ILI-MB-E3

Intelligent Loop Interface-Main Board

Product Installation Document

Document 9000-0579:M7

07/02/2018

ECN 18-0058

Section 1: Description

The ILI-MB-E3 (Intelligent Loop Interface-Main Board) is the main circuit board. When the ILI-MB-E3 is connected to the 
network, it is compatible with the following systems.

It provides terminals for the connection of all of the sub-assemblies. The ILI-MB-E3 sub-assembly can support the following 
modules:

The ILI-MB-E3 supports the System Sensor protocol using Velociti

®

 mode. In Velociti mode, each Signaling Line Circuit (SLC) 

supports 159 detectors and 159 modules. When the unit is used in conjunction with the RPT-E3-UTP Repeater sub-assembly, J2, 
and/or J5 connected, each unit occupies one node on the Broadband network. Figure 1.1 illustrates the ILI-MB-E3 (First 
Generation) module, and Figure 1.2 illustrates the ILI-MB-E3 (Second Generation) module.

!

CAUTION: STATIC SENSITIVE EQUIPMENT

THIS EQUIPMENT IS SENSITIVE TO STATIC ELECTRICITY. IT MAY BE DAMAGED IF NOT PROPERLY HANDLED. 
TRANSPORT AND STORE THIS UNIT IN A STATIC-SHIELDING BAG. 
FAILURE TO OBSERVE THIS REQUIREMENT COULD CAUSE LATENT DAMAGE TO THE EQUIPMENT WHICH 
MIGHT NOT MANIFEST ITSELF UNTIL AFTER THE EQUIPMENT IS PLACED IN SERVICE.

!

CAUTION: DISCONNECT ALL POWER

REMOVE ALL SOURCES OF POWER BEFORE SERVICING, REMOVING OR INSTALLING ANY UNITS.

E3  Series

®

 Fire Alarm and Mass Notification System 

(Autonomous Control Unit)

E3 Series Broadband System 

E3 Series (Expandable Emergency Evacuation) System

E3 Series Classic System (for Fire applications only)

NOTE:

The E3 Series nodes may be networked with the S3 Series System.

up to a total of 16 ASM-16 and/or

DACT-E3

up to a total of 16 ANU-48 Remote LED Driver Modules

LCD-E3 or LCD-SLP

NOTE:

Use the Signaling Line Circuit (SLC) devices for Fire and/or E3 Series Releasing applications.

ILI-MB-E3 (First Generation)

ILI-MB-E3 (Second Generation)

Figure 1.1 ILI-MB-E3 (First Generation) Module

Figure 1.2 ILI-MB-E3 (Second Generation) Module

Содержание Gamewell FCI ILI-MB-E3

Страница 1: ...module CAUTION STATIC SENSITIVE EQUIPMENT THIS EQUIPMENT IS SENSITIVE TO STATIC ELECTRICITY IT MAY BE DAMAGED IF NOT PROPERLY HANDLED TRANSPORT AND STORE THIS UNIT IN A STATIC SHIELDING BAG FAILURE TO OBSERVE THIS REQUIREMENT COULD CAUSE LATENT DAMAGE TO THE EQUIPMENT WHICH MIGHT NOT MANIFEST ITSELF UNTIL AFTER THE EQUIPMENT IS PLACED IN SERVICE CAUTION DISCONNECT ALL POWER REMOVE ALL SOURCES OF P...

Страница 2: ...ries Inc 2018 Copyright by Honeywell International Inc All rights reserved Autonomous Control Unit ACU Main Command Center E3 LOC Remote Command Center E3 Broadband System Distributed System AM 50 Series Amplifiers AOM TELF AOM 2SF AM 50 Series Amplifiers ANU 48 Remote Annunciator ASM 16 Addressable Switch Module ANU 48 Remote Annunciator ASM 16 Addressable Switch Module INI VG Series First Second...

Страница 3: ...on Installers must be Gamewell FCI Factory Certified to program this product For additional information on this product contact the Gamewell FCI Customer Support to schedule the Factory Certified Training 2 3 Specifications The following list the electrical specifications for the ILI MB E3 NFPA 72 National Fire Alarm Code UL 864 Control Units for Fire Alarm Systems Ninth Edition UL 2017 General Pu...

