Vo 1 4 L1 HOT L2 COMPRESSOR CONTACTOR 1 COMPRESSOR CONTACTOR 2 HEAT RELAY 1 1 2 3 4 5 6 7 8 9 FAN RELAY ECONOMIZER HEAT RELAY 2 COMPRESSOR CONTACTOR 3 COMPRESSOR CONTACTOR 4 E GND OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 DI 1 DI 2 DI 3 DI 4 GND GND 24 VAC COM 24 VAC COM 24 VAC 24 VAC 24 VAC...

Страница 4: ...nverting Output Signal to Percent RH 4 to 20mA Signal Example 12 mA output signal 12 4 0 16 50 RH 0 to 10 Vdc Signal Example 8 VDC transmitter signal output 8 Vdc 0 10 80 RH Table 3 Troubleshooting signal in mA 4 0 16 percent RH Problem Items to Check No reading Verify correct supply voltage at the power terminal blocks Verify correct wiring configuration and DIP switch settings Verify that termin...

Страница 5: ...mitter always outputs a signal of 4 mA or 0 Vdc The sensor does not affect the transmitter output 50 RH Output for Testing Only Transmitter always outputs a signal of 12 mA 2 5 VDC or 5 VDC The sensor does not affect the transmitter output 100 RH Output Transmitter always outputs a signal of 20 mA 5 VDC or 10 VDC The sensor does not affect the transmitter output Sensor doesn t affect the transmitt...

Страница 6: ...that if your humidity has drifted 1 lower over a certain time period you will be able to toggle the Increment RH Output switch 2 times in order to slide the whole curve upward 1 Decrement RH Output This DIP switch allows calibration in the same way as the Increment RH The difference is that each toggle results in a decrease of 0 5 RH Using Calibration Trim Potentiometers IMPORTANT Due to the sensi...

Страница 7: ...H7625A H7635A HUMIDITY TEMPERATURE SENSORS 7 62 0208 3 ...

Страница 8: ...national Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2005 Honeywell International Inc 62 0208 3 B B Rev 01 05 LonSpec is a trademark of Echelon Corporation ...

Отзывы: