Introduction

The Galaxy V-Plex Interface supports 128 sensors and 64 outputs. If required additional V-pex interfaces can 
be connected to the RS485 line.
The interface connects directly to the Galaxy RS485 communication bus, and is programmed directly from a 
standard Galaxy keypad connected to the module.

Galaxy V-Plex Interface Layout

Connecting the V-Plex Interface

Connect the V-Plex Interface terminals as in 

V-Plex Connections

,

 

below:

Honeywell Security - Newhouse Industrial Estate - Motherwell - Lanarkshire - ML1 6SB - UK 

 

 

 

Part No.II1-0077 Rev. 2.01     p. 1

V

-Plex Interface - English

V-Plex bus
connection

Processor

Retaining slot

Alternative programming
keypad socket

Tamper
bypass
switch

Programming
switch

SW3

SW4

PL 2

SW2

PANEL

KEYPAD

PROGRAMMING HEADER

PL1

Tamper
switch

V-Plex Interface

Connected to

+

+12 V (at control panel, keypad or remote 
power supply)

-

0V or ground (at control panel, keypad or 
remote power supply)

A

To the A terminal of the previous module on the 
line (or the control panel if the V-Plex Interface 
is the 

fi

 rst module on the line)

B

To the B terminal of the previous module on the 
line (or the control panel if the V-Plex Interface 
is the 

fi

 rst module on the line)

V-Plex Connections for Panel & Keypad Terminals

V-Plex Tamper

If the Galaxy panel is not in Engineer Mode, removing the lid of the enclosure will cause a tamper alarm. 
Switch SW2 can be used to temporarily bypass the tamper switch. Closing SW3 will bypass the tamper 
protection.

Galaxy V-Plex Interface Programming Menu

Programming 

Entering Programming Mode

To enter V-Plex Interface Programming Mode:

Ensure that the Galaxy panel is in Engineer Mode.

1. 

Address a keypad as 0 and connect it to the keypad terminals of the V-Plex Interface.

2. 

Close the programming switch (SW4).

3. 

The V-Plex Interface is now in Programming Mode and the keypad displays a language selection option.

Language Selection

LANGUAGE SELECT

00=ENGLISH

03=ITALIANO

06=ESPANOL

01=NEDERLANDS

04=FRANCAIS

07=CZECH

02=SVENSK

05=FLEMISH

08=SLOVAK

10 = PROG MODULE

20 = PROG ZONES 001-128

30 = PROG OUTPUTS 001-154

2 = Device ID

Enter Number

A=YES

B=NO

11 = Cold start

12 = RIO Address 00-15

0 = Disable

1 = Enable

1 = Type

0 = Serial Poll

1 = Dip SW Poll

2 = Loop No

1 = Loop 1

2 = Loop 2

3 = Device ID

1 = Manual

2 = Self learn

1 = Type

0 = Serial Poll

1 = Dip SW Poll

OPTION 10 - PROG MODULE

OPTION 11 - Cold Start

This option loses all programming by restoring the Non-Volatile Memory to the default values.

OPTION 12 - RIO Address

This option allows the programming of up to 16 simulated RIO modules. The RIO address must be 
enabled to allow zone and output programming of its zone and output addresses. An enabled address is 
shown as 

; a disabled address is shown as 

.

After a cold start, or with a new module, all addresses are disabled.