Страница 4: ... 3 8 W x 30 H x 4 1 2 D 49W x 76H x 11 4D cm Section 2 5 2 Cabinet D E3 INX D Plate E3 INX D PLATE 19 3 8 W x 41 H x 4 1 2 D 49W x 104H x 11 4D cm Section 2 5 2 Cabinet D E3 INCC D Plate E3 INCC D PLATE 19 3 8 W x 41 H x 4 1 2 D 49W x 104H x 11 4D cm Section 2 5 2 E3 Series Combined Fire and MNS System Installation Options Cabinet C E3 INCC CAB C Plate ACU E3 INCC CPLATE 19 3 8 W x 30 H x 4 1 2 D ...

Страница 5: ...B C D Retrofit DR C4 DR D4 and EQ Cabinets Installation Instructions P N LS10082 000GF E E3 Series Remote Annunciator Display and Retrofit Cabinets Installation Instructions P N LS10083 000GF E 2 5 1 ILI MB E3 Installed to the Cabinet B Backbox 1 Align and mount the ILI MB E3 to the studs in the backbox 2 Insert eight standoffs 3 16 hex 4 40 x 1 25 in the eight hole mounting pattern and secure the...

Страница 6: ...3 16 HEX x 4 40 x 1 25 into the eight hole mounting pattern and secure the standoffs to the E3 Series mounting plate as shown in Location 1 of the figure below Note PCA orientation Figure 2 5 2 1 illustrates the ILI MB E3 installed to the Cabinet C E3 INCC C Plate Figure 2 5 2 1 ILI MB E3 Installed to an E3 Series Mounting Plate E3 Series Cabinet C E3 Series Cabinet D E3 INCC C Plate E3 INCC D Pla...

Страница 7: ... the screws to the B SLIM E3 plate as shown in Location 1 of the figure below 2 Insert the eight standoffs 3 16 HEX 4 40 x 1 25 into the eight hole mounting pattern and secure the standoffs to the retrofit cabinet mounting plate as shown in Location 1 of the figure below NOTE Use standoffs to mount the DACT E3 RPT E3 UTP or the ANX on top of the ILI MB E3 Figure 2 5 3 1 1 illustrates the ILI MB E3...

Страница 8: ... impedance 0 5 µf max line capacitance Ground fault test impedance Zero Ohms Wiring 18 AWG minimum twisted pair unshielded Class 2 Power Limited Supervised E3 Series Releasing Feature To actuate the E3 Series Releasing feature use the signaling line circuit Honeywell model TC810S1000 Releasing Control Module For additional information on the Honeywell TC810S1000 device refer to the Honeywell TC810...

Страница 9: ...ring Circuit Ratings 24 VDC Nominal Max alarm load 2 0 A circuit Special Application 0 2 A Regulated Ground fault test impedance Zero ohms Wiring 18 AWG minimum Class 2 Power Limited Supervised ILI MB E3 Second Generation End of Line Resistor ILI95 MB E3 End of Line Resistor For the ILI MB E3 use UL Listed End of Line Resistor model ELR 47K for Class B Style Y wiring The model ELR 47K is supplied ...

Страница 10: ...eed 0 5 microfarads RS 485 Class 2 Power Limited Connects to LCD E3 LCD SLP ASM 16 ANU 48 and LCD 7100 RAN 7100 modules Twisted unshielded pair with a characteristic impedance of 120 Ohms 18 AWG 0 78 mm2 minimum 3 000 ft 914 m maximum 16 AWG 1 30 mm2 RS 232 Class 2 Power Limited Connects to Printers CRT or PC Twisted unshielded pair 18 AWG 0 78 mm2 minimum 50 15 24 without modem 16 AWG 1 30 mm2 NA...

Страница 11: ... 8 NAC 2 A Notification Appliance Circuit 2 See Note 6 TB3 1 AUX RS 485 A Output to LCD E3 LCD SLP ASM 16 ANU 48 LCD 7100 RAN 7100 DACT E3 See Note 3 TB3 2 AUX RS 485 B Output to LCD E3 LCD SLP ASM 16 ANU 48 LCD 7100 RAN 7100 DACT E3 See Note 3 TB3 3 Earth Ground Connect to water pipe ground TB3 4 Resettable B Auxiliary resettable 24 VDC power TB3 5 GND Common negative TB3 6 Non resettable B Auxil...

Страница 12: ...Port RxD connects to printer DB 9 PIN 3 W1 Factory Jumper Factory Use Only Default OUT For W2 thru W5 and J7 refer to the subsections ILI MB E3 First Generation and ILI MB E3 Second Generation sections W7 W8 Municipal Jumpers MB For Master Box Releasing PR For Polarity Reversal See Note 7 W9 Ground Fault Detection IN ENABLE OUT DISABLE See Note 1 SW2 1 Switch 1 ON SLC 1 DISABLED OFF SLC 1 ENABLED ...

Страница 13: ... Port TB3 1 COM A TB3 2 COM B to connect to the LCD E3 E3 annunciator module LCD SLP E3 S3 annunciator module LCD 7100 RAN 7100 7100 Remote Annunciator Module ASM 16 Addressable Switch Module ANU 48 LED Annunciator Driver Module or DACT E3 E3 Digital Communicator Transmitter NOTE 4 RPT E3 UTP E3 Repeater Module is required when this ILI MB E3 is networked via ARCNET to any of the following INI VGE...

Страница 14: ...1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 on 9 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 10 on 1 7 8 4 6 5 3 2 on 25 1 7 8 4 6 5 3 2 on 26 on 27 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 on 33 on 34 1 7 8 4 6 5 3 2 on 35 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 on 36 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 on 39 1 7 8 4 6 5 3 2 on 40...

Страница 15: ...RE RESISTANCE PER LOOP 0 5µF MAX CAPACITANCE PER LOOP NAC1 CLASS B OUT NAC1 CLASS A RETURN NAC2 CLASS B OUT NAC2 CLASS B OUT NAC2 CLASS A RETURN NAC2 CLASS A RETURN NAC1 CLASS A RETURN NAC1 CLASS B OUT NOTE 7 NAC1 NAC2 ARE RATED AS 2 0 A SPECIAL APPLICATION AND 0 2 A REGULATED 5 6 7 8 NOTE 6 NAC1 NAC2 TYPICAL STYLE Y CLASS B NAC USE A UL LISTED EOL RESISTOR RANGE LISTED IN TABLE 3 1 1 OR TYPICAL S...

Страница 16: ...ISTED PAIR 18 AWG MIN 40 OHMS MAX WIRE RESISTANCE PER LOOP 0 5µF MAX CAPACITANCE PER LOOP NAC1 CLASS B OUT NAC1 CLASS A RETURN NAC2 CLASS B OUT NAC2 CLASS B OUT NAC2 CLASS A RETURN NAC2 CLASS A RETURN NAC1 CLASS A RETURN NAC1 CLASS B OUT NOTE 7 NAC1 NAC2 ARE RATED AS 2 0 A SPECIAL APPLICATION AND 0 2 A REGULATED 5 6 7 8 NOTE 6 NAC1 NAC2 TYPICAL STYLE Y CLASS B NAC USE 33KOHM 1 2 W EOL RESISTOR OR ...

Страница 17: ...ANX Addressable Node Expander Use the ANX for Fire applications only E ILI S E3 Intelligent Loop Interface Expander Board Use up to eight ILI S E3 modules in an E3 Series configuration F ILI95 S E3 Intelligent Loop Interface95 Expander Board Display Panels G ANU 48 Remote LED Driver Assembly H ASM 16 Addressable Switch Module I LCD E3 LCD Display Module J LCD SLP Liquid Crystal Display Small Loop ...

Страница 18: ... Board Installation Instructions 9000 0580 RPT E3 UTP Repeater E3 Unshielded Twisted Pair Installation Instructions 9000 0581 DACT E3 Digital Alarm Communicator Transmitter Installation Instructions 9000 0582 LCD E3 Liquid Crystal Display E3 Installation Instructions 9001 0017 ILI95 MB E3 Intelligent Loop Interface 95 Main Board Installation Instructions 9001 0018 ILI95 S E3 Intelligent Loop Inter...

Отзывы: