GREEN CLASS METER
9
62-0340-01
MAINS Line Voltage & Current Sensor Wiring Diagrams
LOAD
A
B
C
N
Α Β
C
Ν
G
B W B W B W
Α
Β
C
*
*
*
SOURCE
3-PHASE, 4-WIRE INSTALLATION DIAGRAM
Line Voltage Connections: # 14-22 AWG
Sensor Connections:
B = Black Lead
W = White Lead
* 1/10 A, 600 VAC inline fuse per conductor.
Littlefuse part number KLDR .100.
** Neutral not used in delta system.
Remove neutral terminal block screw for Delta systems.
LOAD
LINE VOLTAGE CURRENT SENSORS
A
B
C
N
Α Β
C
Ν
G
B W B W B W
Α Β
C
*
*
*
SOURCE
3-PHASE, 3-WIRE INSTALLATION DIAGRAM
Line Voltage Connections: # 14-22 AWG
Sensor Connections:
B = Black Lead
W = White Lead
* 1/10 A, 600 VAC inline fuse per conductor.
Littlefuse part number KLDR .100.
** Neutral not used in delta system.
Remove neutral terminal block screw for Delta systems.
The current sensor connection points are located on the
bottom center of the main power board. If supplied with the
terminal block (TB1) (standard configuration), the current sen-
sors are connected to the 6 positions on the right side.
If your meter is equipped with removable current sensor
terminal blocks (ST configuration), you can find the current
censor connection points located on the bottom center of
the main power board. Three removable plugs exist, one
for each current sensor phase input. The header portions
of the connectors are labeled TB2, TB3 and TB4. Text
silkscreened on each of the connectors instruct you which
terminal of the plug is for the white conductor and which
terminal is wired to the black conductor. Once each current
sensor is wired to its respective plug, insert each plug into
the appropriate header.