ILI-MB-E3 Product Installation Document —
P/N 9000-0579:M7 07/02/2018
Designation
Description
Comments
ILI-MB-E3 (First and Second Generation) Wiring Designations
TB4-7
SLC 1 B-
SLC 1 Style 4 / 6 / 7 Out (See Note 5)
TB4-8
SLC 1 B+
SLC 1 Style 4 / 6 / 7 Out (See Note 5)
TB5-1
Alarm DC NC
Alarm relay contact, N/C
TB5-2
Alarm DC NO
Alarm relay contact, N/O
TB5-3
Alarm DC Common
Alarm relay contact, Common
TB5-4
Supv DC NC
Supervisory relay contact, N/C
TB5-5
Supv DC NO
Supervisory relay contact, N/O
TB5-6
Supv DC Common
Supervisory relay contact, Common
TB5-7
Trbl DC NC
Trouble relay contact, N/C
TB5-8
Trbl DC NO
Trouble relay contact, N/O
TB5-9
Trbl DC Common
Trouble relay contact, Common
TB6-1
RS-232 GND
For Programming, GND connects to red lead on the download cable P/
N 75267. For Printer Port, GND connects to printer DB-9, PIN-5.
RS-232
Download
or Printer Port
(See Note 9).
TB6-2
RS-232 TxD
For Programming, TxD connects to black lead on the download cable
P/N 75267. For Printer Port, TxD connects to printer DB-9, PIN-2.
TB6-3
RS-232 Supervision
Optional Printer Supervision.
For Printer Port, SUPV connects to printer DB-9, PIN-4.
TB6-4
RS-232 RxD
For Programming, RxD connects to green lead on the download cable
P/N 75267. For Printer Port, RxD connects to printer DB-9, PIN-3.
W1
Factory Jumper
Factory Use Only (Default OUT)
For W2 thru W5 and J7, refer to the subsections: ILI-MB-E3 (First Generation) and ILI-MB-E3 (Second Generation) sections.
W7, W8
Municipal Jumpers
“MB” = For Master Box / Releasing
“PR” = For Polarity Reversal (See Note 7)
W9
Ground Fault Detection
IN = ENABLE
OUT = DISABLE (See Note 1)
SW2-1
Switch
1 ON = SLC 1 DISABLED
(OFF = SLC 1 ENABLED)
SW2-2
Switch
2 ON = SLC 2 DISABLED
(OFF = SLC 2 ENABLED)
SW2-3
Switch
3 ON = NAC 1 & 2 DISABLED
(OFF = NAC 1 & 2 ENABLED)
SW2-4
Switch
4 ON = BUZZER DISABLED
(OFF = BUZZER ENABLED)
SW2-5
Switch
5 ON = RS-232 115.2 K BAUD
(OFF = defined by CAMWorks™)
J1
ILI to PM-9/PM-9G
COMM Port
Connects to PM-9/PM-9G J1. (See Notes 1 & 2)
J2
Local ARCNET
Connects to J5 of the next ILI-E3, ILI95-E3 Series or ANX sub-assembly.(See Note 8)
J4
ARCNET Repeater
Connector
Connects to INI-VG Series (First/Second/Third Generation) J7 or J10 of the RPT-E3-UTP
(See Note 4).
J5
Local ARCNET
Connects to J2 from the previous ILI-E3, ILI95-E3 Series or ANX sub-assembly.
(See Note 8).
ILI-MB-E3 (First Generation) Designations
W2
Factory Jumper
Factory Use Only (Default OUT)
Used for the
ILI-MB-E3, (First
Generation) only.
W3
Factory Jumper
Factory Use Only (Default OUT)
W4
ARCNET Termination
OPEN = Normal Operation
SHORT = If the ILI-MB-E3 is located at the end of the ARCNET bus.
W5
RS-485 AUX Terminal
OPEN = OFF
SHORT = ON (RS-485 Termination)
Table 3.5.1.1 ILI-MB- E3 Wiring Designations (Continued)