Power up

Fit the two battery

”

upright inside the backbox

Œ

, in the

correct orientation with the + terminal to the left, between
the 'battery stop brackets'. Connect the battery lead

{

and

link wire

|

as illustrated in the diagram above. The mains

power to the panel can then be switched ON. Power up
from battery only is possible by pressing switch SW2 on
MRC.

Lamp Test

Press the button located on the bottom centre face of the
panel to conduct a 'lamp test'. The test will illuminate
alternate blocks of LEDs so that they can be checked and
sound the two tone internal buzzer for the test duration.

Zonal Mimic overlay

A landscape Zonal Mimic makes use of the zonal overlay
supplied. An editable PDF file of the zonal overlay is
available on the

Gent Expert Forum

(www.gentexpert.co.uk). The file is used for the entry of
zone labels and subsequent printout on to one of the blank
A3 sheets supplied.

Customised Mimic overlay

To create a customised mimic plan use the LED spacing
sheet provided to draw a representation of the protected
building or areas within, such that the layout is drawn
around the LED matrix. The final plan may be drawn using
a CAD package and printed to one of the blank A3 sheets
supplied, to make the customised mimic overlay. To avoid
waste of blank A3 sheets supplied, do a trial print to
normal A3 paper and check the plan for alignment with the
LED matrix.

How fit an overlay

Place the required printed overlay on top of the LEDs and
align the plan such that it fits inside the LED matrix and
hold the overlay in place using the magnetic strip. The
overlay is secured in place when the outer cover is fitted to
the panel.

How to fit the outer cover

Hook



the Outer Cover

Ž

over the top edge of

the Back Box

Œ

. Close

‚

the bottom of the Outer

Cover onto the Back box

and secure the Outer
Cover by the two captive
screws on the cover using

the key



supplied.

Ensure the zonal mimic
or customised mimic
plan is located centrally
within the anti glare
window of the outer
cover.

Data and Installation

A3 Mimic Panel

Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions of changes.

Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK

Website: www.gent.co.uk

Tel44 (0) 116 246 2000

Website: www.gentexpert.co.uk

Fax (UK): +44 (0)116 246 2300

4

4188-945_issue 2_05/10_pt1_A3 Mimic

by Honeywell

Do not dispose of with your normal household waste.
Do not burn.

WEEE Directive:

At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.

At the end of their useful life, the packaging,
product and batteries should be disposed of
via a suitable recycling centre and in
accordance with national or local legislation.

FS2

3.15A(T)
Ceramic

(Anti Surge)

Battery Fuse

BT+

BT

-

+

RS485

0V 24V

-

BUZZER
DISABLE

DANGER
DO NOT
REMOVE

P5

FS2

P1

SW3

PB2

WD1

P14

P7
USB

FS3

2A(QB)

DANGER

WARNING

Removal of

cover exposes

live parts.

+

+

-

-

2 x 6V
7Ah Battery

Back box

Master Repeat Card

Inner Door

Black

Red

Battery lead

Link lead

BATTERY
POWER UP

SW2

Magnetic Strip

Custom Mimic or Zonal
overlay

Mimic panel
Back box with inner door assembly

A

A

Outer Cover

Back box

Содержание Gent Vigilon A3 Mimic

Страница 1: ...ast fire flashing option with in phase or anti phase flash The panel has its own mains derived power supply with battery for standby power in the event of mains supply failure Technical Data Panel dimensions height 403mm width 338mm depth 101mm Weight 7 9Kg without batteries 10 5Kg with batteries Storage temperature 10 to 55ºC Operating temperature 0 to 45ºC Relative humidity Non condensing Up to ...

Страница 2: ...to the top side of the inner door 1 Set Mounting the backbox The A3 Customised Mimic panel can be mounted either landscape or portrait while an A3 Zonal mimic panel must only be mounted landscape when using the overlay supplied a Locate the package Back box assembly u Landscape orientation Portrait orientation b Knock out the required cable entry points from the back box c Mark out the 4 back box ...

Страница 3: ...d j from the back box to the inner door assembly Connect the flat flexible cable k to socket P13 on the Master Repeat Card see details on fitting and remove of flat flexible cable How to disconnect a flat flexible cable Hold the locking tab by the edges at positions j and lift it upwards one side at a time k to disengage the flat flexible cable Then remove the cable l from the socket How to connec...

Страница 4: ...he overlay in place using the magnetic strip The overlay is secured in place when the outer cover is fitted to the panel How to fit the outer cover Hook the Outer Cover over the top edge of the Back Box Close the bottom of the Outer Cover onto the Back box and secure the Outer Cover by the two captive screws on the cover using the key supplied Ensure the zonal mimic or customised mimic plan is loc...

Отзывы: