background image

applications. 

NOTE:

 Intelligent photoelectric smoke sensors are also listed for 

use inside DNR(W) duct smoke detectors. 

WIRING GUIDE

All wiring must be installed in compliance with the National Electrical Code, 

applicable local codes, and any special requirements of the Authority Having 

Jurisdiction. Proper wire gauges should be used. The installation wires should 

be color-coded to limit wiring mistakes and ease system troubleshooting. Im-

proper connections will prevent a system from responding properly in the 

event of a fire.

Remove power from the communication line before installing sensors.

1.   Wire the sensor base (supplied separately) as shown in the wiring 

diagram. (See Figure 2.)

2.   Set the desired address on the sensor address switches. (See Figure 1.) 
3.   Install the sensor into the sensor base. Push the sensor into the base while 

turning it clockwise to secure it in place.

4.   After all sensors have been installed, apply power to the control panel and 

activate the communication line.

5.   Test the sensor(s) as described in the TESTING section of this manual.

CAUTION

Dust covers provide limited protection against airborne dust particles during 

shipping. Dust covers must be removed before the sensors can sense smoke. 

Remove sensors prior to heavy remodeling or construction.

FIGURE 2. WIRING DIAGRAM:

2

3

1

2

3

3

1

2

1

(–)

(+)

+

-

UL Listed Compatib

le

Control P

anel

CAUTION: Do not loop wire under 

terminal 1 or 2.  Break wire run to 

supervise connections.

CLASS A OPTIONAL WIRING

Remote 

Annunciator

(–)
(+)

RA

+

+

RA

+

+

RA

+

+

 

C0129-10

TAMPER-RESISTANCE

Intelligent photoelectric smoke sensors include a tamper-resistant capability 

that prevents their removal from the base without the use of a tool. Refer to 

the base manual for details on making use of this capability.

SPECIFICATIONS

Operating Voltage Range: 

15 to 32 VDC

Operating Current @ 24 VDC:  

200 uA (one communication every 5 seconds with green LED blink on communication)

Maximum Alarm Current:  

2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)

Maximum Current:  

4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)

Operating Humidity Range: 

10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range: 

32°F to 122°F (0°C to 50°C)

Air Velocity: 

0 to 4000 ft./min. (0 to 1219.2 m/min.) 

Height: 

2.0˝ (51 mm) installed in B300-6 Base

Diameter: 

6.2˝ (156 mm) installed in B300-6 Base; 4.1˝ (104 mm) installed in B501 Base

Weight: 

3.4 oz. (95 g)  

Isolator Load Rating:  

0.0063*

*Please refer to your isolator base/module manual for isolator calculation instructions.

UL 268 listed for Open Air Protection. 

UL268A listed for Duct Applications.

This sensor must be installed in compliance with the control panel system 

installation manual. The installation must meet the requirements of the Au-

thority Having Jurisdiction (AHJ). Sensors offer maximum performance when 

installed in compliance with the National Fire Protection Association (NFPA); 

see NFPA 72. 

GENERAL DESCRIPTION

Models ASD-PL3 and ASD-PL3-IV are plug-in type smoke sensors that com-

bine a photoelectronic sensing chamber with addressable-analog communica-

tions.
The sensors transmit an analog representation of smoke density over a com-

munication line to a control panel. Rotary dial switches are provided for set-

ting the sensor’s address. (See Figure 1.) 

FIGURE 1. ROTARY ADDRESS SWITCHES:

 

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

 C0162-00

Two LEDs on the sensor are controlled by the panel to indicate sensor status. 

An output is provided for connection to an optional remote LED annunciator  

(P/N RA100Z). 
Gamewell-FCI panels offer different features sets across different models. As a 

result, certain features of the photoelectric sensors may be available on some 

control panels, but not on others. ASD-PL3 will support only Velociti® Series 

protocol mode. ASD-PL3-IV will support either Velociti or CLIP (Classic Loop 

Interface Protocol) mode. The possible features available if supported by the 

control panel are:
1.   The sensor’s LEDs can operate in three ways—on, off, and blinking–and 

they can be set to red, green, or amber. This is controlled by the panel.  

2.   The remote output may be synchronized to the LED operation or con-

trolled independent of the LEDs.

3.   Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the UL listed control panel for specific 

operation. The photoelectric sensors require compatible addressable com-

munications to function properly. Connect these sensors to listed-compatible 

control panels only.  

SPACING

Gamewell-FCI recommends spacing sensors in compliance with NFPA 72. In 

low air flow applications with smooth ceilings, space sensors 30 feet apart 

(9.1 m). For specific information regarding sensor spacing, placement, and 

special applications, refer to NFPA 72 or the System Smoke Detector Applica-

tion Guide, available from Gamewell-FCI. 

Duct Applications: 

ASD-PL3 and ASD-PL3-IV are listed for use in ducts. See 

Duct Smoke Detectors Applications Guide HVAG53 for details on pendant mount 

I56-6535-00

1

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 

ASD-PL3 and ASD-PL3-IV  

Intelligent Photoelectric Smoke Sensors

12 Clintonville Road

Northford, CT 06472-1653

Phone: 203.484.7161; Fax: 203.484.7118

www.gamewell-fci.com

Velociti® Series 3

  

I56-6535-001 

 

 09/23/2019

Отзывы: