background image

LOC Operation Instructions for FIRE Overrides Mass Notification —

 P/N LS10037-000GF-E:A  03/21/13

2

ACU TRANSFER OF CONTROL

Activation and Control of the MNS functions is required to 
be restricted to only one location at one time. During an 
MNS event, the location of the Active Control displays on 
all NGA display locations. The ACU can override any LOC-
In-Control and can seize control at anytime.

If an MNS state is already in effect and the Control status 
resides in an LOC, the Operator at the ACU may override 
the LOC by the activation of any ASM-16 button dedicated 
to any Mass Notification function.

To Transfer Control to the ACU, the Operator does the 
following:
1.

Press any configured switch on the ASM-16 to 
relinquish control from an LOC.

2.

On the ASM-16, the red LED (next to the configured 
switch) turns off and the green LED turns on. 

3.

After the green LED (next to the configured switch) 
turns on, the Operator can take control of the ACU.

RESET PAGE

To reset the Page or MIC, do the following:
1.

Press Switch 9 on the ASM-16.

2.

On Switch 9, the red and green LEDs turn on.

3.

Key the MIC, on the ASM-16, the green LED turns off 
and the yellow and red LEDs turn on.

4.

Release the MIC, on the ASM-16, the yellow LED 
turns off and the red LED remains on.

5.

To reset the Page, do either of the following:
• Press Switch 9 on the ASM-16.
• Wait until the preconfigured Time-Out occurs.

6.

After the page is reset, on the ASM-16, the red LED 
turns off and the green LED turns on.

NGA LED INDICATORS

The NGA operates its LEDs by active conditions initiated 
by the System. The following lists the NGA LED Indicators 
and Functions.

Description  

LED

Function

Power On

Green    Lights steady green when 

powered ON.

Alarm

Red

Blinks red until you press 

ACK

 

button. Then lights steady red until 
you clear all Alarm Events.

Supervisory

Yellow   Blinks yellow until you press 

ACK

 

button. Then lights steady yellow 
until you clear all Supervisory 
Events.

System 
Trouble

Yellow Blinks yellow until you press 

ACK

 

button. Then lights steady yellow 
until you clear all System Trouble 
Events.

Ground Fault

Yellow Lights steady yellow when a 

ground fault is present.

The following lists the NGA Diagnostic LED Indicators:

Designation Label

Description

LED1

REC

Network is reconfiguring.            

LED2

MRC

This node is initiating a network 
reconfiguration.

LED3

DUP

Duplicate node address or 
switch error.

LED4

TX

The sub-assembly is 
transmitting network data.

LED5

RX

The sub-assembly is receiving 
network data.

LED6

RST

Firmware Fault

LED7

DG

Trouble condition

NGA TOUCHSCREEN TABS AND BUTTONS

For additional information on the NGA’s touchscreen tabs 
and buttons, refer to the following documents:

Mass Notification System (MNS) Installation/Operation 
Manual, P/N: LS10013-000GF-E

NGA Installation Instructions, P/N: 9000-0568

ASM-16 LED INDICATORS

There are three (3) LEDs for each of the sixteen (16) 
switches on the ASM-16 module, totaling 48 LEDs. The 
standard LEDs and descriptions are listed as follows:

Red LED      

Control Not available

Green LED 

Control Available

Yellow LED

Control Fault

The ASM-16 slide-in labels identify the switch and LED 
functions required by the Facilities Management and 
approved by the AHJ.

For additional information on Mass Notification, refer to the 

Mass Notification System (MNS) Installation/Operation 
Manual, P/N: LS10013-000GF-E

.

SERVICE CALLS:

NOTE: THIS EQUIPMENT IS TO BE SERVICED BY ONLY 
AUTHORIZED PERSONNEL. FOR SERVICE, CALL:

For ready reference, the ACU Operating Instructions must 
be framed and placed adjacent to the control unit.

Отзывы: